7
05.01
7.2 Voltage matching
7-209
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
7.2.3
Minimum cross–sections for PE (protective conductor)/equipotential
bonding conductor
Table 7-4
Minimum cross–sections for PE (protective conductor)
P
rated
[kW]
I
rated
[A]
PE
[mm
2
]
PE
[AWG/kcmil]
5
7
1.5
16
10
14
4
14
28
40
10
8
16
23
4/10
10
36
52
16
6
55
79
16
4
80
115
25
3
120
173
50
1/0
7 Line Supply Connection