6.2 Interface overview
6-157
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Set–up operation
Terminal 112 is jumpered by default with terminal 9 (+24 V enable voltage).
Open:
The step–up converter voltage control is set to start inhibit, monitoring
disabled
Terminal 112 can only be used for SIMODRIVE 611 analog and not for
SIMODRIVE 611 digital/universal.
Signaling contact, start inhibit DC link controller
Terminals AS1 – AS2 closed means that ”start inhibit is effective”
(i.e. terminal 112 = open, setup mode)
(not available for UI modules 5 kW, 10 kW, 28 kW)
Terminal 112 can only be used for SIMODRIVE 611 analog and not for
SIMODRIVE 611 digital/universal.
Reference potential, electronics
If analog setpoints are routed from an external controller to the drive group, then
wire an equipotential bonding conductor via terminal X131. This cable must be
routed in parallel to the speed setpoint cable.
Cross–section = 10 mm
!
Electronics power supply
Terminal 7:
P24
+20.4 to 28.8 V/50 mA
Terminal 45:
P15
+15 V/10 mA
Terminal 44:
N15
–15 V/10 mA
Terminal 10:
N24
–20.4 to 28.8 V/50 mA
Terminal 15:
M
0 V(only for circuits of terminals 7, 45, 44
and terminal 10; max. load, 120 mA)
–
Terminal 15 may not be connected to PE (ground loop)
–
Terminal 15 may not be connected to terminal 19 (otherwise there will be
a short–circuit through the reactor; terminal 15 is internally connected to
X131).
Connecting terminals to separately supply the internal electronics power supply,
e.g. through fused terminals (refer to the circuit example in Section 8.3.1).
In this case, jumpers 1U1–2U1, 1V1–2V1, 1W1–2W1 must be removed.
Notice
Observe additional information and instructions under Section 8.3 Monitoring
module, and Section 8.15 Six–conductor connection!
Terminal 112
Terminals AS1,
AS2
Terminal X131
Terminals 7, 45, 44,
10, 15 (X141)
Terminals
2U1, 2V1, 2W1