6.3 Function overview and settings
6-163
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
OFF: Ready signal (X111 ready relay)
For S1.2 = OFF, the relay pulls–in if the following conditions are fulfilled:
–
Internal main contactor CLOSED (terminals NS1 – NS2 connected, ter-
minal 48 enabled)
–
Terminals 63, 64 = ON
–
No fault present (also not at the FD 611 A Standard, 611 U,
resolver and 611 D drives and HLA modules).
–
FD with High Standard or resolver for the setting ”ready” is enabled (ter-
minals 663, 65)
–
For 840D/810D, the NCU must have run–up
ON:
Fault signal (X111 ready relay)
For S1.2 = ON, the relay picks up if the following conditions are fulfilled:
–
Internal main contactor CLOSED (terminals NS1 – NS2 connected, ter-
minal 48 enabled)
–
No fault present (also not at the FD 611 A Standard, 611 U,
resolver and 611 D drives and HLA modules).
–
FD with High Standard or resolver for the setting ”ready” is enabled (ter-
minals 663, 65)
–
For 840D and 810D the NCU must have run–up
OFF: Standard setting, regenerative feedback into the line supply active
I/R modules
16 kW to 120 kW are capable of regenerative feedback.
UI module:
5 kW, 10 kW, 28 kW: The pulsed resistor in the module
is effective and active.
ON:
Regenerative feedback to the line supply is switched off
I/R modules:
16 kW to 120 kW: Regenerative feedback mode is
disabled
UI module:
5 kW, 10 kW: The pulsed resistor in the module is
not active
Valid for
UI 5 kW, Order No.: 6SN1146–1AB00–0BA1 and
UI 10 kW, Order No.: 6SN1145–1AA01–0AA1
Not valid for UI 28 kW. In this case, the external
pulsed resistor must be disconnected.
OFF: Standard setting for all NE modules, refer to S 1.1
ON:
V
line
= 480 V +6% / –10%; V
DC link
= V
line
1.35 in infeed mode
V
DC link
= 700 to 750 V
"
2.5%
in regenerative feedback mode
Monitoring thresholds: (I/R, UI, monitoring modules)
PR on = 744 V
"
2.5%;
PR off = 718 V
"
2.5%
V
DC link
w
795 V
"
2.5%
S1.4 exceeds the setting of S1.1
Please note! Unregulated operation in the infeed direction.
!
Warning
An incorrect switch setting (”OFF”) for S1.4 when connected to U
line
= 480 V
will overload the NE module and destroy it!
Switch S1.2
Switch S1.3
Switch S1.4
6 Infeed Modules