background image

Connection 

09.02 

3-58

 

Siemens AG    6SE7087-6AK85-1AA0 

 

Rectifier/Regenerating Unit    Operating instructions 

 

Parameterizing a unit as a 12-pulse slave (see Section 3.8.3)

 

Using P077 = 5 or 6, almost all settings required for the parameterization as a 12-pulse slave can be carried 
out automatically (see Chapter 4.3.9.1).  
Meaning of P077 = 5 or 6: 

P077= 5:  Basic setting (index i001): 12-pulse slave (all control is carried out via the master) 

Reserve setting (index i002): stand-alone unit with operator control via PMU 

P077= 6:  Basic setting (index i001): 12-pulse slave (all control is carried out via the master) 

Reserve setting (index i002): stand-alone unit with operator control via OP1S 

Note: When the reserve setting is selected, the unit operates as a stand-alone unit with on-site operator 
control. Changeover between the basic and reserve settings takes place via binary input 5 (P590=1005), but 
the reserve setting can be set permanently via P590= 1. 

Procedure for carrying out the P077-dependent factory setting (see Section 4.3.9.1):  

  Set P051= 3 (expert mode)  

  Set P052= 2 (Select "Initialize" function (set MLFB), so that P077 can be modified)  

  Set P077= 5 or 6 (Select the required P077-dependent parameter setting)  

  Set P052= 0 and press the <P> key (terminate the "initialize" function)  

  Set P052= 1 (select the function "Generate manufacturer setting"; when  the <P> key is pressed, all 

parameters are reset to their factory setting or to the P077-dependent value)  

 

If only those parameter values that are dependent on P077 are required to be changed and all other 
parameters should remain unchanged, the following procedure is necessary: 

  Set P051= 3 (expert mode) 

  Set P052= 2 (select "Initialize" function (set MLFB)) 

  Note P070 and set P070= 0 

  Set P077= 5 or 6 (select the required P077-dependent parameter setting) 

  Set P052= 0 and press the <P> key (read in the parameter values dependent on P077) 

  Move the F060 error message into the "background" by pressing <P>+<H> 

  Set P052= 2  (select "Initialize" function (set MLFB) again) 

  P070= noted value (restore MLFB) 

  P052= 0 and press the <P> key (MLFB is read in and the dependent parameters P071, P075 and P076 

are set) 

  Move the F060 error message into the "foreground" again by pressing <P>+<T>, and reset by pressing 

the <P> key 

 

Additional parameter settings for the 12-pulse slave: 

  P051= 3 (expert mode) 

  P688 = 1 (Peer-to-Peer protocol) 

  Switch off earth short-circuit test (P354 = 0), when the unit is supplied from an unearthed supply, e.g. 

from the delta winding of the 12-pulse transformer 

  For factory settings in accordance with  P077= 5 or 6, binary input 1 is a source for "No external fault 1" 

and binary input 2 is a source for "No external warning 1". If this is not required, e.g. in the case of open 
terminals, P575 = 1 and P588 = 1 must be set. 

 

https://www.aotewell.com

AoteWell Automation Sales Team

Sales@aotewell.com

AoteWell LTD

Buy Siemens PLC HMI Drives at AoteWell.com

https://www.aotewell.com

Summary of Contents for 6SE7022-1EC85-1AA0

Page 1: ...enerating Unit Sizes C to K Operating Instructions Edition i Order No 6SE7087 6AK85 1AA0 https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 2: ...ructions or that some parameters might have an extended setting range Leave such parameters in their factory setting and on no account set any values that are not described in these operating instructions You can order the latest software version EPROM under MLFB No 6SW1701 0DA14 The reproduction transmission or use of this document or contents is not permitted without express written authority Of...

Page 3: ...ing unit PMU 3 18 3 4 Measures for keeping to RFI suppression regulations 3 19 3 5 Single line diagrams with suggested circuit arrangements 3 20 3 6 Power sections 3 28 3 7 Parallel connection of parallel unit s size K 3 47 3 7 1 Single line diagrams with suggested circuit arrangements for parallel connection 3 50 3 8 12 pulse mode only possible with the optional RS485 interface 3 52 3 8 1 General...

Page 4: ... 23 4 16 4 3 1 1 6 Selecting the source for control word 2 bit 24 31 4 17 4 3 1 1 7 Significance of control word 1 and 2 commands 4 18 4 3 1 2 Status word status word 1 and status word 2 4 23 4 3 1 2 1 Introduction and application example 4 23 4 3 1 2 2 Overview of the status word status word 1 and status word 2 4 24 4 3 1 2 3 Selecting the destinations for the status word bits 0 31 4 25 4 3 1 2 4...

Page 5: ... with CAN Layer 2 4 62 4 5 3 2 Diagnostic tools 4 66 4 5 4 Sequence of operations for starting up the serial I O board SCB1 4 69 4 5 4 1 SCB1 as master for SCI1 and SCI2 4 70 4 5 4 2 SCB1 as peer to peer interface 4 71 4 5 4 3 Diagnostic tools 4 71 4 5 5 Sequence of operations for starting up the SCB2 board 4 72 4 5 6 Structure of request response telegrams 4 73 5 Parameter list 5 1 5 1 Operation ...

Page 6: ...istor blocks for size H 8 12 8 2 5 2 Disassembling the thyristor blocks for size K 8 13 9 Options 9 1 9 1 Options which can be integrated into the electronics box 9 1 9 2 Interface boards 9 3 9 3 Power Supply 9 4 9 4 Operator control panel OP1S 9 4 9 5 Mechanical design 9 6 9 6 RS485 interface PTP1 9 6 9 6 1 Order designation 9 6 9 6 2 Installation 9 7 9 6 3 Function and terminal description 9 7 9...

Page 7: ... Environmental compatibility 13 1 14 Technical data 14 1 14 1 Power reduction at increased coolant temperature 14 10 14 2 Power reduction at altitudes 1000m above MSL 14 10 14 3 Applied standards 14 11 https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 8: ...s AG 6SE7087 6AK85 1AA0 Rectifier Regenerating Unit Operating Instructions https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 9: ...injury CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided may result in property demage NOTICE NOTICE used without the safety alert symbol indicates a potentially situation which if not avoided may result in an undesireable result or state NOTE For reasons of clarity these operating instructions do not contain all details of all types of t...

Page 10: ...lms insulating desktops or synthetic fibber clothing items Modules must only be placed on conductive surfaces When soldering modules the tip of the soldering iron must be earthed Modules and components must only be stored or dispatched in conductive packaging e g metallized plastic boxes or metal tins If packagings are not conductive modules must be placed in a conductive envelopment prior to pack...

Page 11: ... is not permitted to open the housing until after waiting for 5 minutes Non observance of warning notices can result in death severe personal injury or considerable property damage Such personnel must be thoroughly acquainted with all warnings and maintenance activities Perfect and safe operation of the equipment requires proper transport expert storage installation and assembly and cautious opera...

Page 12: ...ens AG 6SE7087 6AK85 1AA0 Rectifier Regenerating Unit Operating Instructions https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 13: ...d by connecting power sections of size K in parallel Up to 2 parallel units of the same rated current can be connected in parallel with one basic unit see Section 3 7 for further details on parallel connection You can make technological adaptations and expansions over a defined interface in the control section Harmonic loading on the supply network can be reduced by coupling 2 units for 12 pulse m...

Page 14: ... K on the electronics box Operation is performed via the terminal strip or via a serial interface Optional interfaces and intelligent I O modules are available in conjunction with programmable controllers and other automation equipment for controlling the rectifier regenerating units https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at...

Page 15: ...d The packaging may be disposed of in accordance with local cardboard disposal regulations You should notify your freight forwarder immediately if you discover any transportation damage 2 2 Storage The units must be stored in clean dry rooms Temperatures between 25 C 13 F and 70 C 158 F are permissible Temperature fluctuations 20 K per hour are not permissible 2 3 Assembly The following are requir...

Page 16: ...ust be dry and dust free Air fed in must not contain any gases vapors or dusts that are electrically conductive or detrimental to functioning Air containing dust must be filtered WARNING Dimension cabinet ventilation according to the dissipated power Technical data in Chapter 14 The unit s ambient climate in operating rooms must not exceed the values of code 3K3 as detailed in DIN IEC 721 Part 3 3...

Page 17: ...X48 R77 R78 R75 R76 A23 X300 5 F10 54 Z Options PMU max 5 7 Detail Z 1 Mounting hole for screw M6 2 Hook suspension for mounting on a g rail according to EN50035 3 Space required for cooling the unit 4 Screen connection for two cables 5 Shock hazard protection 6 Connector for power supply DC24V and main contactor No displacement of the centre of gravity Weight refer to section 14 technical data Di...

Page 18: ...SE7034 2HE85 1AA0 500 400 6SE7035 3HE85 1AA0 600 500 Weight refer to section 14 1 Mounting hole for screw M8 2 Mounting hole for power connections M16 for 6SE7036 1EE85 1AA0 6SE7035 4FE85 1AA0 6SE7034 2HE85 1AA0 and 6SE7035 3HE85 1AA0 M12 for every other units 3 Connection for PE mounted M16 for 6SE7036 1EE85 1AA0 6SE7035 4FE85 1AA0 6SE7034 2HE85 1AA0 and 6SE7035 3HE85 1AA0 M12 for every other uni...

Page 19: ...unting with M8 bolts Front view 1 Mounting hole for M12 screw 2 M12 thread 3 Screen connection for cables 4 Connector for 24 V DC power supply and main contactor 5 Fan connection 6 Remove transport plates before start up 7 For cabinet installation Insulate this part of the unit against the cabinet walls and door When the units are installed in cabinets it must be ensured that the air intake and ex...

Page 20: ...the air intake and exhaust is adequate for air requirements and intake air temperature see Section 14 Technical Data No displacement of the centre of gravity Weight refer to Section 14 Technical Data Dimension mm 1 Mounting hole for M12 screw 2 M12 thread 3 Screen connection for cables 4 Connector for 24 V DC power supply and main contactor 5 Fan connection 6 Remove transport plate and transport c...

Page 21: ...de Order No for three busbars Unit Order No 6SE7032 7FE87 3AE0 6SE7031 7EE85 1AA0 6SE7032 2EE85 1AA0 6SE7033 1EE85 1AA0 6SE7031 5FE85 1AA0 6SE7032 4FE85 1AA0 6SE7032 7FE85 1AA0 6SE7032 7HE87 3AE0 6SE7033 8EE85 1AA0 6SE7034 6EE85 1AA0 6SE7033 5FE85 1AA0 6SE7034 2FE85 1AA0 6SE7031 4HE85 1AA0 6SE7032 2HE85 1AA0 6SE7032 7HE85 1AA0 6SE7034 2HE87 3AE0 6SE7036 1EE85 1AA0 6SE7035 4FE85 1AA0 6SE7034 2HE85 ...

Page 22: ...0 2 8 Siemens AG 6SE7087 6AK85 1AA0 Rectifier Regenerating Unit Operating Instructions https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 23: ...may carry a voltage even when the motor is at standstill When working on the open unit pay attention to the fact that live parts are exposed The unit may only be operated with the front covers attached The user is responsible for ensuring that the common rectifier converter motor and other units are installed and connected in accordance with the technical regulations recognized in the country of i...

Page 24: ...ns connection size E 1U2 1T1 1V2 1T2 1W2 1T3 C L D L PE2 V1 L2 U1 L1 W1 L3 PE1 X9 X19 Mains Autotransformer regen system Mains fan DC link DC output 1 1 Figure 3 3 Mains connection size H 1U2 1T1 1V2 1T2 1W2 1T3 PE1 V1 L2 W1 L3 C L D L U1 L1 PE2 X9 X19 Mains Mains fan DC link DC output 1 1 Autotransformer regen system Figure 3 4 Mains connection size K 1 Due to the press in nuts cable lugs or DC r...

Page 25: ...lied to the rectifier and regenerating power terminals U1 L1 V1 L2 W1 L3 and 1U2 1T1 1V2 1T2 1W2 1T3 must have an identical phase angle and identical frequency Recommendation The inductive components of the impedance drop uk of the auto transformer should lie between 1 5 and 3 see Table 3 4 Commutating reactor Selection of the reactors for 4 uk should be based on the rated current in regenerative ...

Page 26: ...T2A 250V time lag 5x20 mm 19198 T2A 250V Messrs Wickmann Werke GmbH or 0034 3993 FSD Messrs Schurter Sizes H and K Terminal X19 fused with fuse F3 and F4 T2A 250V time lag 6 3x32 mm x 1 19343 T7A 250V Messrs Wickmann Werke GmbH or 0034 5243 FST Messrs Schurter WARNING If the device is operated on a network in which a phase is grounded instead of the neutral the plant operator must ensure that fans...

Page 27: ...x300 2x600 240 500 36 1EE85 1AA0 380 to 480 526 2x240 2x500 2x300 2x600 300 600 38 2EH85 1AA0 380 to 480 710 C 4x300 R 100x10 4x600 C 4x300 R 60x10 4x600 C 4x300 R 100x10 4x600 41 0EH85 1AA0 380 to 480 888 C 4x300 R 100x10 4x600 C 4x300 R 60x10 4x600 C 4x300 R 100x10 4x600 41 3EK85 1AA0 380 to 480 1156 C 4x300 R 100x10 4x600 C 6x300 R 100x10 6x600 C 4x300 R 100x10 4x600 41 3EK85 1AD0 380 to 480 11...

Page 28: ...6x600 C 4x300 R 100x10 4x600 31 4HE85 1AA0 660 to 690 123 2x120 2x4 0 2x150 2x300 70 2 0 32 2HE85 1AA0 660 to 690 193 2x120 2x4 0 2x150 2x300 95 3 0 32 7HE85 1AA0 660 to 690 234 2x120 2x4 0 2x150 2x300 120 4 0 34 2HE85 1AA0 660 to 690 366 2x240 2x500 2x300 2x600 185 350 35 3HE85 1AA0 660 to 690 465 2x240 2x500 2x300 2x600 300 600 37 7HH85 1AA0 660 to 690 671 C 4x300 R 100x10 4x600 C 4x300 R 60x10 ...

Page 29: ...3 550 170M6693 34 2FE85 1AA0 500 3NE3334 0B 35 4FE85 1AA0 630 3NE3336 800 170M6696 31 4HE85 1AA0 160 3NE3224 32 2HE85 1AA0 315 3NE3230 0B 350 170M6689 32 7HE85 1AA0 350 3NE3231 34 2HE85 1AA0 560 3NE3335 35 3HE85 1AA0 630 3NE3336 800 170M6696 Table 3 3 Recommended mains fuses Table 3 3 Semiconductor protection only lines are not reliably protected CAUTION Devices of sizes C and E require semiconduc...

Page 30: ... 50 170L3834 1 24 1FC85 1AA0 63 3NE4118 80 170L3836 1 27 2FC85 1AA0 100 3NE4121 125 170L3838 1 28 8FC85 1AA0 160 3NE4124 31 5FE85 1AA0 200 3NE3225 250 170M3695 32 4FE85 1AA0 315 3NE3230 0B 400 170M4693 32 7FE85 1AA0 350 3NE3231 450 170M4694 33 5FE85 1AA0 450 3NE3333 550 170M4696 34 2FE85 1AA0 500 3NE3334 0B 700 170M5697 35 4FE85 1AA0 710 3NE3337 8 900 170M5699 31 4HE85 1AA0 200 3NE3225 250 170M369...

