Procedure
To screw transport units together, proceed as follows:
①
Holes for threaded pins
②
Self-adhesive sealing strips
Figure 5-1
Screwing the transport units together
1. Affix the self-adhesive sealing strips
②
.
2. Align the cabinets.
3. Insert the threaded pins through the holes
①
.
4. Attach the contact washers to the threaded pins.
5. Screw the transport units together using the nuts with a torque of 32 Nm.
5.5
Connect to the foundation
Four holes for M12 screws are provided on each cabinet panel to secure the cabinet to the
foundation. Information on mounting holes and their fixing dimensions are specified in the
dimension drawing.
Install the transport units in accordance with the specifications provided in the accompanying
dimension drawings. When doing this, maintain the specified distance between the top of the
cabinet and the ceiling.
5.6
Mounting fans
You must mount the fans, if, for logistical reasons, the fans were separately supplied. Proceed
as described in the section "Mounting fans" of Chapter "Replacing fans".
See also
Mounting
5.6 Mounting fans
SINAMICS GL150 6SL38502UM114PA0Z
70
Operating Instructions Rev.201910281441 EXAMPLE