7
05.01
7.4 Line filters for I/R and UI modules
7-233
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Caution
The connections/terminals may not be interchanged:
Incoming line supply cable to LINE/NETZ L1, L2, L3
Outgoing cable to the line reactor to LOAD/LAST U, V, W
If this is not observed, the line filter could be damaged.
Table 7-14
Assigning the wideband filters to the I/R modules
I/RF module
16/21 kW
I/RF module
36/47 kW
I/RF module
55/71 kW
I/RF module
80/104 kW
I/RF module
120/156
kW
Filter
components
Line filter
16 kW
Line filter
36 kW
Line filter
55 kW
Line filter
80 kW
Line filter
120 kW
Rated AC current
30 A
67 A
103 A
150 A
225 A
Supply voltage
3–ph. 380 V – 10% ... 3–ph. 480 V AC + 10% (TN line supply)
1)
; 50...60 Hz
10%
Order number
6SL3000–
0BE21–6AA
6SL3000–
0BE23–6AA
6SL3000–
0BE25–5AA
6SL3000–
0BE28–0AA
6SL3000–
0BE31–2AA
Mounting position
Wall or base/floor mounting, refer to Fig. 7-13
Dimensions (W x H x D),
approx.
130x480x150
130x480x245
130x480x260
200x480x260
300x480x260
Module width
Refer to dimension drawings, Chapter 12
Weight, filter
9 kg
16 kg
19 kg
22 kg
34,5 kg
Power loss
70 W
90 W
110 W
150 W
200 W
Connection
16/10 mm
2 3)
/1.5 Nm
PE, M5 studs/
3 Nm
2)
50 mm
2
/6 Nm
PE, M8
studs/13 Nm
2)
50 mm
2
/6 Nm
PE, M8
studs/13 Nm
2)
95 mm
2
/15 Nm
PE, M8
studs/13 Nm
2)
95 mm
2
/15 Nm
PE, M8 studs/
13 Nm
2)
Terminals
Line supply connection
(line)
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
Terminals
Load connection (load)
U, V, W
U, V, W
U, V, W
U, V, W
U, V, W
I
rated
fuse
4)
35 A
80 A
125 A
160 A
250 A
Permissible
ambient temperature
Operation
[
°
C]
Storage/transport
[
°
C]
0 ... +40; m55 at 0.6
•
P
rated
of the l/R module
–25 ... +70
Cooler
Natural ventilation
Degree of protection to
EN 60529 (IEC 60529)
IP20
DIN EN 61800-3 (IEC
61800-3)/VDE 0160-103 ra-
dio interference suppres-
sion
Limit value Class C2
1) The permissible supply voltage of the system depends on the infeed module used.
2) For ring cable lugs to DIN 46234.
3) The first data applies for pin–type cable lugs, the second data applies for finely–stranded conductors without end sleeves
4) The fuse used must have this rated current. Recommendations for the fuses, refer to Table 7-6.
7 Line Supply Connection
02.12