Settings on the “Heating engineer” level
Press
and
simultaneously for 3 seconds to activate the “Heating engineer” level for
selecting the plant type and the plant-related variables.
Selecting the plant type on operating line 51:
The required plant type must be selected on operating line 51 using buttons
and
. This
activates all functions required for the respective type of plant and shows the associated operat-
ing lines.
A plant type is comprised of a space heating circuit (6 different types) and a d.h.w. circuit
(5 different types). The 2 types of circuits can be combined in 29 different ways. The following
plant diagrams show all possible combinations.
The controller's operating line 51 only accepts combinations that are possible.
Example of a setting:
25
4
0
Z0
2
1 = heating circuit type 1
2 = d.h.w. circuit type 2
51 Plant
type
1
−
1
(1
−
0 … 6
−
5)
.........................
Type numbers in the following
section
Plant types
A6
Room unit
E2
Load (room)
B1
Flow boiler temperature sensor
LPB
Data bus
B3
Flow temperature sensor for d.h.w.
K6
Electric immersion heater
B31
D.h.w. storage tank temp. sensor / thermostat 1
M1
Heating circuit pump or circulating pump
B32
D.h.w. storage tank temp. sensor / thermostat 2
M3
Charging pump
B5
Room temperature sensor
M4
Circulating pump
B6
Collector sensor
M5
Collector pump
B7
Return temperature sensor (primary circuit)
N1
Controller RVL481
B71
Return temperature sensor (secondary circuit)
Y1
Heating circuit valve
B9
Outside sensor
Y3
Changeover valve
E1
Heat source (boiler / heat exchanger)
Y7
D.h.w. valve