SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Table 6-24
Braking power of the UI and pulsed resistor modules (PR)
Description
External PR 0.3/25 kW
1)
External PR Plus 1.5/25 kW
Order number
6SN1113–1AA00–0DA0
6SL3100–1BE22–5AA0
Can be used
for
28 kW UI module
28 kW UI module
PR module 6SN1113–1AB0
V
–0BA
V
Attenuation: 0...230 kHz
3 dB
for
PR module 6SN1113–1AB0 –0BA
S
Attenuation: 0...230 kHz
3 dB
S
Must be used together with HFD commutating reactor for damping
Pn
0.3 kW
1.5 kW
P
max
25 kW
25 kW
E
max
7.5 kWs
180 kWs
Dimension drawings, refer to Chapter 12
1) External PR can also be used for damping after a protecting measurement on the HFD reactor.
The resistor can be mounted either horizontally or vertically.
red, blue, PE (green yellow), each 1.5 mm
2
Shielded 3 m connecting cable, can be extended up to max. 10 m
PE
Fig. 6-23
Connection for external pulsed resistor 0.3/25 kW
The shield is connected through a PG gland
Shielded connecting cable (braided shield), cross–section 2.5 – 4 mm
2
,
max. length 10 m
PE
V/L2
U/L1/C/L+
W/L3/D/L–
3R
1R
PE
PE
Fig. 6-24
Connection for external PR for braking power ratings up to 1.5/25 kW
Note
Conductors that are not used in multi–conductor cables must always be
connected to PE at both ends.
Mounting
positions
6 Infeed Modules