Page 31: ...0M5696 41 5HK85 1AD0 710 3NE3337 8 630 170M5696 41 8HK85 1AA0 800 3NE3338 8 800 170M5698 41 8HK85 1AD0 800 3NE3338 8 800 170M5698 Table 3 5 Built in branch fuses 3 1 1 Short circuit withstand capability for sizes H and K In the event of a line side short circuit in front of the super fast built in fuses the power fed in from the supply depends on the protective devices provided on the system side ...

Page 32: ...36 1EE85 1AA0 380 to 480 526 581 4EU3651 4UB00 400 50 460 60 560 38 2EH85 1AA0 380 to 480 710 784 4EU3951 6UA00 400 50 460 60 710 41 0EH85 1AA0 380 to 480 888 980 4EU3951 1UB00 400 50 460 60 910 41 3EK85 1AA0 380 to 480 1156 1276 4EU4351 3UA00 400 50 460 60 1120 41 3EK85 1AD0 380 to 480 1156 1276 4EU4351 3UA00 400 50 460 60 1120 41 8EK85 1AA0 380 to 480 1542 1702 4EU4351 7UA00 400 50 460 60 1600 4...

Page 33: ... 5HK85 1AD0 660 to 690 1306 1442 4EU5051 0UA00 690 50 1250 41 8HK85 1AA0 660 to 690 1633 1803 4EU5251 0UA00 690 50 1600 41 8HK85 1AD0 660 bi 690 1633 1803 4EU5251 0UA00 690 50 1600 Table 3 6 Recommended commutating reactor Unit Order No Rated input current Feed back current Line voltage range 15 Autotransformer Duty factor Autotransformer Duty factor Volt Freq 100 25 6SE70 A A V Hz 22 1EC85 1AA0 1...

Page 34: ... 26 500 50 60 4AP3095 0UA31 8A 4AP2795 0UA61 8A 600 60 4AP3095 0UA51 8A 4AP2595 0UA01 8A 24 1FC85 1AA0 36 40 500 50 60 4AU3695 0UA41 8A 4AP2795 0UA71 8A 600 60 4AP3695 0UA01 8A 4AP2795 0UA31 8A 27 2FC85 1AA0 62 69 500 50 60 4AU3995 0UA21 8A 4AP3095 0UA81 8A 600 60 4AP3695 0UA11 8A 4AP3095 0UA61 8A 28 8FC85 1AA0 82 90 500 50 60 4AU3995 0UA31 8A 4AU3695 0UA31 8A 600 60 4AU3995 0UA71 8A 4AU3095 0UA01...

Page 35: ... 8A 31 4HE85 1AA0 123 136 660 690 50 60 4BU4795 0UA31 8A 4BU4395 0UA31 8A 32 2HE85 1AA0 193 213 660 690 50 60 4BU5295 0UA21 8A 4BU4595 0UA51 8A 32 7HE85 1AA0 234 258 660 690 50 60 4BU5395 0UA31 8A 4BU4795 0UA51 8A 34 2HE85 1AA0 366 404 660 690 50 60 4BU5595 0UA11 8A 4BU5295 0UA31 8A 35 3HE85 1AA0 465 514 660 690 50 60 4BU5895 0UA31 8A 4BU5395 0UA51 8A 37 7HH85 1AA0 671 741 660 690 50 60 4BU6095 0U...

Page 36: ...t options 1A for basic unit master 0 3A for parallel unit slave X9 2 Reference potential for DC X9 1 X9 3 not connected N C X9 4 Main contactor control circuit X9 5 Main contactor control circuit Table 3 8 Connector X9 pin assignments for auxiliary power supply and main contactor control Terminal X9 1 fused with fuse F1 T2A 250V time lag 5x20mm 19198 T2A 250V Messrs Wickmann Werke GmbH or 0034 399...

Page 37: ...protect ESD endangered components in the introductory chapter entitled General 3 3 1 Connectors for the control terminal block Conductors with cross sectional areas of 0 14 to 1 5 mm2 AWG 26 to 16 or 1 mm2 AWG 18 finely stranded with core end ferrules can be connected to the connectors Recommended 0 5 mm2 AWG 20 3 3 2 Connecting the control leads NOTICE When installed control leads must be shielde...

Page 38: ...lamps are sharp edged Ø 15mm Ø 7 5mm Ø 5mm Figure 3 6 Connecting the control leads and handling the shielding clamps If two shielding clamps cannot cope with the number of control leads on the Size C unit the EMC shielding enclosure option should be used Order number Size C 6SE7090 0XC87 3CA0 3 3 3 Terminals and setting elements on the CUR A10 module X100 X101 X102 PMU X104 R135 R136 S1 S2 A10 CUR...

Page 39: ...d please refer to the description of these modules Electronics terminals Function Terminal Connected loads Description Serial interface RS485 Bus X100 1 X100 2 X100 3 X100 4 X100 5 RS485P Plus line Send and receive RS485N Minus line line RS485P Plus line difference input output RS485N Minus line Signal frame For functions see Section 4 3 6 1 Binary inputs X101 6 X101 7 X101 8 X101 9 X101 10 X101 1...

Page 40: ...automation unit or a PC can be realized via connector X300 on the PMU The cables must be shielded and connected to ground at both ends See Sec 3 3 2 Thus the rectifier regenerating unit can be controlled and operated from the central control station or control room Figure 3 8 Parameterizing unit PMU PMU X300 Description 1 Housing ground 2 Receive line RS232 standard V 24 3 Transmit and receive lin...

Page 41: ...terference and observe the radio interference suppression levels shielded cable must be used between the converter output and the motor and shielded control cables laid The shield must be connected to ground potential at both ends Filters The radio interference filters must be connected before the infeed unit The housings must be interconnected conductively To observe the radio interference suppre...

Page 42: ...6 10nF M BI 10nF A01 BO S2 M 150Ω 390Ω 390Ω M P5 X117 1 2 3 4 5 RS485 M RS485 TTL X115 X116 R15 R16 N P N P A2 C98043 A1690 K1 2 X9 3 X9 4 X9 5 RESET F1 F2 5V 15V 15V 24V L_DSAVE X9 1 X9 2 RS485 OP1S DriveMonitor RS232 DriveMonitor K1 Load Filter optional Power supply 24V power supply unit Option modules binary selecting inputs analog outputs binary selecting outputs Microprocessor selection Open ...

Page 43: ...F A01 BO S2 M 150Ω 390Ω 390Ω M P5 X117 1 2 3 4 5 RS485 M RS485 TTL X115 X116 R15 R16 N P N P A2 C98043 A1690 K1 2 X9 3 X9 4 X9 5 RESET F1 F2 5V 15V 15V 24V L_DSAVE X9 1 X9 2 RS485 OP1S DriveMonitor RS232 DriveMonitor A10 X101 K1 Load Filter optional Power supply 24V power supply unit Option modules binary selecting inputs analog outputs binary selecting outputs Microprocessor selection Open and cl...

Page 44: ...AC 50 60Hz 400V 3AC 50 60Hz 500V 3AC 50 60Hz 690V 1AC 50 60Hz 230V F3 F4 X19 1 X19 2 M 1 X29 1 M P5 X117 1 2 3 4 5 RS485 M RS485 TTL X115 X116 R15 R16 N P N P A2 C98043 A1690 RS485 OP1S DriveMonitor RS232 DriveMonitor K1 Load Filter optional Power supply 24V power supply unit Option modules binary selecting inputs analog outputs binary selecting outputs Microprocessor selection Open and closed loo...

Page 45: ...SAVE X9 1 X9 2 3AC 50 60Hz 400V 3AC 50 60Hz 500V 3AC 50 60Hz 690V 1AC 50 60Hz 230V F3 F4 X19 1 X19 2 M 1 X29 1 M P5 X117 1 2 3 4 5 RS485 M RS485 TTL X115 X116 R15 R16 N P N P A2 C98043 A1690 RS485 OP1S DriveMonitor RS232 DriveMonitor A10 X101 K1 Load Filter optional Power supply 24V power supply unit Option modules binary selecting inputs analog outputs binary selecting outputs Microprocessor sele...

Page 46: ...N P N P A2 C98043 A1690 X27 RESET F1 F2 5V 15V 15V 24V L_DSAVE K1 2 X9 1 F5 X9 2 X9 3 X9 4 X9 5 X9 1 X9 2 X9 3 X9 4 X9 5 3AC 50 60Hz 400V 3AC 50 60Hz 500V 3AC 50 60Hz 690V 1AC 50 60Hz 230V RS485 OP1S DriveMonitor RS232 DriveMonitor 12 12 6 6 K1 Voltage measurement Fuse monitoring Load Filter optional Power supply 24V power supply unit Option modules binary selecting inputs analog outputs binary se...

Page 47: ...0 X27 RESET F1 F2 5V 15V 15V 24V L_DSAVE K1 2 X9 1 F5 X9 2 X9 3 X9 4 X9 5 X9 1 X9 2 X9 3 X9 4 X9 5 K1 3AC 50 60Hz 400V 3AC 50 60Hz 500V 3AC 50 60Hz 690V 1AC 50 60Hz 230V RS485 OP1S DriveMonitor RS232 DriveMonitor 12 12 6 6 ϑ A10 X101 1U1 1U1 1V1 1V1 1W1 1W1 2U1 2V1 2W1 Voltage measurement Fuse monitoring Load Filter optional Power supply 24V power supply unit Option modules binary selecting inputs...

Page 48: ...R16 N P N P A2 C98043 A1690 X27 RESET F1 F2 5V 15V 15V 24V L_DSAVE K1 2 X9 1 F5 X9 2 X9 3 X9 4 X9 5 X9 1 X9 2 X9 3 X9 4 X9 5 3AC 50 60Hz 400V 3AC 50 60Hz 500V 3AC 50 60Hz 690V 1AC 50 60Hz 230V RS485 OP1S DriveMonitor RS232 DriveMonitor 12 12 6 6 K1 Voltage measurement Fuse monitoring Load Filter optional Power supply 24V power supply unit Option modules binary selecting inputs analog outputs binar...

Page 49: ...A1690 X27 RESET F1 F2 5V 15V 15V 24V L_DSAVE K1 2 X9 1 F5 X9 2 X9 3 X9 4 X9 5 X9 1 X9 2 X9 3 X9 4 X9 5 3AC 50 60Hz 400V 3AC 50 60Hz 500V 3AC 50 60Hz 690V 1AC 50 60Hz 230V RS485 OP1S DriveMonitor RS232 DriveMonitor 12 12 6 6 ϑ A10 X101 1U1 1U1 1V1 1V1 1W1 1W1 2U1 2V1 2W1 K1 Voltage measurement Fuse monitoring Load Filter optional Power supply 24V power supply unit Option modules binary selecting in...

Page 50: ...2 U1 L1 X24 X21 X26 X23 X22 X25 X11 X14 X13 X16 X15 X12 T3 1W2 1T3 T4 1V2 1T2 1U2 1T1 X1 X4 k X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 D L V23 26 V25 22 V21 24 V11 14 V13 16 V15 12 k l T1 T2 K L K L l k R76 R78 R75 R77 F2 T3 2A X9 4 X9 3 X9 5 F1 T2A X9 1 X9 2 K1 2 F10 C D U1 V1 W1 1U2 1V2 1W2 X30 1 X30 2 X239 X20 1 X20 2 X20 1 1 X20 1 2 M E1 N C PE A23 C98043 A1681 A23 C98043 A1681 A23 C980...

Page 51: ...E1 T3 T4 T1 T2 A23 C98043 A1682 A23 C98043 A1682 A601 C98043 A1683 A10 X109 C98043 A1680 R11 R14 R13 R16 R15 R12 R21 R24 R23 R26 V25 V22 V23 V26 V21 V24 W1 L3 V1 L2 U1 L1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 C L D L G2 K2 G2 K2 G1 K1 G2 K2 G1 K1 G1 K1 AK A K AK A K AK A K X24 X21 X26 X23 X22 X25 F10 V11 14 V13 16 V15 12 AK K AK K AK K G2 G1 G2 G1 G2 G1 X14 X11 X16 X13 X12 X15 A A A G1 K1 G2 K2 G1 K1 G2 K...

Page 52: ...1 1 X26 1 X26 2 X23 2 X23 1 X22 1 X22 2 X25 2 X25 1 A K AK A K AK A K AK K A AK K A AK K A AK X48 1 X48 4 X47 1 X47 3 X47 4 X47 2 k l K L K L l k R76 R78 R75 R77 R80 R79 X30 1 X30 2 M 1 ϑ X239 F4 T2A X29 2 X29 1 X29 3 F3 T2A X19 1 X19 2 K101 2 230V N C X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE R100 E1 A10 X109 C98043 A1680 T3 T4 T1 T2 R15 R12 R11 R14 R13 R16 R25 R22 R21 R24 R23 R26 A601 C...

Page 53: ... R79 X30 1 X30 2 M 1 ϑ X239 F4 T2A X29 2 X29 1 X29 3 F3 T2A X19 1 X19 2 K101 2 230V N C X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE R100 E1 A10 X109 C98043 A1680 T3 T4 T1 T2 R15 R12 R11 R14 R13 R16 A601 C98043 A1683 A23 C98043 A1682 A23 C98043 A1682 R24 R21 R26 R23 R25 R22 V25 V22 V23 V26 V21 V24 W1 L3 V1 L2 U1 L1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 C L D L G2 K2 G2 K2 G1 K1 G2 K2 G1 K1 G1 K1 AK ...

Page 54: ... 1 X30 2 M 1 ϑ X239 F4 T2A X29 2 X29 1 X29 3 F3 T2A X19 1 X19 2 K101 2 230V AK AK AK K K K A A A A A A K K K AK AK AK V15 V12 K2 G2 G1 K1 X12 X15 V13 V16 K2 G2 G1 K1 X16 X13 V11 V14 K2 G2 G1K1 X14 X11 V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V21 V24 K2 G2 G1 K1 X24 X21 W1 L3 T2 V1 L2 U1 L1 T1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 F10 C L D L X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 P...

Page 55: ... K AK AK AK V15 V12 K2 G2 G1 K1 X12 X15 V13 V16 K2 G2 G1 K1 X16 X13 V11 V14 K2 G2 G1K1 X14 X11 V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V21 V24 K2 G2 G1 K1 X24 X21 W1 L3 T2 V1 L2 U1 L1 T1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 F10 C L D L D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 X4 1U2 1V2 1W2 ...

Page 56: ... X25 2 V25 R25 C25 G25 K25 K X12 2 X12 1 V12 R12 C12 K12 G12 A A K XW25 F25 F22 F21 F24 F23 F26 X47 3 X47 2 k l K L K L l k X47 1 X47 4 T1 T2 X48 3 X48 2 k l K L K L l k X48 1 X48 4 T3 T4 PE X1 U1 L1 V1 L2 W1 L3 X4 1U2 1T1 1V2 1T2 1W2 1T3 R75 R77 R76 R78 R79 R80 X29 2 X29 1 X29 3 K101 2 M 1 E1 X20 1 X20 2 X31 1 X31 2 ϑ R100 F2 T7A X9 4 X9 3 X9 5 F1 T2A X9 1 X9 2 K1 2 N C A23 C98043 A1685 X239 F5 T...

