Press the <F1> "Help " key function to call up information about the cause and remedial
measures. Press the <F5> "Quitt." key to acknowledge a stored fault.
Alarms are indicated as follows:
● The yellow LED "Alarm" flashes
Additionally, a note relating to the cause of the alarm is displayed in the status bar of the
operator panel.
Every fault and alarm is entered in the fault/alarm buffer along with time the fault occurred. The
time stamp refers to the relative system time in milliseconds (r0969).
8.4.2
Diagnostics via LEDs
8.4.2.1
LEDs of the Power Stack Adapters
Table 8-1
LEDs of the Power Stack Adapters
LED
Color
Status
Description; cause
Remedy
PWR
-
Off
24 V power supply has failed or is too low
(< 14 V) or internal fuse defective.
Check input voltage.
If input voltage is > 18 V and LED off:
Return component for repair.
Red
Continuous
light
24 V power supply is available (>14 V);
internal board voltage fault.
Check input voltage.
If input voltage is > 18 V and LED red:
Return component for repair.
Green
Continuous
light
24 V power supply OK.
Internal board voltages OK.
--
RUN /
ERR
-
Off
The electronic power supply is missing or
lies outside the permissible tolerance
range.
-
Green
Continuous
light
The component is ready for operation
and cyclic DRIVE-CLiQ communication
is in progress.
-
Orange
Continuous
light
DRIVE-CLiQ communication is being es‐
tablished.
-
Red
Continuous
light
At least one fault is present in the com‐
ponent.
LED is controlled irrespective of the cor‐
responding messages being reconfig‐
ured.
Remedy and acknowledge fault.
Green/red
0.5 Hz flashing
light
Firmware download in progress.
-
2 Hz flashing
light
Firmware download is complete. Waiting
for POWER ON.
Carry out a POWER ON.
Green/
orange
or
Red/orange
Flashing light
Component recognition via LED is acti‐
vated.
The color depends on the LED state
when component recognition is activated.
-
Operation
8.4 Fault and system messages
SINAMICS PERFECT HARMONY GH150 6SL3825
Operating Instructions 05/2020
89
Summary of Contents for 6SL3825
Page 2: ...19 06 2020 09 58 V14 00 ...
Page 12: ...Table of contents SINAMICS PERFECT HARMONY GH150 6SL3825 12 Operating Instructions 05 2020 ...
Page 130: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3825 130 Operating Instructions 05 2020 ...
Page 134: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3825 134 Operating Instructions 05 2020 ...
Page 140: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3825 140 Operating Instructions 05 2020 ...
Page 145: ......