On-Line Operation
UMSITRPDS3-1
November
2010
6-16
6.2.10 Select Measured Value to Display
Mode 13 has three options:
•
Display output current in mA
•
Display output current in % (of the set measured range)
•
Display input pressure in engineering units selected in mode 14
To make a selection:
1.
Press the M pushbutton to enable mode 13.
2.
Press either arrow pushbutton to select the desired option.
3.
Press the M pushbutton to save the selection.
6.2.11 Select the Displayed Input Pressure Engineering Unit
Mode 14 selects the engineering units that are to be assigned to the displayed input pressure (selected in
mode 13). Available selections are shown in Figure 6-3. The engineering unit set using HART (Section
6.4.11) has no effect on this local setting.
1.
To select the engineering unit:
2.
Press the M pushbutton to enable mode 14.
3.
Press either arrow pushbutton to step through the available engineering units list.
4.
Press the M pushbutton to save the selection.
If the capacity of the digital display is exceeded, 9.9.9.9.9 will appear.
Summary of Contents for 7MF4033 series
Page 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Page 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Page 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Page 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Page 197: ......
Page 198: ......
Page 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Page 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Page 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Page 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...