6.5 HFD reactor
6-175
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
6.5.1
Assignment of the HFD reactors/damping resistors to the NE
modules
Table 6-12
HFD reactor/damping resistor assignment, data
UI module
28/50 kW
I/RF module
16/21 kW
I/RF module
36/47 kW
I/RF module
55/71 kW
I/RF module
80/104 kW
I/RF module
120/156 kW
Type
HFD reactor
28 kW
16 kW
36 kW
55 kW
80 kW
120 kW
Order No.
6SL3000–
6SN1111–
–
1AA00–0CA
0DE21–6AA
0DE23–6AA
0DE25–5AA
0DE28–0AA
0DE31–2AA
Pv
70 W
170 W
250 W
350 W
450 W
590 W
Degree of protec-
tion acc. to
DIN EN 60529
(IEC 60529)
IP00
Maximum permis-
sible ambient
temperature
Transport
Storage
Operation
–25..+80
C
–25..+80
C
0...+40
C, for power derating, up to +55
C
Connection
max. 35 mm
2
max. 16 mm
2
max. 35 mm
2
max. 70 mm
2
max. 95 mm
2
Tightening torque
of terminals [Nm]
2.5
1.2
2.5
Conductor 7
PE 3...4
Spring–loaded terminals
Terminals of HFD resistor 1.2
Approx. weight
6 kg
8.5 kg
13 kg
18 kg
40 kg
50 kg
Mounting position
Any
Any
Any
Any
Any
Any
Terminal place-
ment
Input: 1U1, 1V1, 1W1
ment
Output: 1U2, 1V2, 1W2
HFD damping re-
sistor
–
Refer to Table 6-15
Cooling clearances (without any additional measures, HFD line reactors can become hot!): 100 mm
Drilling template
Refer to Chapter 12 Dimension drawings