6.2 Interface overview
6-152
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
6.2.3
Cable cross–sections that can be connected
The cable cross–sections that can be connected are listed in Table 6-3:
Table 6-3
Cable cross–sections that can be connected at the infeed module (line supply connection)
MLFB
Connection cross–section [mm
2
]
1)
2)
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
[Nm]
6SN1143–1BB00–0FA
120 kW
X
M6
25...30
6SN1143–1BB00–0EA
80 kW
X
M6
15...20
6SN1145–1BA01–0DA
55 kW
X
M6
15...20
6SN1145–1BB00–0DA
55 kW
X
M6
15...20
6SN1145–1BA02–0CA
36 kW
X
M6
6...8
6SN1145–1BA01–0BA
16 kW
X
M5
1,5...1,8
6SN114
–1A
01–0BA
28 kW
X
M6
6...8
6SN1145–1AA01–0AA
10 kW
X
M5
1,5...1,8
6SN1146–1AB00–0BA
5 kW
X
X
X
X
M5
0,7...0,8
Key
Terminal area for flexible cable with end sleeves (with or without plastic collars)
Terminal area for flexible cables with terminal pin
X
IP20 is guaranteed when correctly used, e.g. insulated pin–type cable lugs
1) Size of the screw for the protective conductor connection
2) Tightening torque of the terminals or connectors