Technical Data
09.02
14-2
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
R/R unit
6SE70..-.....-1AA0 22-1EC85 24-1EC85 28-6EC85
Rated voltage, rated frequency, rated current
Rated voltage
Rectifier connection
Regenerative connection
DC link voltage
V
3AC 200V –10% to 230V +15% or
3AC 380V –15% to 480V +10%
using an (auto) transformer
1.2 times the voltage of the rectifier connection
DC 270V –10% to 310V +15% or
DC 510V –15% to 650V +10%
Rated frequency f
n
Input
Output
Hz
46 to 64 (automatic frequency matching)
DC
Rated current
(rms value)
With autotransformer
Regenerating,
line
side
Regenerating,
unit
side
Rectifier
operation
Without autotransformer
Regenerating,
unit
side
Rectifier
operation
A
20
17
18
17
18
40
33
36
33
36
82
68
74
68
74
Load class I to EN 60146-1-1 of the DC link current (average value)
in rectifier operation; currents reduced to 92% in regenerative operation
Rated current
(average)
DC link connection
Rectifier
operation
A 21 41 86
Load class II to EN 60146-1-1 of the DC link current (average value)
in rectifier operation; currents reduced to 92% in regenerative operation
Rated
current
A
19 37 78
Base load duration
s
240
Excess current
A
29
56
117
Excess current duration
s
60
Losses, cooling
Power dissipation
−
Maximum
kW
0,14 0,19 0,31
Cooling air requirement
m
3
/s
0,028 0,028 0,028
Sound pressure level, dimensions, weight
Sound pressure level
dB(A)
60
60
60
Size
Width
Height
(without securing bracket)
Depth
mm
mm
mm
C
180
600
350
C
180
600
350
C
180
600
350
Weight app.
kg
23
23
23
https://www.aotewell.com