background image

Output Capacity Kit 

15900-407  

4.

 

Align the selected gasket with the matching air passages and mounting holes in the new spool block. 

5.

 

Insert the two 8-32 screws supplied in the kit through the block and gasket. (The high capacity block requires 
the longer screws supplied in the kit.) 

6.

 

Install the block and gasket in the enclosure. Align the spool block and gasket with the air passages and 
mounting holes in the enclosure. Tighten the hardware to 20 lb in. (2.3 N m). 

7.

 

Lift the beam assembly slightly and insert one end of the spool clip into the bronze bushing in the under side of 
the beam assembly. Insert the other end of the spool clip into the countersunk end of the spool at the top of the 
spool block. The longest section of the clip should be positioned inside the V-shaped slot in the front of the 
beam. See Figure 3.

 Do not permanently deform the clip from the original shape.

 

 

Note 

If the spool clip is deformed, refer to the drawing below and carefully re-form the clip as 
shown. 

M

G

0052

4a

1.91" +/- .020"

 

8.

 

Model 760E only: Install the I/P Transducer. Refer to SD760 as needed. 

9.

 

Refer to the Calibration section of SD760 and test the Positioner to ensure that the spool valve is operating 
freely and that there are no air leaks. Check Positioner calibration and calibrate if necessary. 

10.

 

Install the enclosure cover, tighten screws to 20 in lbs (2.3 Nm) and install the Positioner. 

 

CUSTOMER/PRODUCT SUPPORT 

For the location of your local Siemens representative, visit the Siemens Process Instrumentation product support 
page at 

http://www2.sea.siemens.com/Products/Process-Instrumentation/Support/Customer-Support.htm

 
For technical support refer to the following table and click the appropriate link. 

Technical Support 
 

Online Support Request 

http://www.siemens.com/automation/support-request

 

Telephone 

1 800 333 7421 

 

Hours of Operation 

8 a.m. to 4:45 p.m. eastern time, Monday through Friday (except holidays) 

 Technical 

Publications 

in PDF 

http://www2.sea.siemens.com/Products/Process-Instrumentation/Support/PI-User-
Manuals.htm

 then click the product line (e.g. Control Solutions) 

Public Internet Site 

http://www2.sea.siemens.com/Products/Process-Instrumentation

Repair Service 

1 800 365 8766 extension 3187 (for warranty and non-warranty service) 

 

 
 
 
 
 
 
ValvePAC is a trademark of Siemens Energy & Automation, Inc.

 Viton® is a registered trademark of DuPont Performance Elastomers.

 

Nomex is a trademark of 

E. I. du Pont de Nemours and Company.

 

All product designations may be trademarks or product 

names of Siemens Energy & Automation, Inc. or other supplier companies whose use by third parties for their own purposes 
could violate the rights of the owners. 
 
Siemens Energy & Automation, Inc. assumes no liability for errors or omissions in this document or for the application and use 
of information in this document.  The information herein is subject to change without notice. 
 
Procedures in this document have been reviewed for compliance with applicable approval agency requirements and are 
considered sound practice. Neither Siemens Energy & Automation, Inc. nor these agencies are responsible for repairs made by 
the user. 
 

4

  

January 

2009 

 

Summary of Contents for 760 Series

Page 1: ...t Viton Nomex 1 Valve Block Gasket Neoprene Nylon 1 8 32 Spool Block Mounting Screws 2 Kit Installation Instruction 1 KIT INSTALLATION The area in which the Kit is installed must be clean Hands and tools must also be clean Keep all Kit parts in the supplied bag until they are to be installed to prevent contamination by dust dirt fumes and other environmental contaminants Contaminants can cause the...

Page 2: ...y Remove the I P transducer Refer to SD760 as needed See Figure 1 FIGURE 1 I P Transducer Cam and CAMLOC not shown 7 At the spool block see Figures 2 and 3 carefully note how the spool clip is installed At the top of the block the clip is inserted in the countersink in the end of the spool At the bottom of the block the clip end is in the bronze bushing in the underside of the beam assembly 8 Remo...

Page 3: ...s tubular container Place a finger over the spool hole in the bottom of the spool block to prevent the spool from falling through the block Insert the spool long journal first into the top of the spool block 3 Select a gasket from the Output Capacity Kit see Figure 4 High temperature application or an ozone atmospheric condition Select the Viton Nomex gasket Other applications Select the neoprene ...

Page 4: ...ntative visit the Siemens Process Instrumentation product support page at http www2 sea siemens com Products Process Instrumentation Support Customer Support htm For technical support refer to the following table and click the appropriate link Technical Support Online Support Request http www siemens com automation support request Telephone 1 800 333 7421 Hours of Operation 8 a m to 4 45 p m easte...

Reviews: