Line Supply Connection
7.1
Line supply connection conditions for line supply infeed
For technical data, refer to Chapter 6.4 and Tables 7-1/7-2.
SIMODRIVE infeed units are designed to be connected to line supplies with
compatibility level, Class 3 of electromagnetic environments in industrial plants
and systems according to IEC/DIN EN61000–2–4:2002.
When the EMC mounting/installation guidelines are complied with, noise immu-
nity values according to IEC/DIN EN61000–6–2 Electromagnetic Compatibility
(EMC) – Generic Standard, Noise Immunity/emission – Part 2: Industrial envi-
ronments (1999) are complied with.
The SIMODRIVE unit may be directly connected to TN line supplies with selec-
tively tripping, AC/DC–sensitive RCCBs as protective measure.
Upstream devices providing protection against hazardous leakage currents or
for fire protection (such as residual–current protective devices) must be univer-
sal current–sensitive in accordance with the requirements of DIN EN 50178. In
the case of other residual–current protective devices, a transformer with sepa-
rate windings must be connected upstream of the converter for purposes of
decoupling.
Commutating reactor(s)
U1 V1 W1
Connection schematic with RCCB
PE
L3
L2
L1
NE module
Residual–current circ.
breaker (RCCB)
AC/DC–sensitive
PEN
Line
supply/transformer
for the factory
Line filter
Selective
Fuses
Fig. 7-1
Residual–current circuit–breaker (RCCB) connection schematic
Supply voltage
and frequency
Compatibility/
noise immunity
Direct connection
to line supplies
with selective
AC/DC–sensitive
RCCBs
7