4-118
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
External 26.5 V infeed, enable, BERO inputs
S
X431:
Axis 1
S
X432:
Axis 2
Table 4-22
Connector X431; 8–pin Phoenix Combicon connector
Pin
X431
Type
1)
Function
Typ. voltage/
limit values
1
M
I
Electronic ground
2
PV1
O
P24EXT switched, axis 1
Max. 2.0 A
3
MV1
O
M24EXT switched, axis 1
4
C1
–
Reserved, do not use
5
P24
I
Input for ex24 V
26.5 V
"
2%
6
M24
I
Input for external 0 V
7
663
I
Module–specific enable signal
21 V...30 V
8
9
O
Enable voltage, internal, +24 V
1)
I = Input, O = Output
Table 4-23
Connector X432; 8–pin Phoenix Combicon connector
Pin
X432
Type
1)
Function
Typ. voltage/
limit values
1
M
I
Electronic ground
2
PV2
O
P24EXT switched, axis 2
Max. 2.0 A
3
MV2
O
M24EXT switched, axis 2
4
C2
–
Reserved, do not use
5
B1
I
BERO input, axis 1
15 V...30 V
6
19
O
Internal enable voltage, ground, term.19
7
B2
I
BERO input, axis 2
15 V...30 V
8
9
O
Enable voltage, internal, +24 V
1)
I = Input, O = Output
Notice
A connection (jumper) between X431.6 and X432.3 is not permissible!
Max. terminal cross–section 2.5 mm
2
.
It is only necessary to supply terminals X431 pins 5 and 6 with 24 V if the 24 V
outputs of connectors X111/112, X121/122 or X431/432 are to be used.
Terminals
4 Control Units