3.5.5
Phase shifter start (option E07)
The generator that is decoupled from the gas turbine is accelerated to a speed slightly above
the synchronous speed via the starting converter. The starting converter is switched off
automatically once the speed setpoint is reached. The speed setpoint is approx. 10% above the
synchronous speed.
After the starting converter has been disconnected, the generator is excited to the rated voltage
and is synchronized with the line at a synchronous speed during runout. Once the generator
has been successfully synchronized with the line, positive or negative reactive power is
generated with the static excitation equipment.
3.5.6
Brake after phase shifter operation (option E08)
With this software option, the generator is decelerated by the starting converter. The generator
can then be recoupled with the turbine.
3.5.7
Plug connection between the starting converter and excitation equipment (option
G57)
Three plug connections are provided in the cutout in the side panel. This is used to connect the
power unit of the starting converter with the open-loop control cabinet of the excitation
equipment. The sockets are permanently installed in the open-loop control cabinet side panel.
The corresponding connectors in the converter can be freely connected to the terminals with
the adequate lengths provided.
The connectors are defined for the following signal and supply voltages:
Table 3-2
Connector assignment for voltages less than 60 V
Signal name
Pin assignment = MBJ01DE001.CX-X24
24 V DC supply voltage
P24V
1
2
3
4
M24V
Enable signal from the starting converter power
unit
P24V
5
Signal
6
Protective trip from the starting converter power
unit
P24V
7
Signal
8
Protection of the damping element OK (optional) P24V
9
Signal
10
Reserve
Reserve
11
12
Reserve
13
14
Reserve
15
Description
3.5 Options
SINAMICS GL150 6SL38502UM114PA0Z
Operating Instructions Rev.201910281441 EXAMPLE
41