6
05.01
6.4 Technical data
6-166
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Switches S1.1 and S1.4 (see Chapter 6.3) are used to adapt the line infeed mo-
dules to the prevailing line supply conditions.
The converter system is designed for operation on grounded line supplies TN–S
and TN–C (IEC 60364–1 VDE 0100–300). For other line supply types, a trans-
former with separate windings in vector group yn on the secondary side must be
connected upstream (refer to Chapter 7 for the dimensioning).
Table 6-8
Supply voltage and frequency
NE-Module
S1.1, S1.4 = OFF
Un = 3AC 400 V
S1.1 = ON
Un = 3AC 415 V
S1.4 = ON
Un = 3AC 480 V
Line voltage: U1, V1, W1
3AC 400 V
10%
3AC 415 V
10%
3AC 480 V + 6% –10%
With derating P
rated
and P
max
1)
3AC 380 V
15%
DC link voltage
DC 600 V
DC 625 V
DC 580...710 V
Frequency
45...65 Hz
55...65 Hz
1) See Table 6-9, Technical data I/R modules
This means that the operational reliability is increased even when connected to weak line supplies!
Supply voltage
and frequency
6 Infeed Modules
02.12