Page 57: ...23 V25 V12 V11 V13 V15 V22 V26 V24 Level B rear level Level A front level Figure 3 24 Arrangement of the thyristor blocks Size H see dimension drawing in Section 2 4 https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 58: ... V16 R16 C16 K16 G16 A A K XV23 X25 1 X25 2 V25 R25 C25 G25 K25 K X12 2 X12 1 V12 R12 C12 K12 G12 A A K XW25 X47 3 X47 2 k l K L K L l k X47 1 X47 4 T1 T2 X48 3 X48 2 k l K L K L l k X48 1 X48 4 T3 T4 PE X4 1U2 1T1 1V2 1T2 1W2 1T3 R75 R77 R76 R78 R79 R80 X1 U1 L1 V1 L2 W1 L3 F112 F111 F141 F142 F132 F131 F161 F162 F152 F151 F121 F122 X32 1 X32 2 ϑ R101 M 1 E1 230V X20 1 X20 2 F242 F241 F211 F212 F...

Page 59: ...4 V21 V16 V23 V15 V22 V12 V25 Level B Level A Figure 3 26 Arrangement of the thyristor blocks view from right hand side of unit Size K see dimension drawing in Section 2 4 https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 60: ...1U2 1V2 1W2 X30 1 X30 2 ϑ X239 AK G1 G2 AK G1 G2 A AK G1 G2 K T2 C L W1 L3 T1 A K A K V1 L2 U1 L1 X11 X14 X13 X16 X15 X12 T3 1W2 1T3 T4 1V2 1T2 1U2 1T1 X1 X4 D L V11 14 V13 16 V15 12 F10 M AK G2 G1 AK G2 G1 A AK G2 G1 K A K A K X24 X21 X26 X23 X22 X25 V21 24 V23 26 V25 22 X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE A23 C98043 A1681 A23 C98043 A1681 A23 C98043 A1681 R100 E1 A10 X109 C98043 A...

Page 61: ...682 A23 C98043 A1682 A601 C98043 A1684 R15 R12 R11 R14 R13 R16 R24 R21 R26 R23 R25 R22 R100 E1 A10 X109 C98043 A1680 T3 T4 T1 T2 G1 K1 G2 K2 G1 K1 G2 K2 G1 K1 G2 K2 X24 1 X24 2 V21 V24 V23 V26 V25 V22 X21 2 X21 1 X26 1 X26 2 X23 2 X23 1 X22 1 X22 2 X25 2 X25 1 K A AK K A AK K A AK V25 V22 V23 V26 V21 V24 W1 L3 V1 L2 U1 L1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 C L D L G2 K2 G2 K2 G1 K1 G2 K2 G1 K1 G1 K1 AK...

Page 62: ...U1 V1 W1 L1 L2 L3 PE D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 A601 C98043 A1684 A602 C98043 A1684 R14 R11 R16 R13 R15 R12 R24 R21 R26 R23 R25 R22 R100 E1 A10 X109 C98043 A1680 T3 T4 T1 T2 A23 C98043 A1682 A23 C98043 A1682 V25 V22 V23 V26 V21 V24 W1 L3 V1 L2 U1 L1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 C L D L...

Page 63: ... K1 X12 X15 V13 V16 K2 G2 G1 K1 X16 X13 V11 V14 K2 G2 G1K1 X14 X11 V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V21 V24 K2 G2 G1 K1 X24 X21 W1 L3 T2 V1 L2 U1 L1 T1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 F10 C L D L X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1...

Page 64: ... T2A X29 2 X29 1 X29 3 F3 T2A X19 1 X19 2 K101 2 230V AK AK AK K K K A A A A A A K K K AK AK AK V15 V12 K2 G2 G1 K1 X12 X15 V13 V16 K2 G2 G1 K1 X16 X13 V11 V14 K2 G2 G1K1 X14 X11 V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V21 V24 K2 G2 G1 K1 X24 X21 W1 L3 T2 V1 L2 U1 L1 T1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 F10 C L D L X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE A23 C98043 A1682 A23...

Page 65: ... R79 AK AK AK K K K A A A V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V21 V24 K2 G2 G1 K1 X24 X21 W1 L3 V1 L2 U1 L1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 F10 C L D L X30 1 X30 2 M 1 ϑ X239 F4 T2A X29 2 X29 1 X29 3 F3 T2A X19 1 X19 2 K101 2 230V X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE A23 C98043 A1682 A601 C98043 A1684 A23 C98043 A1682 R15 R12 R11 R14 R13 R16 R25 R22 R21 R24 R23 R26 ...

Page 66: ...U1 V1 W1 L1 L2 L3 PE D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 A23 C98043 A1682 A602 C98043 A1684 A23 C98043 A1682 A601 C98043 A1684 R14 R11 R16 R13 R15 R12 R24 R21 R26 R23 R25 R22 R100 E1 A10 X109 C98043 A1680 T3 T4 T1 T2 AK AK AK K K K A A A V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V2...

Page 67: ...V12 K2 G2 G1 K1 X12 X15 V13 V16 K2 G2 G1 K1 X16 X13 V11 V14 K2 G2 G1K1 X14 X11 V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V21 V24 K2 G2 G1 K1 X24 X21 W1 L3 T2 V1 L2 U1 L1 T1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 F10 C L D L X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 V1 1 V1 2 W1 1 W1 2 D C 1U2 1 1U2 2 1V2 1 1V2 2 1W2 1 1W2 2 U1 1 U1 2 ...

Page 68: ...V AK AK AK K K K A A A A A A K K K AK AK AK V15 V12 K2 G2 G1 K1 X12 X15 V13 V16 K2 G2 G1 K1 X16 X13 V11 V14 K2 G2 G1K1 X14 X11 V25 V22 K2 G2 G1 K1 X22 X25 V23 V26 K2 G2 G1 K1 X26 X23 V21 V24 K2 G2 G1 K1 X24 X21 W1 L3 T2 V1 L2 U1 L1 T1 1W2 1T3 T4 1U2 1T1 T3 1V2 1T2 F10 C L D L X4 1U2 1V2 1W2 1T1 1T2 1T3 X1 U1 V1 W1 L1 L2 L3 PE A23 C98043 A1682 A23 C98043 A1682 R24 C24 R26 C26 R22 C22 C21 R21 C23 R2...

Page 69: ...basic and parallel units The parallel units have the same technical data as the corresponding basic units The parallel units do not include a CUR electronic module and are fitted with a C98043 A1695 A23 Power Interface module instead of a C98043 A1685 A23 Power Interface module The parallel units do not require a separate external 24V power supply via X9 The contactor for the parallel unit s is co...

Page 70: ...nit 1 Rectification Regeneration Basic unit Rectification Regeneration Parallel unit 2 Rectification Regeneration Parallel unit 1 Rectification Regeneration Basic unit Rectification Regeneration Parallel unit 2 Rectification Regeneration Arrangement for low power system Identical fuses for basic unit and parallel unit s Identical cable lengths leading to the power section connections of the basic ...

Page 71: ...ring for current asymmetry over current or under current in the parallel power section as compared to the current in the basic unit F034 that is not active The results of the thyristor test selected via P353 are only conditionally applicable when units are connected in parallel Start up The start up procedure is exactly the same as in the case of a single basic unit The final cabling parallel conn...

Page 72: ...20V DC 675V 780V DC 890V 930V K1 2 3AC 50 60Hz 400V 3AC 50 60Hz 500V 3AC 50 60Hz 690V 1AC 50 60Hz 230V 12 12 6 6 K1 K3 6 6 K2 Power section parallel unit Load Filter optional to electronics module A10 X109 Parallel unit Basic unit Connections for second parallel unit Filter optional Fan unit Termistor Load Fan unit Power section basic unit 24V power supply unit Termistor Voltage measurement Fuse m...

Page 73: ... 50 60Hz 230V 12 12 6 6 K1 K3 6 6 ϑ 1U1 1U1 1V1 1V1 1W1 1W1 2U1 2V1 2W1 A10 X101 ϑ 1U1 1U1 1V1 1V1 1W1 1W1 2U1 2V1 2W1 A10 X101 K2 Power section parallel unit Load Filter optional to electronics module A10 X109 Parallel unit Basic unit Connections for second parallel unit Filter optional Fan unit Termistor Load Fan unit Power section basic unit 24V power supply unit Termistor Voltage measurement F...

Page 74: ...of the 3 phase AC supplies are decoupled on the line side line side with respect to the unit terminals through inductances due to the secondary leakage inductance of the 12 pulse transformer commutating reactors and in the regenerative direction also due to the leakage inductance of the autotransformers if present Note A 12 pulse transformer alone is not always sufficient for decoupling because th...

Page 75: ...link Mains Autotransformer Reactor 12 pulse slave Rectification Regeneration 12 pulse master Rectification Regeneration 12 pulse transformer 12 pulse transformer Reactor Reactor Reactor Autotransformer Autotransformer Autotransformer 12 pulse slave Rectification Regeneration 12 pulse master Rectification Regeneration Figure 3 39 Power section supply with autotransformers b Power section supply wit...

Page 76: ...Reactor Reactor Reactor Reactor Autotransformer Auto transformer Autotransformer Autotransformer Auto transformer Auto transformer 12 pulse master Rectification Regeneration 12 pulse slave Rectification Regeneration Parallel unit Rectification Regeneration Parallel unit Rectification Regeneration Parallel unit Rectification Regeneration Parallel unit Rectification Regeneration Figure 3 41 Example ...

Page 77: ... 3 but should only be parameterized when the 12 pulse master is required to go into the fault state in the event of a 12 pulse slave fault see Section 3 8 6 Use of SST2 receive data P554 i001 or i002 6001 ON OFF1 P555 i001 or i002 6001 not OFF2 with the fault state for the 12 pulse master or when no 12 pulse mode is selected on the 12 pulse master see P583 i001 or i002 OFF2 is signaled P561 i001 o...

Page 78: ...Unit high state Unit is a comon rectifier P070 100 P070 101 r599 6 Message DC link forming or current identification is being carried out r599 7 r550 7 fault reset r599 8 r550 8 typing 1 ON AND r552 3 no fault AND r551 23 12 pulse mode is selected r599 9 r550 9 typing 2 ON AND r552 3 no fault AND r551 23 12 pulse mode is selected r599 10 r550 10 PLC control r599 11 r550 11 Ud reduction requested r...

Page 79: ...prevented until the 12 pulse slave reports the run operating state via r599 bit 3 of the first SST2 receive data or until a maximum waiting time of 5 s has elapsed During this waiting time the 12 pulse slave is given the opportunity of carrying out the earth short circuit test In addition ramping up of the pre charging ramp parameter P329 is prevented Bits 0 1 8 and 9 of r599 control status word f...

Page 80: ... key is pressed all parameters are reset to their factory setting or to the P077 dependent value If only those parameter values that are dependent on P077 are required to be changed and all other parameters should remain unchanged the following procedure is necessary Set P051 3 expert mode Set P052 2 select Initialize function set MLFB Note P070 and set P070 0 Set P077 5 or 6 select the required P...

Page 81: ...n Uninterrupted changeover of the 12 pulse master unit to stand alone 6 pulse mode in the event of failure of the 12 pulse slave unit during 12 pulse mode If the 12 pulse master is required to continue to run in normal stand alone 6 pulse mode in the event of failure of the 12 pulse slave unit without interruption External fault 3 must not be wired to the Peer to Peer interface but instead the par...

Page 82: ...link on SST2 is in the form of a four wire connection A screened 4 core cable must be connected at the screw terminals of the 5 pole plug of terminal block X117 on submodule A2 C98043 A1690 Submodule A2 is fitted to the CUR A10 electronics module see Section 9 6 The 4 core cable is not included in the scope of delivery X117 1 2 3 4 5 A2 X117 1 2 3 4 5 A2 M M 12 pulse master 12 pulse slave Figure 3...

Page 83: ...ower supply of the variable voltage DC link of SIMOVERT converters of the 6SEE70 series Mode variants a The line voltage in the regenerative branch is stepped up by an auto transformer to prevent having to reduce the DC link voltage in regenerating mode b Permanent reduction of the DC link voltage by phase angle control in rectifier mode in order to always be able to feed power back into the syste...

Page 84: ... second rectifier regenerating unit with the current setpoint The second rectifier regenerating unit that is linked to the first via the SST2 serial interface RS485 interface option with peer to peer protocol only becomes a 12 pulse slave after parameterization 12 pulse mode is used to reduce the harmonic loading on the system and to increase the performance for high power rectifier regenerating u...

Page 85: ...fic data record is accessed see the function diagram for selecting the data sets in Section 4 4 There are two types of data set Data sets for basic reserve setting B R can be selected via control word 2 bit 30 Associated source selection parameter P590 Affected parameters P486 P554 to P557 P561 P565 to P569 P571 to P575 P578 P579 P583 and P586 to P589 e g for changing over between manual and autom...

Page 86: ...t up instructions Section 4 1 Forming If the inverter s connected have been switched off continuously or not connected for more than a year is their link capacitors must be formed see Section 4 3 9 6 Connect up the supply and electronics power supply of the converter with the front panel closed The rectifier regenerating unit is supplied with the factory setting refer to Section 5 Parameter list c...

Page 87: ...d mode Parameterization enable e g with P053 6 the parameters from the parameterization unit PMU and from serial interface 1 of the basic unit SST1 and therefore also from the optional user friendly operator panel OP1S can be modified Operator control If the unit is to be switched on and off via the optional user friendly operator panel OP1S P554 2001 Source for control command ON OFF1 P555 2001 S...

Page 88: ...tch on Press the I key on the PMU Circuit identification takes place takes about 10 s Following circuit identification the operating display is activated If an error occurs during circuit identification the identification process must be repeated error value r949 assigned to error memory r947 can provide more information on the cause of error if the error in index i009 has been reset see Sections ...

Page 89: ... of the basic unit SST1 and therefore also from the optional user friendly operator panel OP1S can be modified Operator control If the unit is to be switched on and off via the optional user friendly operator panel OP1S P554 2001 Source for control command ON OFF1 P555 2001 Source for control command OFF2 Drive setting Supply voltage V Value of the rated voltage at the rectifier bridge Configurati...

Page 90: ...on via terminal X101 12 binary input 4 P613 1001 message DC link voltage reduced output at alarm relay X104 17 18 ready for regenerative feedback P319 Hysteresis for the message DC link voltage reduced ready for regenerative feedback c2 Automatic reduction of the DC link voltage depending on the DC link current only implemented on Software Version 3 2 and higher and not shown in the adjacent diagr...

Page 91: ...mmand and setpoint sources Destinations for signals and actual values Process data refer to Section 4 3 1 Control word commands status word messages Setpoint actual values Possible process data sources destinations refer to Sections 4 3 2 to 4 3 6 Binary inputs binary outputs Analog inputs Serial interface in the basic unit SST1 SST2 SST2 only with optional RS485 interface PTP1 Option boards SCB C...

