6
05.01
6.2 Interface overview
6-156
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
External switching voltage for the coil circuit of the line contactor
Is used to supply the coil circuit of the internal line contactor only at the 80 kW
and 120 kW I/R modules (do not connect between the I/R module and reactor).
Fuse: I
r
≥
4 A, version gL
2–ph. 360 to 457 V AC/45 to 53 Hz; 400 to 510 V/57 to 65 Hz
Table 6-4
Technical data of the internal line and pre–charging contactor
I/RF module
Type
Pull–in power [VA]
Holding power [VA]
50 Hz
60 Hz
50 Hz
60 Hz
6SN114
–1BB0
–0EA1
3TK48
330
378
36
44.2
6SN114
–1BB0
–0FA1
3TK50
550
627
32
39
Matching transformer for the coil connections L1, L2 at the line supply voltage 230 V and
380 V; for two 5TK5022–0AR0 contactors.
Table 6-5
Matching transformer SIDAC 1–phase autotransformer
For 50 Hz line supplies
For 60 Hz line supplies
Type
4AM4096–0EM50–0AA0
4AM4696–0EM70–0FA0
Throughput rating [VA]
80
80
Input voltage [V]
380/230
380/230
Output voltage [V]
415 (min. 360/max. 458)
460/415
Output current [A]
0.193
0.19...0.17
Insulating material class
T40/B
T40/B
Applicable standard
EN 61558–13
VDE 0532
Frequency [Hz]
50/60
50/60
Vector group
IA0
Ii0
Degree of protection
IP00
IP00
Dimension sketch
PD10 T8/2
LV 10
for voltage fluctuations
+10% –13.2 %
+10% –13.2 %
Note
If, for the 80/104 kW or 120/156 kW I/R module, the line supply voltage at
terminals L1, L2 fails or fuses F1, F2 trip, then only the pulses in the I/R module
are cancelled and the internal line contactor drops–out.
This is displayed using the ”line fault” LED, the ready relay and also the
contactor signaling contacts. In this case, in order to re–close the internal line
contactor, terminal 48 must be inhibited (de–energized) and re–energized after
≥
one second or the unit must be powered–down/powered–up.
Reset
The fault signal is reset using a pushbutton (pulse edge) between terminal R
and terminal 15.
For the SIMODRIVE 611 universal HRS control unit, the reset is effective if, in
addition, terminal 65 ”controller enable” is also inhibited.
Terminals L1, L2
Terminal R
6 Infeed Modules
11.05