Calibration and Maintenance
UMSITRPSD3-1
November
2010
7-10
Device Parameters After Replacing Electronics Module or Measuring Cell
Parameter Description
Stored
Not Stored
(2)
Configuration
Dependent (1)
Damping x
AO alarm type
x
Alarm LRV/URV
x
Saturation alarm activation
x
Transmission functions
x
Square root switch point
x
Pressure units
x
Polling address
x
Tag x
Mechanical construction:
electronics/sensor
x
Min/max pointer
x
Zero calibration
x
Upper/lower sensor calibration points
x
Service interval
x
Minimum span
x
Measurement limits
Sensor limits
Explosion protection
x
Sensor serial number
x
Working hour meter, sensor
x
Working hour meter, electronics
x
Firmware/Software revision
x
Min/max pointer, electronics
x
Calibration interval, electronics
x
Saturation alarm duration
x
Local display unit
x
Current calibration
Message
x
Descriptor
x
Date
x
Final assembly number
x
Bargraph activation
x
Write protection mode
x
Hardware revision
x
Device revision
x
Unit tracking
x
Notes:
(1) Column specifies sensor data that remains after changing electronics or sensor.
(2) Dependent on electronics module version. Check the parameters and configure as needed.
Summary of Contents for 7MF4033 series
Page 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Page 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Page 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Page 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Page 197: ......
Page 198: ......
Page 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Page 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Page 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Page 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...