Page 92: ...6 P24 X101 9 BE1 X101 10 BE2 X101 11 BE3 X101 12 BE4 X101 13 BE5 X102 15 AAM X102 14 AA Manual automatic operation Automatic operation BE5 high signal level Command input from the automation unit via serial interface SST1 the monitoring of external faults via a terminal strip also possible Manual operation BE5 low signal level Command input via the terminal strip CUR SST1 P554 2 2001 P565 2 2001 S...

Page 93: ...ting i002 Reserve setting An overview of possible sources which are assigned fixed values 0 6005 non consecutively are provided in Section 4 3 1 1 3 to 4 3 1 1 6 Selecting the source for the control word In this overview values 0 and 1 are an exception sources are not selected with these values but the bits are set permanently to 0 LOW or 1 HIGH also refer to select parameters P554 to P591 in Sect...

Page 94: ... Word4 Control word bit Select parameter Basic set Reserve set Value Source Changeover using control word bit 30 P590 6001 to 6005 SST1 Peer to Peer word 1 to word 5 Meaning ON OFF1 Basic set via PMU keys I 0 Reserve set via bin input 1 of CUR Op cond OFF2 Basic set Constant value 1 always op cond Reserve set Constant value 1 always op cond Note For OFF2 and OFF3 3 selection parameters can be assi...

Page 95: ...ed P572 1 13 No fault external 3 Fault external 3 P573 1 14 Motoring Generating Specification of the direction of supply P574 1 15 No fault external 1 Fault external 1 P575 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 16 PMU Display Control word 2 visualization parameter r551 Bit High Low Comments Source selection 16 17 18 RDS reserve data set bit 0 LSB Logic operation with bit 19 P578 1 19 RDS re...

Page 96: ...2 x x x x Consecutively to x x x x 4110 BE10 x x x x 4111 only SCI 2 Slave 1 BE11 x x x x 4112 BE12 x x x x Consecutively to x x x x 4116 BE16 x x x x 4201 SCI 1 and 2 Slave 2 BE1 x x x x 4202 BE2 x x x x Consecutively to x x x x 4210 BE10 x x x x 4211 only SCI 2 Slave 2 BE11 x x x x 4212 BE12 x x x x Consecutively to x x x x 4216 BE16 x x x x 4501 SCB SST USS Peer t Peer Word1 x x x x 4504 SCB SS...

Page 97: ...lave 1 BE1 x x x x x x x 4102 BE2 x x x x x x x Consecutively to x x x x x x x 4110 BE10 x x x x x x x 4111 only SCI 2 Slave 1 BE11 x x x x x x x 4112 BE12 x x x x x x x Consecutively to x x x x x x x 4116 BE16 x x x x x x x 4201 SCI 1 and 2 Slave 2 BE1 x x x x x x x 4202 BE2 x x x x x x x Consecutively to x x x x x x x 4210 BE10 x x x x x x x 4211 only SCI 2 Slave 2 BE11 x x x x x x x 4212 BE12 x...

Page 98: ...x 4101 SCI 1 and 2 Slave 1 BE1 x x x 4102 BE2 x x x Consecutively to x x x 4110 BE10 x x x 4111 only SCI 2 Slave 1 BE11 x x x 4112 BE12 x x x Consecutively to x x x 4116 BE16 x x x 4201 SCI 1 and 2 Slave 2 BE1 x x x 4202 BE2 x x x Consecutively to x x x 4210 BE10 x x x 4211 only SCI 2 Slave 2 BE11 x x x 4212 BE12 x x x Consecutively to x x x 4216 BE16 x x x 4501 SCB SST USS Peer t Peer Word1 4504 ...

Page 99: ...BE1 x x x x x x 4102 BE2 x x x x x x Consecutively to x x x x x x 4110 BE10 x x x x x x 4111 only SCI 2 Slave 1 BE11 x x x x x x 4112 BE12 x x x x x x Consecutively to x x x x x x 4116 BE16 x x x x x x 4201 SCI 1 and 2 Slave 2 BE1 x x x x x x 4202 BE2 x x x x x x Consecutively to x x x x x x 4210 BE10 x x x x x x 4211 only SCI 2 Slave 2 BE11 x x x x x x 4212 BE12 x x x x x x Consecutively to x x x...

Page 100: ...l After the command has been accepted The rectifier regenerating unit discharges the DC link with the fixed discharge ramp of 2 s to about 20 of 1 35 P071 The firing pulses are then inhibited and the main contactor if installed drops out If the OFF1 command is removed again ON command during the discharge process the latter is interrupted and changeover is made again to the RUN 014 status If the r...

Page 101: ... If no faults are present The drive changes into the status SWITCH ON INHIBIT 008 If actual faults are present The drive remains in the FAULT status 007 NOTE The acknowledge command is simultaneously effective from three sources P565 P566 and P567 and always from the PMU Bit 8 Inching 1 ON command Inching 1 ON The command is executed with a positive edge change from L to H L H only in the READY TO...

Page 102: ...e abruptly If it is odd the setpoint is ramped down according to the discharge time in P330 At the same time the intermediate DC link voltage threshold for enabling the regenerating bridge is reduced to the following value if an autotransformer is not present i e when 17 1 U U rectifier Supply ng regenerati Supply 00 100 318 P U 35 1 ng regenerati Supply This causes the signal Regenerating ready s...

Page 103: ...dge Bit 15 Fault external 1 command L Fault external 1 The command is executed with an L signal After the command has been accepted Changeover to the FAULT status 007 fault F035 The firing pulses are inhibited and the main contactor if installed drops out see also Chapter 7 Faults and Warnings Bit 16 and 17 reserved Bit 18 Reserve data set RDS bit 0 LSB command In conjunction with bit 19 RDS bit 1...

Page 104: ... the thyristor test is not carried out Master S F unit The closed loop control operates with an external DC link current setpoint Bit 28 Alarm external 1 command L Alarm external 1 The command is executed with an L signal After the command has been accepted The operating status is retained An alarm message A015 is output also refer to Section 7 Fault and Alarm Messages Bit 29 Alarm external 2 comm...

Page 105: ... which are assigned fixed values is provided in Section 4 3 1 2 3 Selecting the destinations for the status word NOTE For the output of faults alarms and switch on inhibit of the status word HIGH active via the terminal strip then these are LOW active at the terminals binary outputs i e the relay drops out This is also true for possible option boards Also refer to Section 4 3 3 Binary outputs Exam...

Page 106: ...not energized Can only be connector for terminals CUR or SCI P612 13 Ud reduced Ud not reduced P613 1 14 Motoring Generating P614 1 15 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 16 PMU Display Status word 2 visualization parameter r553 Bit High Low Comments Dest selection 16 17 18 Current active Current limit not active Inverted for terminal strips P618 1 19 Fault external 1 No fault external 1 ...

Page 107: ...ter Value Destination 0000 No destination Factory setting except P603 1001 CUR BA1 X104 17 18 1002 CUR BA2 X104 19 20 Factory setting for P603 Index i002 Selecting a terminal on the SCI 1 2 board option Value Destination 0000 No destination Factory setting 4101 SCI 1 and 2 Slave 1 BA1 4102 BA2 4103 BA3 4104 BA4 4105 BA5 4106 BA6 4107 BA7 4108 BA8 4109 only SCI 2 Slave 1 BA9 4110 BA10 4111 BA11 411...

Page 108: ...nd is applied over the control word bit 1 and or an ON command is still applied the control word bit 0 edge evaluation If the message is output at a terminal strip CUR SCB1 an L signal appears there for this message Bit 7 Signal Alarm H An H signal indicates that an alarm Axxx is present If the alarm is output at the terminal strip CUR SCB1 an L signal appears there for this alarm Bit 8 Signal Set...

Page 109: ... L signal appears there for this fault signal Bit 20 Signal Fault external 2 H An H signal indicates that a Fault external 2 is present in control word bit 26 If this fault is output at a terminal strip CUR SCB1 an L signal appears there for this fault signal Bit 21 Signal External alarm H An H signal indicates that an Alarm external 1 is present in control word bit 28 or an alarm external 2 in co...

Page 110: ... 2004 Word4 only if word 4 is not assigned for control word 2 with 2004 Section 4 3 1 1 consecutively to 2016 Word16 OPTIONS 3002 CB TB Word2 3003 Word3 3004 Word4 only if word 4 is not assigned for control word 2 with 3004 Section 4 3 1 1 consecutively to 3016 Word16 4101 SCB1 with SCI 1 Slave1 analog input AE1 4102 AE2 4103 AE3 4201 SCB1 with SCI 1 Slave2 analog input AE1 4202 AE2 4203 AE3 4501 ...

Page 111: ...t via the SCB1 interface with SCI1 also refer to the Instruction Manual for the option boards Indexes i001 Destination Analog output 1 from slave 1 i002 Destination Analog output 2 from slave 1 i003 Destination Analog output 3 from slave 1 i004 Destination Analog output 1 from slave 2 i005 Destination Analog output 2 from slave 2 i006 Destination Analog output 3 from slave 2 P690 SCB actual values...

Page 112: ... Binary input 5 RESERVE BASIC SETTING control word bit 30 4 3 3 Binary outputs 2 binary outputs which can be parameterized for the output of signals and external commands of the rectifier regenerating unit status word Connecting up Binary output 1 on the CUR control terminal strip connector X104 NO contact Refer to Section 3 3 Control terminal strip Binary output 2 on the CUR control terminal stri...

Page 113: ... CUR Section 4 4 Enter the parameter number 0 to 999 whose value is to output in P655 CUR AA actual values Set the analog output gain factor in P656 CUR AA gain setting range 320 00V to 320 00V pre setting 10 00V gain of 1 Set the offset in P657 CUR AA offset setting range 100 00V to 100 00V pre setting 0 00V no offset The following is obtained for the calculation from the Function diagram analog ...

Page 114: ...V 540 V Thus the following is obtained for the range to be represented 400 V 74 05 Parameter value PWE1 to be represented as Uoff1 0 00 V 600 V 111 07 Parameter value PWE2 to be represented as Uoff2 10 00 V Define gain factor P656 and offset P657 The following is obtained from the formula shown above V 98 19 100 74 05 V 27 03 V 0 100 74 05 V 27 03 0V 100 PWE V factor Gain V U V Offset V 27 03 37 1...

Page 115: ...ollowing is obtained for the range to be represented 630 A 150 Parameter value PWE1 represented as Voff1 10 00 V 630 A 150 Parameter value PWE2 represented as Voff2 10 00 V Define gain factor P656 and offset P657 The following is obtained from the formula shown above V 0 00 V 0 00 1 V 10 100 150 00 V 6 67 10V 100 PWE V factor Gain V U V Offset V 6 67 300 100 V 20 00 150 150 100 V 10 00 V 10 00 PWE...

Page 116: ... of DIP FIX switches S1 and S2 must be closed on board CUR Parameterization Defining the interface P683 to P687 Define the process data control word status word setpoints actual values for the interface Refer to Process data Section 4 3 1 Enabling parameterization P053 or P927 NOTE The factory setting refer to Parameter list Chapter 5 can be used if the SST1 basic converter interface is not used 4...

Page 117: ...special functions using P077 1 to 6 an appropriate set of factory settings can be selected for certain parameters in accordance with the table shown below In this manner for example certain terminals of the basic unit can be parameterized fast as sources for certain control word functions The following table shows the factory settings for the parameters that are dependent on P077 Normal factory se...

Page 118: ...ecial factory setting is required otherwise start at b P051 3 Access stage Expert mode to permit access to P077 P052 2 Select Initialize function to modify P077 P key The operating display appears 000 P077 Select the required P077 dependent parameter set in accordance with the above table P052 0 Terminate the function Initialize P key The operating display appears Then continue with b b Start of t...

Page 119: ...he input to the rectifier bridge P075 Rated DC current P076 Only the ones position is modified Ones position 2 when rectifier and regenerating mode is possible Ones position 1 when only rectifier mode is possible only set when P070 101 The operating display Switch on inhibit 008 or Ready to switch on 009 appears after Initialization has been completed MLFB table Brief description of the table colu...

Page 120: ...0 H 62 6SE7037 7HH85 1AA0 774 0 3AC 660 690 H 63 6SE7038 2EH85 1AA0 821 0 3AC 380 480 H 66 6SE7041 0EH85 1AA0 1023 0 3AC 380 480 H 67 6SE7041 0FH85 1AA0 1023 0 3AC 500 600 H 68 6SE7041 0HH85 1AA0 1023 0 3AC 660 690 H 71 6SE7041 3FK85 1AA0 1285 0 3AC 500 600 K 72 6SE7041 3HK85 1AA0 1285 0 3AC 660 690 K 73 6SE7041 3EK85 1AA0 1333 0 3AC 380 480 K 74 6SE7041 5FK85 1AA0 1464 0 3AC 500 600 K 75 6SE7041 ...

Page 121: ...8 Ready to switch on 009 or Fault 007 Procedure P052 3 Function selection Upread Download P key The operating display appears 021 Using a PC at the basic device interface SST1 and an appropriate application program e g DriveMonitor it is possible to read and change all parameters independently of their operating state and access level P051 P052 0 Function selection Return P key After return the op...

Page 122: ...rameters to configure the optional board see Section 4 5 or the operating instructions for the board P090 Board slot 2 To the RIGHT in the electronics box P091 Board slot 3 In the CENTER in the electronics box Parameter values for P090 P091 0 No option board 1 CB Communications board 2 TB Technology board only P090 3 SCB Serial Communication Board Additional parameters depending on the option boar...

Page 123: ...re P052 5 Function selection Drive setting P051 3 Access stage Expert mode if all parameters which can be accessed in the drive setting status A are required All parameters which can be written into the drive setting A status see right hand column of the parameter list in Chapter 5 can be changed if necessary P052 20 Function selection Forming refer to Section 4 3 9 6 P052 21 Function selection Ci...

Page 124: ...rm DC link function P key The operating display appears The rectifier regenerating unit must be switched on within 20 s otherwise message F091 fault value 4 appears Switch on the rectifier regenerating unit NOTE The firing pulses are enabled the rectifier regenerating unit carries current and the DC link is charged During the forming procedure the connected SIMOVERT Master Drives FC VC SC must not...

Page 125: ...cted to the DC link at any one time varies it is recommended that reserve data set selection is implemented Up to 4 different configurations can be formed for this purpose that are each assigned to a reserve data set Circuit identification has to be carried out separately for each of these reserve data sets During circuit identification the appropriate configuration must exist for the selected dat...

Page 126: ...ts of the inverters connected to the rectifier regenerating unit significantly drops below the rated current of the rectifier regenerating unit The operating display appears Circuit identification takes about 10 s with a discharged DC link capacitor The following parameters are set automatically P140 Circuit resistance of the rectifier bridge P142 Circuit resistance of the regenerating bridge P143...

Page 127: ...Return function P key NOTE Parameters r990 and r991 provide a list of modified parameters for the PMU and also for the OP1S 4 3 10 Functions 4 3 10 1 WEA automatic restart The Automatic Restart function can be used for the automatic acknowledgment of faults and automatic restart of the unit following a power failure F003 F004 F005 F007 F009 or F010 without the operator having to intervene The rect...

