7
05.01
7.3 Overcurrent protective devices, transformers and main switch
7-225
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
7.3.4
Assignment of the isolating transformer to the UI modules
Table 7-11
Matching transformers with separate windings for 50 Hz/60 Hz line supplies
UI module
5 kW
2)
UI module
10 kW
2)
UI module
28 kW
Nominal rated power
[kVA]
8
16
47
Power loss, max.
[W]
520
650
1200
Vector group
YYn0 neutral point N can only be loaded with maximum 10%!
Short–circuit voltage uk [%]
10
Degree of protection to
DIN EN 60529 (IEC 60529)
S
Degree of protection IP 00:
V
––> Order No. 0
S
Degree of protection IP 20:
V
––> Order No. 8
S
Degree of protection IP 23:
V
––> Order No. 2
1)
Humidity rating EN 60721–3–3
Class 3K5 condensation and formation of ice excluded
Permiss. ambient temperature
S
Operation
_
C
S
Storage/transport
_
C
–25 to +40, for power derating up to +55
–25 to +80
Approx. weight for
S
Degree of prot. IP 00
[kg]
S
Degree of prot. IP 20/23
[kg]
55
65
70
95
200
216
Dim. (L x W x H) approx.
[mm]
360 x 268 x 320
420 x 262 x 370
480 x 267 x 420
Max. conn., secondary
[mm
2
]
6
6
35
Input voltage, 3–ph. 575 V – 500 V – 480 V AC
10%; 50 Hz – 10% to 60 Hz + 10%
Rated input current
[A]
10
20
58
Max. conn., primary
[mm
2
]
6
6
35
Order No. according to Catalog
PD10
4AU36 95–0SB0
V
–0CN2
4AU39 95–0SA3
V
–0CN2
4BU47 95–0SC3
V
–0C
Input voltage, 3–ph. 440 V – 415 V – 400 V AC
10%; 50 Hz – 10% to 60 Hz + 10%
Rated input current
[A]
12
24
70
Max. conn., primary
[mm
2
]
6
16
35
Order No. according to Catalog
PD10
4AU36 95–0SB1
V
–0CN2
4AU39 95–0SA4
V
–0CN2
4BU47 95–0SC4
V
–0C
Input voltage, 3–ph. 240 V – 220 V – 200 V AC
10%; 50 Hz – 10% to 60 Hz + 10%
Rated input current
[A]
26
47
140
Max. conn., primary
[mm
2
]
6
16
70
Order No. according to Catalog
PD10
4AU36 95–0SB2
V
–0CN2
4AU39 95–0SA5
V
–0CN2
4BU47 95–0SC5
V
–0C
1)
For degree of protection IP 23, a 10% power derating must be taken into account
2) Not degree of protection IP 20
Note
UI modules can be operated on TN line supplies from 360 V (with derating!) to
480 V without a matching transformer.
7 Line Supply Connection
02.12