8.16 VPM Voltage Protection Module
8-330
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
When the VPM is tripped or in the event of a temperature fault, signaling contact
X3 opens and interrupts the pulse enable of the SIMODRIVE converter
(see Fig. 8-45).
!
Warning
The signaling contact X3 closes autonomously after t > 2 min or after the
temperature switch has been reset. Therefore, measures must be adopted to
prevent the drive from starting by itself!
off
60
C
ϑ
ϑ
X3
on
55
C
ϑ
2 min
Fig. 8-45
Signaling contact X3 of the VPM
Table 8-7
Technical data, signaling contact X3
Designation
Technical specifications
Contact
1.Operating message
2. Operating v24 V (from external)
NC contact, floating
Switch rating
30 V DC at 0.1 A
Switching voltage/switching current
min 19 V/10 mA
Interrupts when the housing temperature
80
2.5
C
Switches back
55
C
Interruption time after the start of short–cir-
cuit operation
2 min
Note:
This value is valid 15 s after the drive and
pulse enable
Terminal type:
Spring loaded terminal WAGO, type 226–111, cable cross–sectionmax.: 1,5 mm
2
,shiel-
ded cable
Cable gland: max. 9 mm
∅
.
Types VPM 120, VPM 200 and VPM 200 Dynamik
Screwed connection: 1 x M16, z. B. Fa. Pflitsch, Order No.: UNI DICHT
EMV 2165211S05
counter nut: M16: GM216PA.
!
Caution
When a VPM is tripped, the short–circuit thyristor must be safely cleared before
the connected drive can be switched on again. This is only ensured if the motor
has first come to a standstill.
An X3 signal contact that has closed again is not an explicit indication that
this has occurred.
Be especially cautious of this in the event of servicing.
Signal contact X3