Page 128: ...ay then stop for some considerable time and may be erroneously assumed to be switched off Fatal injuries severe bodily harm or damage to property and machinery may result if the area surrounding the drive is entered while the drive is in this state NOTE If the kinetic buffering function KIP is activated on a connected converter from the series SIMOVERT Master Drives 6SE70 on the rectifier regenera...

Page 129: ...nking is required for the energy recovery As from Unit Software Release 3 2 the Ud can also be reduced automatically as an alternative depending on the DC link current Id When the current dependent Ud reduction is released by P323 1 the command for the reduction is generated internally by Ud The Ud setpoint is automatically reduced to the value in accordance with P318 when Id averaged over 3 curre...

Page 130: ...rt parameters contain a useful factory setting and must not usually be altered Not only the parameter but also the most important connectors Kxxx are drawn into the function diagrams Connectors can be seen as digital measuring points of internal controlled variables or memory locations e g DC link voltage K287 DC link current K114 control angle K100 The connectors are only used for factory interna...

Page 131: ...lel switching acc to P076 and or 12 pulse operation 3 ramp up ramp down time 0 on request by STW bit11 controlled Ud_set_deceleration logic if no AUS1 pending and P330 has an even value 2 K190 Set K167 Ud actual value on neg edge ov Ud_set reduction on no operation on AUS1 and not ready for regenerative feedback in 12 pulse operation on waiting in status Load current injection C correction 1 Round...

Page 132: ...operation P312 2111 P component active I component active U_netw_infeed U_netw_regenerative_feedback alpha G alpha W Disable regenerative feedback on STW1 Bit12 0 no regen _feedback enable Ud 0 9375 1 35 U_netw_regen _feedback or Ud 0 875 1 35 U_netw_regen _feedb at AUS1 Ud 1 35 U_netw_regen _feedback P318 100 if the Ud_set reduction logic demands it U_netw_regen _feedback P074 precharging ramp_fu...

Page 133: ...set DAC Hardware filtering to terminal block P655 CU AA actual values P656 CU AA gain Contents of parameter 001 0 Analog output CUR U OFF Parameter value 100 x Gain V Offset V Figure 4 4 3 Analog output CUR https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 134: ...589 P578 Q RDS Bit 0 Control word bit 18 Reserve data set selection RDS Parameters involved P140 to P144 P160 P161 P310 to P320 P329 P408 P517 P518 P773 to P777 P579 Q RDS Bit 1 Control word bit 19 P579 0 0 1 1 P578 0 1 0 1 Index i001 i002 i003 i004 All grey hatched background fields can be changed via the control word This is described in Figure 4 4 4 GRND Figure 4 4 4 Selecting the data sets htt...

Page 135: ...sibility for ensuring that the system is properly configured 1 Disconnect the power supply and insert the board in location 2 2 After the next switch on the board must be logged in via P090 The parameters of the technology board d and H parameters can then be accessed The connections for the process data on the basic unit are made using the corresponding source and target connections see Section 4...

Page 136: ...esponding source and target parameters see Section 4 3 For the meaning of the bits in the control words and the status words see Section 4 3 3 Switching off and on of the electronics supply voltage Doing this causes the values of parameters P695 P697 and P918 to be transferred from the supplementary board The CBP2 Communication Board PROFIBUS serves to link drives and higher level automation syste...

Page 137: ...s exchanged cyclically with the drives in most cases The user data structure for the cyclic channel MSCY_C1 see picture above is referred to as a Parameter Process data Object PPO in the PROFIBUS profile for variable speed drives This channel is also frequently referred to as the STANDARD channel The user data structure is divided into two different sections which can be transferred in each telegr...

Page 138: ...ound in Section 4 5 6 Structure of request response telegrams The parameter identifier PKE contains the number of the relevant parameter and an identifier which determines the action to be taken e g read value The index IND contains the number of the relevant index value equals 0 in the case of nonindexed parameters The IND structure differs depending on the communication mode Definition in the PP...

Page 139: ...o job job must be issued PROFIBUS devices have a variety of difference performance features In order to ensure that all master systems can correctly address each supplementary board the characteristic features of each board are stored in a separate device master file GSD File siem8045 gsd is needed for board CBP2 The appropriate file can be chosen in the selection menu for the SIMOVERT MASTER DRIV...

Page 140: ...atus Bit0 Offline Passive Idle 0 SPC3 is operating in normal mode offline 1 SPC3 is operating in Passive Idle Bit2 Diag flag 0 diagnostic buffer has been picked up by master 1 diagnostic buffer has not been picked up by master Bit3 RAM Access Violation memory access 1 5kB 0 no address violation 1 for addresses 1536 bytes 1024 is subtracted from address and access made to the new address Bit4 5 DP ...

Page 141: ...ck counter 022 L byte DP T GET DB101 ps ack counter H byte DP T PUT DB101 ps ack counter 023 L byte DP T service neg acknow counter H byte DP T Application association pos acknow counter 024 Reserved 025 Date of creation Day month 026 Date of creation Year 027 Software version Vx yz display x 028 Software version Vx yz display yz 029 Software version Flash EPROM checks 030 Reserved 031 Reserved 03...

Page 142: ...ble break bus connector removed or DP master switched off Effect When the telegram failure monitoring function is active P695 set to value other than 0 this disturbance generates fault message F082 with fault value 10 Alarm A085 Error in the DPS software of the communication board Effect Fault message F081 is generated Alarm A086 Failure of heartbeat counter detected by SIMOVERT 6SE70 Effect Inter...

Page 143: ...n 4 3 For the meaning of bits in the control words and the status words see Section 4 3 3 Switching off and on of the electronics supply voltage Doing this causes the values of parameters P696 to P706 and P918 to be transferred from the supplementary board The CAN Controller Area Network fieldbus is being used increasingly for industrial applications in spite of its limited network length max 40 m...

Page 144: ...nd therefore processed faster by the drive every 3 3 ms at system frequency of 50 Hz than the non time critical PKW data parameter identifier value which is processed by the drive every 20 ms All settings required to operate the communication board are made in drive parameters Process data PZD are categorized as either data received by the drive control words and setpoints PZD Receive or data tran...

Page 145: ... have changed event or on request Remote Transmission Requests This option should only be used in cases where values seldom change so as to prevent excessive bus loading Structure of a telegram for PZD data exchange The telegram consists of the following data words Identifier ID Process data word 1 PZD1 Process data word 2 PZD2 Process data word 3 PZD3 Process data word 4 PZD4 ID is the CAN identi...

Page 146: ...l word 1 or else the drives will not accept setpoints and control words The consistency of process data can only be guaranteed within a COB If more than 4 data words are needed these must be divided among several COBs Since drives accept the data asynchronously the data transferred in several COBs may not always be accepted and processed in the same processing cycle For this reason interrelated da...

Page 147: ...ter value of the indexed parameter P140 02 in the RAM to 5 000Ω The example telegram therefore contains the following values Request identifier 300d 012Ch for use of the IDs of the example above Request code 7d 7h Change parameter value array word Parameter number 140d 008Ch PKE 708Ch Index 2d 0002h Parameter value 5000d 1388h 3 decimal places value 5000 Using the CAN BusAnalyser from Steinbeis th...

Page 148: ...with PZD Transmit P698 PZD transmit length 0 P699 PZD transmit length 16 i e too long P699 Incorrect CAN identifier with PZD Receive Broadcast P701 Incorrect CAN identifier with PZD Receive Multicast P702 Incorrect CAN identifier with PZD Receive Internode P703 Invalid baud rate P705 Incorrect CAN protocol type P706 PKW Request Broadcast P704 without PKW Request P696 Overlap between CAN identifier...

Page 149: ...ts and responses since Power ON r731 015 Number of PKW request processing errors e g owing to bus overload or missing responses from CUD1 see below for error type r731 016 0 9 11 12 Type of PKW request processing error No error Error transmitting the PKW response while waiting for a free channel Timeout waiting for the PKW response from the CUD1 Timeout waiting for a free channel bus overload r731...

Page 150: ...e telegram failure time set in P695 No fault message is generated for PKW data Alarm A084 Bus Off Errored telegrams are being received or sent and the error counter on the supplementary board has exceeded the fault limit Errored telegrams are ignored The data most recently transferred remain valid If the errored telegrams contain process data fault message F082 with fault value 10 may be activated...

Page 151: ...aves The input signal for each input is zero calibrated via the indices P664 Actual value output via analog outputs of SCI1 slaves A connector number is selected via the indices to define the output quantity at each output P665 Gain of analog outputs of SCI1 slaves The gain for each output is parameterized via the indices P666 Offset compensation of analog outputs of SCI1 slaves The output signal ...

Page 152: ...itional inputs outputs SCI1 SCI2 10 binary inputs 16 binary inputs 8 binary outputs 12 binary outputs 3 analog inputs 3 analog outputs Reception of SCI data by the SCB1 or transmission to the SCIs is synchronized i e the data of two slaves is received simultaneously or transmitted simultaneously Details of the input output functions and connections can be found in the operating instructions for th...

Page 153: ...ipulated e g multiplication by a factor The first device at the beginning of the peer to peer chain feeds the required setpoints into the chain using the relevant visualization parameters The data received are treated in the same way as other externally supplied setpoints and connected to the appropriate source parameters Control word bits can be extracted individually from the peer to peer telegr...

Page 154: ...ure time for the USS or peer to peer protocol P689 2 SCB peer forwarding Identifies words in the received peer to peer telegram that should be forwarded immediately P690i SCB actual values Selection of parameter values that should be transmitted via the serial interface of the SCB2 board r730i SCB diagnosis SCB diagnostic information P090 or P091 for logging the board The display parameter r730 di...

Page 155: ...he telegram frame with header and trailer Header Trailer Index IND Parameter value PWE Parameter identifier PKE The parameter identifier PKE contains a request or response identifier i e type of request or response and the number of the addressed parameter The spontaneous signaling bit SPM bit11 is not used on the SIMOVERT 6SE70 Common Rectifier Header Trailer Index IND SPM Parameter value PWE Par...

Page 156: ...he associated response identifier but error identifier 7 or 8 instead In this case an error code defining the error in more detail as shown in the following list is returned as a parameter value Error code Meaning 0 Illegal parameter number PNU No PNU specified 1 Parameter value cannot be modified Visualization parameter 2 Lower or upper value limit violated 3 Faulty subindex 4 Parameter is not in...

Page 157: ...ader Trailer Index IND Bit 15 Parameter value PWE Parameter identifier PKE Index L byte Index H byte An index value of 255 means that the request applies to all indices of the relevant parameter In the case of a modification request the parameter values for all indices of the parameter must be transferred Conversely the drive supplies all index values in its response to a read request The paramete...

Page 158: ...ns AG 6SE7087 6AK85 1AA0 Rectifier Regenerating Unit Operating Instructions https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 159: ...0 089 Drive Data 090 099 Hardware Configuration 100 149 DC Link Data 150 329 Control 330 409 Convenience functions 410 549 Setpoint Channel 550 649 Control and Status Word 650 679 Analog Input Output 680 719 Communications 720 759 Diagnostics 760 779 Modulator 780 799 Factory Parameters 900 999 Profile Parameters Profibus https www aotewell com AoteWell Automation Sales Team Sales aotewell com Aot...

Page 160: ...antity L2 Nibble coded quantity 4 Scaling for access via the PKW mechanism If necessary Specification of scaling group for process data PZD PZD group PZD scaling 0 or no specification As for PKW scaling 1 4000Hex 100 5 Access stage P051 starting at which a parameter can be modified or displayed 1 Operator input 2 Standard mode 3 Expert mode 4 Factory set parameters 6 Specification of the operating...

Page 161: ...it for voltage at power terminals X4 1U2 X4 1V2 X4 1W2 regenerative bridge or Wait for checkback signal System contactor energized or Waiting state before energizing the system contactor Waiting time P409 o009 Wait for Ready to Switch On Wait for Ready to Switch On OFF1 active or Wait until internal OFF state is canceled by an external OFF command o008 Switch on inhibit isolation OFF2 Wait for ack...

Page 162: ...ge PNU 6Hex Type I2 Scaling 1Hex 1 V 0 100 0 to 16384V 0 to 1000 V 2 BR r011 Heatsink Temp Temperature of the heat sink PNU 0BHex Type I2 Scalling 1Hex 1 C PZD gr 1 Analog output 100 100 C 53 to 199 C 3 BR r012 Base Reserve Base reserve settings of the process data wiring for control word bits 0 Base setting 1 Reserve setting PNU 0CHex Type O2 Scaling 1Hex 1 0 to 1 2 BR r013 Operat Hours Display o...

Page 163: ...al DC link current PNU 23Hex Type I2 Scaling 1Hex 1 100 P075 PZD gr 1 199 to 199 2 BR r036 DC Volts set Display of DC link voltage setpoint The setpoint 1 35 r030 limited to values of P074 up to 106 8 PNU 24Hex Type O2 Scaling 1Hex 1 100 1 35 P071 PZD gr 1 0 to 199 3 BR r037 DC Volts act Display of actual DC link voltage PNU 25Hex Type O2 Scaling 1Hex 1 100 1 35 P071 PZD gr 1 0 to 199 2 BR r038 DC...

Page 164: ... variable speed drives this function is also accessible via parameter P970 After finishing this function the parameter is automatically reset to 0 2 Release for MLFB setting changing into the status MLFB input To exit this function the parameter must be reset to 0 3 Upread Download Changing into the status Upread Download To exit this function the parameter must be reset to 0 4 Hardware configurat...

Page 165: ... parameters specified in Section 4 4 Selecting the data sets are affected by the copying process whereby each of these parameters has 4 indices that are assigned to the 4 data sets Data set 1 can be set with the parameters Pxxx i001 Data set 2 can be set with the parameters Pxxx i002 Data set 3 can be set with the parameters Pxxx i003 Data set 4 can be set with the parameters Pxxx i004 0xy Do noth...

Page 166: ...mps Rated DC voltage of the R R unit Output DC current average value at the power terminals X1 C and X1 D PNU 4BHex Type O2 Scaling 1Hex 0 1 0 0 to 3276 7 A acc to P070 2 U BR 2 U P076 Config PCircuit Configuration of the power section xx1 Motoring only xx2 Motoring and generating possible 00x No parallel power section connected x1x to x2x Number of additional parallel connected power sections in ...

Page 167: ...ng acc to Parameter list Chapter 5 1 With this setting the following parameters are initialized differently as compared to 0 P554 P555 2 With this setting the following parameters are initialized differently as compared to 0 P554 P555 P565 P566 P567 P575 P588 P607 4 With this setting the following parameters are initialized differently as compared to 0 P554 P555 P565 P566 P575 P588 P607 5 With thi...

Page 168: ...ology Board 3 SCB Serial Communication Board Description for Setting Only the following combinations of PCBs and positions are admitted Position 3 P091 Position 2 P090 CB TB SCB SCB CB CB TB SCB TB CB SCB PNU 5AHex Type O2 Scaling 1Hex 1 0 to 3 none CB TB SCB 0 3 HBR 3 H P091 Board Position 3 PCB in position 3 center of the electronic box Description see P090 PCB position 2 PNU 5BHex Type O2 Scali...

