SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
6.7.2
Pulsed resistor module and unregulated line supply infeed with
pulsed resistor
The pulsed resistor module (PR module) protects the DC link from overvoltage,
which, for example, would occur for UI modules when braking or for I/R modules
when the power fails when stopping. The possible braking power of the total
system can be increased by using one or more pulsed resistor modules.
The pulsed resistor module can be used to quickly discharge the DC link.
If the pulsed resistor (PR) module is supplied from a monitoring module, the
electronics power supply must be implemented with a 3–phase AC supply
system. Fast discharge is not possible if the electronics power supply is exclu-
sively implemented through the DC link (P500/N500).
If heat–sensitive components, e.g. cable ducts, are located above the module
with a clearance < 500 mm, then an air baffle plate must be provided
(Order No. 6SN1162–0BA01–0AA0).
As a result of the universal housing design of the pulsed resistor module, this
can be used both for internally as well as externally cooled module groups.
The UI and PR modules are equipped with a switch–on time monitoring; this
protects the pulsed resistor from overheating.
The switch–in and switch–out thresholds depend on the setting of the line in-
feed switch S 1.1 or S 1.4, see Chapter 6.3.
Table 6-21
Technical data, PR module
Rated supply voltage
435/490/600/625/680 V DC
Continuous power/peak pow-
er/energy
Permitted load cycle, refer to
Section 6.7.4
S
with internal pulsed resistor
P = 0.3/25 kW; E = 7.5 kWs
S
with an external pulsed resistor module
P = 1.5/25 kW; E = 13.5 kWs
Weight
approx. 5 kg
Module width
50 mm
Order number
6SN11 13–1AB01–0AA1