8
05.01
8.16 VPM Voltage Protection Module
8-323
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Table 8-6
Technical data VPM
Technical specifications
VPM 120
VPM 200
VPM 200 Dynamik
Order No.:
6SN1113–1AA00–1JA
6SN1113–1AA00–1KA
6SN1113–1AA00–1KC
Type of voltage
3–phase pulsed AC voltage, EMF motor
Power–up time of the VPM
1 s (from puls enabling)
Normal range of the DC link
voltage
lower limit
490 V DC
upper limit
795 V DC
Operating range of the VPM
830 ... 2000 V (peak amplitude)
Lower limit, DC link voltage
490 V DC
Inverter clock cycle frequency
3.2...8 kHz
Rated current
Max. 120 A rms
Max. 200 A rms
Permissible short–circuit current
Time range
0...10 ms
10...500 ms
500...2 min
2 min
Maximum
1500 A
255 A
90 A
0 A
Maximum
2000 A
600 A
200 A
0 A
Permissible rated current
120 s
Electrical separation
Safe electrical separation between the signaling contact and the motor cables U, V, W
according to DIN VDE 0160/pr EN 50178, UL 508
Degree of protection to
EN 60529 (IEC 60529)
IP20
Permissible humidity
Humidity classification
according to
DIN EN 60721–3–3
< 90 %
Cl. 3K5 condensation and formation of ice excluded.
Low air temperature 0
°
C
Permiss. ambient temperature
Storage and transport
Operation
–25...+55
°
C
0...+55
°
C
Cooler
Air–cooled, free convection
Weight
approx. 6 kg
approx. 11 kg
approx. 13 kg
Clearance required on the
outside at the sides of the
cable glands
200 mm
Dimensions (W x H x D) [mm]
300 x 150 x 180
300 x 250 x 190
300 x 250 x 260
Connection U, V, W, PE
Torque
Cable cross–section
Cable entry
Screwed connection
Screw connection, 8 x M6
10 Nm
50 mm
2
∅
approx. 40 mm
2 x M50
Screw connection, 8 x M8
25 Nm
2 x
50 mm
2
∅
approx. 40 mm
4 x M50
Screw connection, 14 x M8
25 Nm
2 x
50 mm
2
∅
approx. 40 mm
4 x M50
Conn. X3 (signaling contact)
Cable cross–section
Cable entry
Screwed connection
Terminal, type 226–111 Wago
1.5 mm
2
∅
approx. 9 mm
M16
Terminal, type 226–111 Wago
1.5 mm
2
∅
approx. 9 mm
M16
8 Important Circuit Information