Page 169: ...ling 1Hex 0 01 0 00 to 327 67 mH 4 0 00 3 BR 3 BR P142 Inverter Resist Circuit resistance of the regenerative bridge This parameter is automatically set when circuit identification takes place P052 21 RDS parameter PNU 70Hex Type O2 Scaling 1Hex 0 001 0 000 to 32 767 Ω 4 0 000 3 BR 3 BR P143 Inverter Induct Circuit inductance of the regenerative bridge This parameter is automatically set when circ...

Page 170: ... Limit Generating current limit The regenerating current is limited to the value set here RDS parameter PNU 0A1Hex Type I2 Scaling 1Hex 0 1 150 0 to 0 0 of P075 4 150 0 3 ABR 3 A P310 DC Curr Reg Gain Proportional gain of the DC link current controller This parameter is automatically set when circuit identification takes place P052 21 RDS parameter PNU 136Hex Type O2 Scaling 1Hex 0 01 0 01 to 1 00...

Page 171: ...the E unit or the E R unit can be operated at full signal level with the recovery direction blocked P076 xx1 After precharging this leads to the control angle α 0 RDS parameter PNU 13EHex Type O2 Scaling 1Hex 0 01 0 00 to 160 00 of 1 35 Supply voltage at the rectifier bridge 4 80 00 3 ABR 3 ABR P319 DC V set red Hys Hysteresis for Ud Ud set red message Ud reduced RDS parameter PNU 13FHex Type O2 S...

Page 172: ...Time DC link pre charging time RDS parameter PNU 149Hex Type O2 Scaling 1Hex 1 0 to 9999 ms 4 500 3 BR 3 BR P330 Discharge Time DC link discharge time An even parameter value causes abrupt lowering With effect from software version 4 5 an odd parameter value causes the Ud setpoint to ramp down with Ud reduction controlled by STW1 bit11 see Section 4 3 1 1 and 4 3 10 2 With the command OFF1 and cur...

Page 173: ...e thyristor test is only carried out when Ud 5 When Ud 5 a selected thyristor test P353 0 is ignored with P353 3 P353 remains at 3 The thyristors of the regenerating bridge are also fired for the purposes of the thyristor test in the case of regenerating inhibited control word 1 bit 12 corresponding source P572 selected PNU 161Hex Type O2 Scaling 1Hex 1 0 to 3 not active first ON every ON next ON ...

Page 174: ...ry and pre charging of the DC link During the power outage the controllers and firing pulses of the PZD R R are inhibited The rectifier regenerating unit enters status o010 On recovery of the voltage the DC link is charged again as quickly as possible see Section 4 3 10 1 Important The necessary external measures must be taken to guarantee safety on an automatic restart PNU 16EHex Type O2 Scaling ...

Page 175: ... actual value deviation of Ud If the deviation between the Ud setpoint and the actual Ud is considerable the Setpoint actual value deviation message is generated status word 1 Bit 8 r552 Compare P518 min duration of deviation RDS parameter PNU 205Hex Type O2 Scaling 1Hex 0 01 0 00 to 100 00 of 1 35 P071 4 2 00 3 BR 3 B P518 Deviation Time Min deviation time If there is a deviation P517 the Setpoin...

Page 176: ... BR r553 Status Word 2 Display of the status word 2 bits 16 to 31 see Section 4 3 1 2 2 22 23 30 31 18 19 26 27 16 17 24 25 20 21 28 29 PNU 229Hex Type V2 Scaling 1Hex 1 2 BR P554 Src ON OFF1 Source of the ON OFF1 command control word 1 bit 0 0 OFF1 1 Not allowed 1001 CUR binary input 1 1010 PMU ON OFF keys Other values see allowed settings in Section 4 3 1 1 process data wiring of the control wor...

Page 177: ...trol word 1 bit 7 0 No source selected 1 Not allowed 1003 Binary input 3 of the CUR board Other values see allowed settings in Section 4 3 1 1 process data wiring of the control word whereby Reset from the PMU is always possible Note The Acknowledge control command is edge triggered B R parameter PNU 235Hex Type L2 Scaling 1Hex 1 0 to 6005 2 i001 0 i002 1003 2 BR 2 BR P566 Src2 Fault Reset Source ...

Page 178: ... 1 process data wiring of the control word B R parameter PNU 23CHex Type L2 Scaling 1Hex 1 0 to 6005 2 1 2 BR 2 BR P573 Src No ExtFault3 Source for the External fault 3 control command control word 1 bit 13 L signal causes disconnection of the faulted drive 0 Not allowed 1 No external fault 3 1003 Binary input 3 of the CUR board Other values see allowed settings in Section 4 3 1 1 process data wir...

Page 179: ... word 2 bit 19 for selecting the reserve data set RDS 0 RDS bit 1 has the value 0 1 RDS bit 1 has the value 1 Other values see allowed settings in section 4 3 1 1 process data wiring of the control word B R parameter PNU 243Hex Type L2 Scaling 1Hex 1 0 to 6005 2 0 2 BR 2 BR P583 Src 12 Pulse Mode Source for control command 12 pulse mode is selected control word 2 bit 23 0 No 12 pulse mode 1 12 pul...

Page 180: ...l word 2 bit 29 0 Not allowed 1 No external warning Other values see allowed settings in Section 4 3 1 1 process data wiring of the control word B R parameter PNU 24DHex Type L2 Scaling 1Hex 1 1 to 6005 2 1 3 BR 3 BR P590 Src Base Reserve Source of the Base reserve settings switching command control word 2 bit 30 0 Base setting 1 Reserve setting 1005 Binary input 5 of the CUR board Other values se...

Page 181: ...ding on the index selected Parameter values indices as P600 PNU 259Hex Type L2 Scaling 1Hex 1 0 to 4212 2 0 3 BR 3 BR P602 Trg Bit Operat Destination of the status bit Run status word 1 bit 2 The unit is in operation Parameter values indices as P600 PNU 25AHex Type L2 Scaling 1Hex 1 0 to 4212 2 0 2 BR 2 BR P603 Trg Bit Fault Destination of the status bit Fault status word 1 bit 3 Note For issuing ...

Page 182: ...age Destination of the status bit Undervoltage status word 1 bit 11 Note For issuing the message via a terminal the active status bit has H level is inverted broken wire proof Parameter values indices as P600 PNU 263Hex Type L2 Scaling 1Hex 1 0 to 4212 2 0 3 BR 3 BR P612 Trg Bit Contact Destination of the status bit Energize main contactor status word 1 bit 12 H level energize contactor Important ...

Page 183: ...d broken wire proof If an ON command is active L level causes fault trip after 200 msec Parameter values indices as P600 PNU 26CHex Type L2 Scaling 1Hex 1 0 to 4212 2 0 3 BR 3 BR P621 Trg Bit ExtWarn Destination of the status bit External warning status word 2 bit 21 Note For issuing the message via a terminal the active status bit has H level is inverted broken wire proof Parameter values indices...

Page 184: ...the active status bit has H level is inverted broken wire proof Parameter values indices as P600 PNU 270Hex Type L2 Scaling 1Hex 1 0 to 4212 2 0 3 BR 3 BR P631 Trg Bit Charging Destination of the status bit Charging active status word 2 bit 31 Note For issuing the message via a terminal the active status bit has H level is inverted broken wire proof Parameter values indices as P600 PNU 277Hex Type...

Page 185: ...ltage only 2 Signed output inverted positive voltage regenerative current negative voltage motoring current 3 Output of absolute value inverted negative voltage only PNU 292Hex Type O2 Scaling 1Hex 1 0 to 3 signed absoluteVal inverted inv absVal 0 2 BR 2 BR P660 SCI AnalogInConf Configuration of the SCI analog inputs defines the kind of the input signals Parameter values Terminals Terminals X428 3...

Page 186: ...antities which are to be issued for details see SCI manual i001 Sl11 Slave 1 analog output 1 i002 Sl12 Slave 1 analog output 2 i003 Sl13 Slave 1 analog output 3 i004 Sl21 Slave 2 analog output 1 i005 Sl22 Slave 2 analog output 2 i006 Sl23 Slave 2 analog output 3 Condition The related SCB board must be reported via P090 and P091 respectively PNU 298Hex Type O2 Scaling 1Hex 1 0 to 999 6 0 3 BR 3 BR ...

Page 187: ...r positions in the telegram Notes The length number of words of the process data part in the peer to peer telegram is set with P686 Index i003 i001 Word 1 of the process data part of the telegram i002 Word 2 of the process data part of the telegram i005 Word 5 of the process data part of the telegram PNU 2A9Hex Type O2 Scaling 1Hex 1 0 to 999 5 i001 599 i002 34 i003 0 i004 0 i005 0 3 BR 3 B P682 S...

Page 188: ... the parameter data part in the net data block of the telegram 0 No parameter data part in the telegram 3 4 Parameter data part is 3 parameter identifier Ind parameter value 4 words long 127 Variable parameter data length for the transfer of parameter description and texts i001 SST1 serial comm interface 1 CUR i002 SCB SCB if P682 1 2 PNU 2ADHex Type O2 Scaling 1Hex 1 0 to 127 2 i001 127 i002 127 ...

Page 189: ...er to Peer protocol 8 data bits 1 parity bit even parity 1 stop bit With active Peer To Peer protocol P688 1 and telegram failure time P687 i003 0 the unit remains in operating state o008 until telegram traffic is correct PNU 2B0Hex Typ O2 Normierung 1Hex 1 0 to 1 factory internal Peer to Peer 0 3 BR 3 B P689 SCB Peer2PeerExt Immediate transfer on of data received via the peer to peer protocol of ...

Page 190: ...toring no fault trip must be parameterized for sporadic non cyclic telegrams e g operator panel OP at serial comm interface 1 PNU 2B7Hex Type O2 Scaling 1Hex 1 ms 0 to 6500 ms 20 3 BR 3 BR P696 CB Parameter 1 Communication board parameter 1 See manual of the used communication board Parameter is only needed if a communication board is reported P090 or P091 1 The communication board checks if the s...

Page 191: ...cation board parameter 8 See P696 PNU 2BFHex Type O2 Scaling 1Hex 1 0 to 65535 0 3 HBR 3 H P704 CB Parameter 9 Communication Board Parameter 9 See P696 PNU 2C0Hex Type O2 Scaling 1Hex 1 0 to 65535 0 3 HBR 3 H P705 CB Parameter 10 Communication board parameter 10 See P696 PNU 2C1Hex Type O2 Scaling 1Hex 1 0 to 65535 0 3 HBR 3 H P706 CB Parameter 11 Communication board parameter 11 See P696 PNU 2C2H...

Page 192: ...D Extended software version ID of the modules in slots 1 2 and 3 of the electronic box for internal purposes Indices i001 SPL1 Software code of the PCB in position 1 i002 SPL2 Software code of the PCB in position 2 i003 SPL3 Software code of the PCB in position 3 PNU 2D2Hex Type O2 Scaling 1Hex 0 1 3 3 U BR r723 PCB Code Identification code of the PCBs in positions 1 2 and 3 of the electronic box ...

Page 193: ...g inputs outputs according to process data wiring of the setpoint channel and actual value output via SCI P664 i011 BCd0 PCB code word 0 i012 BCd1 PCB code word 1 i013 Warn SCB DPR warning word i014 Sl1 Information if slave 1 needed and if yes which type 0 no slave needed 1 SCI1 2 SCI2 i015 Sl2 Information if slave 2 needed and if yes which type 0 no slave needed 1 SCI1 2 SCI2 i016 IniF with SCI m...

Page 194: ...of the DC link voltage controller on the output side of the limiting module exceeds the value of 0 05 set with this parameter the firing pulses of the rectifier bridge are enabled These pulses are inhibited if the setpoint of the DC link current drops below the value set here RDS parameter PNU 306Hex Type O2 Scaling 1Hex 0 01 100 00 to 0 01 4 3 00 3 BR 3 BR P775 Min Gating Angle Alpha G limit rect...

Page 195: ...t specific response threshold The current setpoint limit is then raised again 1 Response of the i 2 t monitor for the power section i e 100 of the i 2 t value has been reached results in fault F022 and disconnection PNU 311Hex Type O2 Scaling 1Hex 1 0 to 1 1 3 HBR 3 B P793 Line Voltage Delay Stabilizing time for the line voltage If the Switch on command is given the unit waits in status o010 for v...

Page 196: ...signed to the interfaces to enable the spontaneous message mechanism for the relevant interface s PNU 395Hex Type O2 Scaling 1Hex 1 0 to 7 inactive TB CB SCom SCB USS 0 3 BR 3 B P918 CB Bus Address Protocol depending bus address for communication board see manual of this board Notes The communication board checks if the set value is valid Bus addresses 0 to 2 are reserved for master stations If th...

Page 197: ...h is the actual value of the operating hours counter r013 is stored in parameter r748 The data for the current not yet reset trip is present as day hours and seconds in indices 1 to 3 The data for the already reset previous trips is present in groups of 3 elements on the following indices 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Indizes 1 Indizes 9 Indizes 17 Current 1st ack Current...

Page 198: ...g Parameter 2 If a warning numbers 17 to 32 is active the related bar in the display is ON 23 24 31 32 19 20 27 28 17 18 25 26 21 22 29 30 PNU 3BAHex Type V2 Scaling 1Hex 1 3 BR r955 Warning Param 3 Warning Parameter 3 If a warning numbers 33 to 48 is active the related segment in the display is ON 39 40 47 48 35 36 43 44 33 34 41 42 37 38 45 46 PNU 3BBHex Type V2 Scaling 1Hex 1 3 BR r956 Warning ...

Page 199: ... 116 123 124 115 114 121 122 113 PNU 3C0Hex Type V2 Scaling 1Hex 1 3 BR r967 Control Word 1 Display parameter of control word 1 bit 0 15 Identical with r550 control word 1 PNU 3C7Hex Type V2 Scaling 1Hex 1 2 BR r968 Status Word 1 Display parameter of status word 1 bit 0 15 Identical with r552 status word 1 PNU 3C8Hex Type V2 Scaling 1Hex 1 2 BR P970 Factory Settings Parameter reset to factory sett...

Page 200: ...ype O2 Scaling 1Hex 1 101 3 BR r982 PNU Lst 3 avail List of the available parameter numbers part 3 See r980 PNU 3D6Hex Type O2 Scaling 1Hex 1 101 3 BR r990 PNU Lst 1 chnged List of the changed parameter numbers part 1 The parameter numbers are listed in a positive sequence The first existing 0 shows that no more parameter numbers are changed Index range 1 to 101 As special function the value of i1...

Page 201: ...tch on standard For faults Return to the fault display Rectifier regenerating unit shutdown depending on the parameterization of OFF1 or OFF2 P554 to P557 No function P 1 Changeover between parameter number index and parameter value levels see Figure 6 2 whereby the command only becomes effective when the key is released 2 Resetting the current fault message see Figure 6 3 3 In conjunction with th...

Page 202: ...g o009 to the parameter number level in which the separate parameters can be selected via raise or lower The selected access level P051 and the operating state r000 r001 determine here which parameters are displayed All parameters are not always visible see Chapter 5 overview of the abbreviations footnotes 5 to 8 Pressing P again switches to the index level for indexed parameters see Section 4 1 2...

