9.1 Installation and connecting–up regulations
9-341
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
9.1.2
Mounting conditions, internal cooling
Note
The regulations described in the ”SINAMICS S120 Booksize / SIMODRIVE
System Manual” switchgear cabinet integration system manual
Order No.: 6SL3097–0AT00–0AP
V
must be observed for the heat dissipation!
If the guidelines for installing/mounting SIMODRIVE 611 equipment in the cabi-
net are not carefully observed, this can significantly reduce the service life of the
equipment and result in premature component failure.
The following specifications must be carefully observed when mounting/instal-
ling a SIMODRIVE 611 drive group:
S
Cooling clearance
S
Cable routing
S
Air flow, climate–control equipment
Minimum 100 mm clearance at the top and bottom for cooling.
ÄÄÄ
ÄÄÄ
ÄÄÄ
ÄÄÄ
Channel cable
Incorrect
Correct
ÄÄÄ
ÄÄÄ
ÄÄÄ
ÄÄÄ
40 mm
40 mm
80 mm
SIMODRIVE 611
Cooling clearance
top and bottom
100 mm
100 mm
SIMODRIVE 611
100 mm
Fig. 9-4
Cooling clearance
Air intake temperature, max 40
°
C, at higher temperatures (max 55
°
C), the
power must be reduced (derating).