1.3 Engineering a drive
1-37
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
1.3.5
Checking the permissible power supply rating
The infeed or monitoring module used offers a basic equipping of the electronic
(EP values) and control power supply (AP values).
The following table is used to determine the power supply requirement of a drive
line–up.
The number of modules used should be entered. The product from ”Evaluation
factor individual module” and ”Number of modules” should be formed.
An (additional) monitoring module must be provided if one of these values is
exceeded. The following tables should be used again for the module line–up,
supplied from the monitoring module.
The monitoring module must be located to the left in front of the modules to be
monitored.