Page 203: ... level Parameter value level Fast changeover highest index highest value Ready to switch on Parameter indexed yes no Return to parameter number Fast changeover Operating display Figure 6 2 Operator control structure using the PMU https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 204: ...Fault acknow ledged Alarm cause removed or or or or Figure 6 3 Operator control structure of the PMU for alarms and faults Handling of fault and alarm messages reset move into the background in order to parameterize is described in Chapter 7 in detail Figure 6 4 Shifting the PMU display for parameters values with more than 4 digits P P https www aotewell com AoteWell Automation Sales Team Sales ao...

Page 205: ...e optional operator panel OP1S in spite of an active fault message or alarm it is still possible to parameterize If no key is pressed on the PMU for 30 s the fault message which was moved into the background or active alarm appears automatically on the PMU The message can be brought back into the foreground by simultaneously pressing the P keys on the PMU at the parameter number level 7 1 Fault me...

Page 206: ...us or at least one power section connected in parallel reports Power supply faulted 1 2 3 5 Electronics supply voltage of the rectifier regenerating unit too low Power interface module of the rectifier regenerating unit or parallel power section reports Power supply faulted Check electronics power supply Power supply fuse for parallel units blown Internal fault on the power interface module of a s...

Page 207: ...ot connected to X30 module on A1681 and or A1682 F029 Measure Flt Fault in line voltage measurement An offset 5 has been detected when attempting to compensate for the offset of the line voltage measurement 1 2 3 4 Channel V U faulted regenerative feedback direction Channel V W faulted regenerative feedback direction Channel W U faulted regenerative feedback direction Channel W U faulted infeed di...

Page 208: ...nput has been activated There is an External fault 2 signal at the selected binary input P586 source for Ext fault 2 The line to the corresponding binary input is interrupted F038 Ext Fault 3 External fault 3 A parameter programmable fault input has been activated There is an External fault 3 signal at the selected binary input P573 source for Ext fault 3 The line to the corresponding binary input...

Page 209: ...generative operation with continuous DC link current for the current ratio of rectifier regenerating supply voltage As the inverter step limit P776 with respect to the commutation duration depending on uK value of the network has an upper limit P318 has to be set lower or Ud reduction has to be activated via P571if it is not currently active The following must apply cosP776 100 U U P318 rect Suppl...

Page 210: ...he connection between the signal source and the SCI1 module slave 3 X428 10 11 F076 Sl2 AnaIn1 Current at analog input 1 slave 2 under 4 mA Check the connection between the signal source and the SCI1 module slave 3 X428 4 5 F077 Sl2 AnaIn2 Current at analog input 2 slave 2 under 4 mA Check the connection between the signal source and the SCI1 module slave 3 X428 7 8 F078 Sl2 AnaIn3 Current at anal...

Page 211: ...ommutating inductance too low see Section 3 1 Connection to DC link interrupted 4 A waiting time of 20s has already elapsed but the circuit identification cannot be carried out because the DC link voltage is too high Ud 20 of 1 35 P071 Another unit is supplying the DC link Wait until the DC link has discharged sufficiently then start circuit identification again F091 Circuit ID C Circuit identific...

Page 212: ...ound fault in DC link or in motor rectifier fuse defective Ground fault Connection to DC link interrupted e g fuse blown 9 I 0 Message defective CUR module defect 11 12 13 14 15 16 Thyristor cannot be fired X11 Thyristor cannot be fired X12 Thyristor cannot be fired X13 Thyristor cannot be fired X14 Thyristor cannot be fired X15 Thyristor cannot be fired X16 Firing pulse line to relevant thyristor...

Page 213: ...n activated External warning arrived Check whether the line to the relevant binary input is interrupted Check parameter P589 Src No Ext Warn 2 See also Section 4 3 2 A022 P954 5 LT Temp The heat sink temperature is 90 C or with water cooled units The heat sink temperature is 118 C Measure inlet air and or ambient temperature If ϑ 40 C note the reduction curves See Section 14 1 Check whether fan E1...

Page 214: ...xcessive process data length has been set 5 Reduce the number of words P686 SCom SCB PrDat A053 P956 4 Peer Lng f In a peer to peer connection the process data length of the sender and receiver do not agree Match the word lengths of the sender and receiver P686 SCom SCB PrDat A065 P957 0 Auto Restart The line voltage is outside the tolerance band at the moment e g power outage The firing pulses ar...

Page 215: ...rigger modules A23 are separated The power and control terminals may still be live even in the event of motor standstill Despite disconnecting the power terminals from the supply terminal X19 may still be live due to the external fan supply If work on the activated unit is necessary do not touch any live parts use only proper measuring equipment and protective work clothing stand or sit on an unea...

Page 216: ...es not rub and also check the air flow direction arrow pointing upward The air must be discharged from the unit in the upward direction X20 M4 x 49 Torx T20 M4 x 49 Torx T20 Protective grille Fan E1 Figure 8 1 Protective grille and fan 24 V for size C Size E The fan is located on the right underside of the unit Undo the M4 x 8 T20 Torx screw securing the fan Extract the plug in terminal X29 Undo t...

Page 217: ...so they must be screwed down firmly X20 Fan E1 M8 M8 M4 Figure 8 3 Fan AC 230V for size H Size K The two fans are located in the fan box on the top of the unit Unplug X20 Undo both M8 SW 13 fixing screws Pull the fan box out of the unit forwards Installation is carried out in reverse order X20 M8 Fan E1 Fan E2 Figure 8 4 Fan AC 230V for size K WARNING The fan box weighs approx 16 kg for size H and...

Page 218: ... control cabinet directly beforehand Replacing modules in the electronics box option Undo the securing screws of the modules above and below the insertion removal aids By means of the insertion removal aids carefully pull the module out of the electronics box making sure that the module does not get stuck Carefully insert the new module in the guide rails until it moves no further in the electroni...

Page 219: ...over from fault display to parameterization Access stage Expert mode MLFB setting initialization WARNING Initialization is mandatory Specify the ID number of the MLFB in P070 of the rectifier regenerating unit rating plate on the unit as per MLFB table Section 4 3 9 2 P051 3 P052 2 P070 F060 P052 0 See Section 4 2 2 or 4 2 3 P and Higher key P and Lower key P key Return from setting MLFB Change ba...

Page 220: ...and Section 4 3 9 8 displaying modified parameters It should be checked that these entries are up to date before the EPROM is replaced because when the electronics supply voltage is switched on again the function generate factory settings is carried out automatically see Section 4 3 9 1 Then only the values of parameters P070 and P077 are retained WARNING The EPROM must only be replaced by qualifi...

Page 221: ...ixing screws After switching the electronics supply voltage on again wait until the function generate factory setting is complete Then restore the parameter values in accordance with the logbook or reload the values saved using DriveMonitor into the unit If the parameters are restored in accordance with the logbook circuit identification see Section 4 3 9 7 must be carried out due to special param...

Page 222: ...tallation of incorrect load resistors If the load resistors R75 to R78 are not installed the converter will be destroyed Dimensioning of the load resistors Idav A Rating plate R75 R76 Ω R77 R78 Ω R79 R80 Ω Voltage class 480V 21 150 270 41 51 1300 86 43 51 173 15 51 222 10 91 310 10 18 375 8 2 15 463 12 910 6 8 605 10 18 6 8 821 4 7 10 10 1023 4 7 4 7 12 1333 18 12 12 1780 8 2 11 12 https www aotew...

Page 223: ... 12 13 1880 8 2 10 11 Voltage class 690V 140 27 30 222 10 91 270 11 22 420 18 130 6 8 536 12 27 6 8 774 4 7 11 12 1023 4 7 4 7 12 1285 10 33 12 1464 12 12 13 1880 8 2 10 11 Resistors of series W97041 tolerance 0 50 for R 10Ω 0 25 for 10Ω R 47Ω R79 and R80 not envisaged on A1681 0 10 for R 47Ω The load resistance setpoint refers to the DC link current Idav stated on the rating plate https www aotew...

Page 224: ...8043 A1681 X47 X48 2AT 250V F1 2AT 250V F2 R 7 7 R 7 5 R 7 8 R 7 6 Size E C98043 A1682 7AT 250V 7AT 250V 1 5 X 9 X 9 F4 F3 X48 X47 2 A T 2 5 0 V F2 2 A T 2 5 0 V F1 R 78 R 80 R 76 R 77 R 79 R 75 https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 225: ...nd K C98043 A1685 7A T 250V 7A T 250V 1 5 X 9 X 9 X29 2 1 3 2 1 X19 F4 F3 X47 X48 2 A T 2 5 0 V F5 2 A T 2 5 0 V F1 2 A T 2 5 0 V F2 R 79 R 77 R 75 R 76 R 78 R 80 https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 226: ...ssembling the central thyristor block open 4 twisted cables g and detach cable h for the two thermistors that are only located on the central thyristor block Unplug the gate and cathode cables G K j Remove 3 M8 hexagon head bolts k Loosen the two M8 hexagon head screws l push rail approx 150 mm upwards and swing the thyristor block out forwards Loosen M6 nut A and pull the thyristor block out upwa...

Page 227: ...hyristor block remove the two thermistors that are only located on the central thyristor block by removing the screws l Torx drive T25 Loosen the two M10 hexagon head screws and swing the thyristor block out forwards Loosen M10 nut A and pull the thyristor block out upwards at an angle Rear thyristor block level B weight of a thyristor block approx 25 kg Unplug gate and cathode cables G K S Remove...

Page 228: ...ens AG 6SE7087 6AK85 1AA0 Rectifier Regenerating Unit Operating Instructions https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 229: ...7 6SX7010 0FF05 SCB1 Serial communications board with fiber optic cable for serial I O system and peer to peer connection 6SE7090 0XX84 0BC0 Description 6SE7080 0CX84 0BC0 Serial communications board for peer to peer connection and USS protocol via RS485 6SE7090 0XX84 0BB0 Description 6SE7080 0CX84 0BB0 SCB2 Use of the serial interface with USS protocol 6SE7087 6CX87 4KB0 T100 Module incl hardware...

Page 230: ...ions CBC with ADB CBP2 with ADB SCB1 SCB2 T100 T300 T400 NOTE Only one of each option board type may inserted in the electronics box TB technology boards e g T400 must always be inserted at slot 2 If only one option board is used it must always be inserted at slot 2 Small format modules CBP and CBC must be plugged in on the adapter board on the right or below in Slot E or if a technology module is...

Page 231: ...ly X9 The figures are required in addition to the 1A consumed by the basic unit Table 9 3 Current drain of the option boards 9 2 Interface boards The boards listed in the following table must be installed externally and connected to the installation side for start up see Section 4 4 4 Procedure for commissioning the serial I O board SCB1 and the description of the board Desig nation Description Or...

Page 232: ...ace SST1 If the UP or DOWN keys of the OP1S is used to select adjacent parameter numbers the missing numbers are skipped in the range of the basic device parameters With parameters of a technology module this automatic skipping of missing numbers is not possible In that case the numbers of the existing parameters must be entered directly P Fault Run 0 Reset 1 2 3 6 5 4 7 8 9 Jog O I Figure 9 1 OP1...

Page 233: ...he OP1S Communication between the OP1S and the SIMOVERT device is performed via the interface G SST1 RS485 using the GPI protocol By pressing the appropriate key on the OP1S it is possible to execute functions The OP1S sets the appropriate control word bit in PZD word 1 by means of transmission by the GPI protocol For details of the control word bits see Chapter 4 3 1 1 For activation of the requi...

Page 234: ... short designation PTP1 item number C98043 A1690 L1 equipment identifier A2 can be ordered The order numbers MLFB for these versions are 1 Module PTP1 with two spacers 1 module MLFB 6SE7090 0XX85 1NA0 2 Standard package for 12 pulse mode 2 PTP1 modules with two spacers for each of two units MLFB 6SE7090 0XX85 1TA0 3 Retrofitting package for 12 pulse mode 2 PTP1 modules with two spacers 2 CUR contr...

Page 235: ...n 3 5 Single line diagrams with suggested circuit arrangements Function Terminal Connected values Description RS485 serial interface X117 1 RS485R receive cable RS485 positive SST2 X117 2 RS485R receive cable RS485 negative X117 3 RS485T send cable RS485 positive X117 4 RS485T send cable RS485 negative X117 5 Signal earth The bus termination resistors required for peer to peer mode are installed o...

Page 236: ...in file README TXT After you have chosen an installation language by selecting links DriveMonitor Installation of DriveMonitor Start Installation you can call the DriveMonitor installation routine Some Internet Browsers are not capable of starting programs directly If this is the case on your PC a Setup exe Save as dialog appears after you select Start Installation You can then start the Setup pro...

Page 237: ...n select parameter file if the parameter file has been created in SIMOVIS the drive type MASTERDRIVES RRU and the software version used must then be set V4 5 If you want to set up an online link to the drive you must click the ONLINE button and enter the bus address set in the device To create a new offline file File New Based on Factory Setting select drive type and software version If you want t...

Page 238: ...unications via Profibus or USS Order No 6SW1700 5JA00 1AA0 Drive ES Graphic Interconnection of Option S00 free functions blocks using the CFC interconnection editor Order No 6SW1700 5JB00 1AA0 Drive ES Simatic Provides function blocks for SIMATIC CPUs and sample projects for communication with the SIMOVERT 6SE70 Order No 6SW1700 5JC00 1AA0 NOTICE DriveMonitor will run under Windows 95 98 Me or Win...

Page 239: ...FE85 1AA0 6SE7033 5FE85 1AA0 6SE7034 2FE85 1AA0 6SE7035 4FE85 1AA0 A23 FBG Power Interface 6SE7034 2HE85 1HA0 6SE7031 4HE85 1AA0 6SE7032 2HE85 1AA0 6SE7032 7HE85 1AA0 6SE7034 2HE85 1AA0 6SE7035 3HE85 1AA0 A23 PCB Power Interface 6SE7041 8EK85 1HA0 6SE7038 2EH85 1AA0 6SE7041 0EH85 1AA0 6SE7041 3EK85 1AA0 6SE7041 8EK85 1AA0 A23 PCB Power Interface 6SE7041 8HK85 1HA0 6SE7037 7FH85 1AA0 6SE7041 0FH85 ...

Page 240: ...1 7EE85 1AA0 V11 to V16 Thyristor module 6SY7010 0AA07 6SE7032 4FE85 1AA0 V11 to V16 Thyristor module 6SY7010 0AA02 6SE7033 1EE85 1AA0 V11 to V16 Thyristor module 6SY7010 0AA03 6SE7033 8EE85 1AA0 V11 to V16 Thyristor module 6SY7010 0AA05 6SE7034 6EE85 1AA0 V11 to V16 Thyristor module 6SY7010 0AA22 6SE7034 2FE85 1AA0 V11 to V16 Thyristor module 6SY7010 0AA04 6SE7036 1EE85 1AA0 V11 to V16 Thyristor ...

Page 241: ...D0 Ebene B Thyristor block with snubber RC network 6SY7010 0AB08 6SE7041 8EK85 1AA0 6SE7041 8EK85 1AD0 Ebene A Thyristor block with snubber RC network 6SY7010 0AB12 6SE7037 7FH85 1AA0 Ebene B Thyristor block with snubber RC network 6SY7010 0AB13 6SE7037 7FH85 1AA0 Ebene A Thyristor block with snubber RC network 6SY7010 0AB15 6SE7041 0FH85 1AA0 Ebene B Thyristor block with snubber RC network 6SY701...

Page 242: ...22 7FC85 1AA0 6SE7024 1FC85 1AA0 6SE7027 2FC85 1AA0 6SE7028 8FC85 1AA0 6SE7031 7EE85 1AA0 6SE7032 2EE85 1AA0 6SE7033 1EE85 1AA0 6SE7033 8EE85 1AA0 6SE7034 6EE85 1AA0 6SE7036 1EE85 1AA0 6SE7031 5FE85 1AA0 6SE7032 4FE85 1AA0 6SE7032 7FE85 1AA0 6SE7033 5FE85 1AA0 6SE7034 2FE85 1AA0 6SE7035 4FE85 1AA0 6SE7031 4HE85 1AA0 6SE7032 2HE85 1AA0 6SE7032 7HE85 1AA0 6SE7034 2HE85 1AA0 6SE7035 3HE85 1AA0 F5 Fus...

Page 243: ... 1AA0 6SE7041 5FK85 1AD0 6SE7041 8FK85 1AA0 6SE7041 8FK85 1AD0 6SE7041 3HK85 1AA0 6SE7041 3HK85 1AD0 6SE7041 5HK85 1AA0 6SE7041 5HK85 1AD0 6SE7041 8HK85 1AA0 6SE7041 8HK85 1AD0 F10 Fuse link 6SY7010 2AA04 6SE7022 1EC85 1AA0 F10 Fuse link 6SY7010 2AA05 6SE7024 1EC85 1AA0 6SE7024 1FC85 1AA0 F10 Fuse link 6SY7010 2AA06 6SE7028 6EC85 1AA0 F10 Fuse link 6SY7010 2AA07 6SE7031 7EE85 1AA0 6SE7032 2EE85 1A...

Page 244: ...SE7041 8HK85 1AD0 F11 to F26 Fuse link 6SY7010 2AA11 6SE7037 7FH85 1AA0 6SE7037 7HH85 1AA0 F111 to F262 Fuse link 6SY7010 2AA11 6SE7041 3FK85 1AA0 6SE7041 3FK85 1AD0 6SE7041 3HK85 1AA0 6SE7041 3HK85 1AD0 F111 to F262 Fuse link 6SY7010 2AA21 6SE7041 5FK85 1AA0 6SE7041 5FK85 1AD0 6SE7041 5HK85 1AA0 6SE7041 5HK85 1AD0 R100 NTC thermistor 6SY7010 6AA01 6SE7022 1EC85 1AA0 6SE7024 1EC85 1AA0 6SE7028 1EC...

Page 245: ...41 8HK85 1AD0 E1 Fan 6SY7000 0AA48 6SE7022 1EC85 1AA0 6SE7024 1EC85 1AA0 6SE7028 1EC85 1AA0 6SE7022 7FC85 1AA0 6SE7024 1FC85 1AA0 6SE7027 2FC85 1AA0 6SE7028 8FC85 1AA0 E1 Fan 6SY7010 7AA01 6SE7031 7EE85 1AA0 6SE7032 2EE85 1AA0 6SE7033 1EE85 1AA0 6SE7033 8EE85 1AA0 6SE7034 6EE85 1AA0 6SE7036 1EE85 1AA0 6SE7031 5FE85 1AA0 6SE7032 4FE85 1AA0 6SE7032 7FE85 1AA0 6SE7033 5FE85 1AA0 6SE7034 2FE85 1AA0 6S...

Page 246: ... 6SE7028 1EC85 1AA0 6SE7022 7FC85 1AA0 6SE7024 1FC85 1AA0 6SE7027 2FC85 1AA0 6SE7028 8FC85 1AA0 T1 to T4 Current transformer 6SY7010 5AA02 6SE7031 7EE85 1AA0 6SE7032 2EE85 1AA0 6SE7033 1EE85 1AA0 6SE7033 8EE85 1AA0 6SE7034 6EE85 1AA0 6SE7036 1EE85 1AA0 6SE7031 5FE85 1AA0 6SE7032 4FE85 1AA0 6SE7032 7FE85 1AA0 6SE7033 5FE85 1AA0 6SE7034 2FE85 1AA0 6SE7035 4FE85 1AA0 6SE7031 4HE85 1AA0 6SE7032 2HE85 ...

Page 247: ...EK85 1AD0 6SE7041 8EK85 1AA0 6SE7041 8EK85 1AD0 6SE7041 3FK85 1AA0 6SE7041 3FK85 1AD0 6SE7041 5FK85 1AA0 6SE7041 5FK85 1AD0 6SE7041 8FK85 1AA0 6SE7041 8FK85 1AD0 6SE7041 3HK85 1AA0 6SE7041 3HK85 1AD0 6SE7041 5HK85 1AA0 6SE7041 5HK85 1AD0 6SE7041 8HK85 1AA0 6SE7041 8HK85 1AD0 https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell...

Page 248: ...mens AG 6SE7087 6AK85 1AA0 Rectifier Regenerating Unit Operating Instructions https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 249: ...ttings Start up settings change Par No Parameter designation Factory setting Start up setting Start up setting change P050 Language 0 P051 Access Level 2 P052 Function select 0 P053 Parameter Access 6 P054 Display Light 0 P070 MLFB 6SE70 0 P071 Line Volts dependent on P070 P074 Limit LowVoltage 61 P075 Rtd Amps dependent on P070 P076 Config PCircuit 002 P077 Factory set type 0 P090 Board Position ...

Page 250: ...002 0 15 i003 0 15 i004 0 15 i001 i002 i003 i004 i001 i002 i003 i004 P311 DC Curr Reg Time i001 0 015 i002 0 015 i003 0 015 i004 0 015 i001 i002 i003 i004 i001 i002 i003 i004 P313 DC Volts Reg Gain i001 3 00 i002 3 00 i003 3 00 i004 3 00 i001 i002 i003 i004 i001 i002 i003 i004 P314 DC Volts RegTime i001 3 00 i002 3 00 i003 3 00 i004 3 00 i001 i002 i003 i004 i001 i002 i003 i004 P316 DC V Reg Limit ...

Page 251: ...01 500 i002 500 i003 500 i004 500 i001 i002 i003 i004 i001 i002 i003 i004 P330 Discharge time i001 2000 i002 2000 i003 2000 i004 2000 i001 i002 i003 i004 i001 i002 i003 i004 P353 Thyristor Test 0 P354 GroundFault Test 2 P366 Auto Restart 0 P408 Caps FormingTime i001 10 0 i002 10 0 i003 10 0 i004 10 0 i001 i002 i003 i004 i001 i002 i003 i004 P409 Contactor Delay 0 0 P486 Src Current Setp i001 0 i002...

Page 252: ...P571 Src Reduce DC V i001 0 i002 0 i001 i002 i001 i002 P572 Src RegenRelease i001 1 i002 1 i001 i002 i001 i002 P573 Src No ExtFault3 i001 1 i002 1 i001 i002 i001 i002 P574 Src Motor Regen i001 0 i002 0 i001 i002 i001 i002 P575 Src No ExtFault1 i001 1 i002 1 i001 i002 i001 i002 P578 Src RDataSetBit0 i001 0 i002 0 i001 i002 i001 i002 P579 Src RDataSetBit1 i001 0 i002 0 i001 i002 i001 i002 P583 Src 1...

Page 253: ...1 i002 P611 Trg Low Voltage i001 0 i002 0 i001 i002 i001 i002 P612 Trg Bit Contact i001 0 i002 0 i001 i002 i001 i002 P613 Trg DC V reduced i001 0 i002 0 i001 i002 i001 i002 P614 Trg Motor Regen i001 0 i002 0 i001 i002 i001 i002 P618 Trg Cur Lim Active i001 0 i002 0 i001 i002 i001 i002 P619 Trg Bit Ext Flt1 i001 0 i002 0 i001 i002 i001 i002 P620 Trg Bit Ext Flt2 i001 0 i002 0 i001 i002 i001 i002 P6...

Page 254: ...AnalogInOffs i001 0 00 i002 0 00 i003 0 00 i004 0 00 i005 0 00 i006 0 00 i001 i002 i003 i004 i005 i006 i001 i002 i003 i004 i005 i006 P664 SCI AnaOutActVal i001 0 i002 0 i003 0 i004 0 i005 0 i006 0 i001 i002 i003 i004 i005 i006 i001 i002 i003 i004 i005 i006 P665 SCI AnaOutGain i001 10 00 i002 10 00 i003 10 00 i004 10 00 i005 10 00 i006 10 00 i001 i002 i003 i004 i005 i006 i001 i002 i003 i004 i005 i0...

Page 255: ...99 i002 34 i003 0 i004 0 i005 0 i001 i002 i003 i004 i005 i001 i002 i003 i004 i005 P682 SCB Protocol 0 P683 SCom SCB BusAddr i001 0 i002 0 i001 i002 i001 i002 P684 SCom SCB Baud i001 6 i002 6 i003 13 i001 i002 i003 i001 i002 i003 P685 SCom SCB PKWDat i001 127 i002 127 i001 i002 i001 i002 P686 SCom SCB PrDat i001 2 i002 2 i003 2 i001 i002 i003 i001 i002 i003 P687 SCom SCB TlgOFF i001 0 i002 0 i003 1...

Page 256: ...B TB Act Values i001 968 i002 0 i003 0 i004 0 i005 0 i006 0 i007 0 i008 0 i009 0 i010 0 i011 0 i012 0 i013 0 i014 0 i015 0 i016 0 i001 i002 i003 i004 i005 i006 i007 i008 i009 i010 i011 i012 i013 i014 i015 i016 i001 i002 i003 i004 i005 i006 i007 i008 i009 i010 i011 i012 i013 i014 i015 i016 P695 CB TB TlgOFFTime 20 P696 CB Parameter 1 0 P697 CB Parameter 2 0 P698 CB Parameter 3 0 P699 CB Parameter 4...

Page 257: ...adband Invert i001 3 00 i002 3 00 i003 3 00 i004 3 00 i001 i002 i003 i004 i001 i002 i003 i004 P775 Min Gating Angle i001 0 i002 0 i003 0 i004 0 i001 i002 i003 i004 i001 i002 i003 i004 P776 Max Gating Angle i001 150 i002 150 i003 150 i004 150 i001 i002 i003 i004 i001 i002 i003 i004 P777 Max Gating Angle Ramp i001 20 00 i002 20 00 i003 20 00 i004 20 00 i001 i002 i003 i004 i001 i002 i003 i004 P785 I2...

Page 258: ... Regenerating Unit Operating Instructions No Date time Name department Fault and diagnostic messages Measures https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 259: ...ed by pollutant free materials in all components Environmental compatibility was an important criterion in the selection of externally source items Environmental aspects during production Externally sourced items are mainly transported in returnable packaging The packaging material itself is recyclable consisting mainly of cardboard and untreated wood Except for the hot dip galvanized enclosure an...

Page 260: ...3 2 Siemens AG 6SE7087 6AK85 1AA0 Rectifier Regenerating Unit Operating instructions https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 261: ...er connected 1 DIN VDE 0160 04 91 Type of protection Size C Standard Size E Standard Option Size H K Standard IP20 IP00 IP20 IP00 DIN VDE 0470 Part 1 11 92 EN 60529 Interference immunity IEC 801 2 IEC 801 4 Mechanical strength DIN IEC 68 2 6 06 90 Frequency range Constant amplitude of deflection acceleration Hz mm m s2 g 10 to 58 0 075 stationary use more than 58 to 500 9 8 1 3 5 during transport ...

Page 262: ...3 36 82 68 74 68 74 Load class I to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current average DC link connection Rectifier operation A 21 41 86 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 19 37 78 Base l...

Page 263: ...lass I to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current average DC link connection Rectifier operation A 173 222 310 375 463 605 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 157 202 282 341 421 551 Ba...

Page 264: ...n A 821 1023 1333 1780 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 747 931 1213 1620 Base load duration s 240 Excess current A 1121 1396 1820 2430 Excess current duration s 60 Losses cooling Power dissipation Maximum kW 3 29 3 70 4 84 6 24 Cooling air requirement m3 s 0 55 0 55 1 0 1 0 So...

Page 265: ...to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current average DC link connection Rectifier operation A 27 41 72 94 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 25 37 66 86 Base load duration s 240 Excess c...

Page 266: ...he DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current average DC link connection Rectifier operation A 151 235 270 354 420 536 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 137 214 246 322 382 488 Base load duration s 240 Exce...

Page 267: ...1023 1285 1464 1880 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 704 931 1169 1332 1711 Base load duration s 240 Excess current A 1057 1396 1754 1998 2566 Excess current duration s 60 Losses cooling Power dissipation Maximum kW 3 30 4 03 5 40 5 87 7 65 Cooling air requirement m3 s 0 55 0 5...

Page 268: ... 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current average Zwischenkreisanschluß beim Einspeisen A 140 222 270 420 536 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 127 202 246 382 488 Base load duration s 240 Exce...

Page 269: ...3 1285 1464 1880 Load class II to EN 60146 1 1 of the DC link current average value in rectifier operation currents reduced to 92 in regenerative operation Rated current A 704 931 1169 1332 1711 Base load duration s 240 Excess current A 1057 1396 1754 1998 2566 Excess current duration s 60 Losses cooling Power dissipation Maximum kW 3 70 4 15 5 54 5 97 7 62 Cooling air requirement m3 s 0 55 0 55 1...

Page 270: ...ower reduction at altitudes 1000m above MSL The rated current must be reduced as shown in Figure 14 3 in the event of installation altitudes 1000 m above mean sea level Installation altitudes 2000 m above MSL please enquire 90 80 70 0 1000 2000 3000 4000 100 60 90 80 70 0 1000 2000 3000 4000 100 60 Installation altitude in m above sea level permissible rated current in permissible rated voltage in...

Page 271: ... Semiconductor converters general regulations and special regulations for line commutated converters DIN VDE 0843 Electromagnetic compatibility of instrumentation and control equipment in industrial process engineering Part 2 A09 87 Z Interference resistance to static electricity discharges requirements and measurement methods IEC801 2 Ersetzt durch DIN EN 60801 Teil 2 09 87 DIN VDE 0875 RFI suppr...

Page 272: ...s DIN standards and foreign standards Beuth Verlag GmbH Burggrafenstraße 6 10787 Berlin DIN VDE regulations VDE Auslieferungsstelle Merianstraße 29 63069 Offenbach https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 273: ...tifier via a PC DriveMonitor is supplied on the same CD ROM order number 6SX7010 0FA10 as the operating instructions for the 6SE70 converter used in conjunction with the rectifier unit https www aotewell com AoteWell Automation Sales Team Sales aotewell com AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell com https www aotewell com ...

Page 274: ... i C98130 A1234 A1 09 7647 A5E00811825 Version i consists of the following chapters Chapter Pages Date of Edition 0 General 12 09 02 1 Description 2 05 00 2 Transport unpacking assembly 8 05 00 3 Connection 60 09 02 4 Start Up 76 09 02 5 Parameter List 42 09 02 6 Operator control 4 09 02 7 Fault and Alarm Messages 10 09 02 8 Maintenance 14 09 02 9 Options 10 09 02 10 Spare parts 10 09 02 11 Blank ...

Reviews: