UMSITRPDS3-1
Installation
November 2010
4-13
+
_
- +
4-20 mA
Hazardous
Location
Non-Hazardous
Location
Model 353/354
Terminals
AIN1
See Note 4
20
I
O
Transmitter
Terminals
See Note 5
250
See Note 1
See Note 2
See Note 6
See Note 3
21
6
GND
5
Common Ground Bus
MG
00350a
1. Minimum network resistance equals the sum of the barrier resistances and the current sense resistor. Minimum
value is 250 Ohms; maximum value is 1100 Ohms.
2. Connect the HART Communicator as shown in Figure 2-2 for hazardous and non-hazardous locations. The
HART Communicator is a non-polar device.
3. Supply and return barriers are shown. Interconnect all cable shields and ground only at the barriers.
4. Procidia (Model 353R or i|pac) terminal assignments are:
•
34 – Analog Input 1 +
•
35 – Analog Input 1 Common
•
33 – 24 Vdc
•
18 – Station Common
5. For access to transmitter field terminals, remove the enclosure cap.
6. Maximum cable length is as calculated using the formula in section 4.3.6.
FIGURE 4-8 Model 353/354 to Transmitter Connections (Analog Mode)
Summary of Contents for 7MF4033 series
Page 48: ...Model 275 Universal Hart Communicator UMSITRPDS3 1 November 2010 2 26 ...
Page 86: ...Installation UMSITRPDS3 1 November 2010 4 34 ...
Page 152: ...Calibration and Maintenance UMSITRPSD3 1 November 2010 7 20 ...
Page 158: ...Circuit Description UMSITRPDS3 1 November 2010 8 6 ...
Page 197: ......
Page 198: ......
Page 200: ...Model Designations and Specifications UMSITRPDS3 1 November 2010 9 42 ...
Page 204: ...Glossary UMSITRPDS3 1 November 2010 10 4 ...
Page 208: ...Appendix A Online Configuration Map UMSITRPDS3 1 11 4 November 2010 ...
Page 216: ...Appendix C Elevation and Suppression Correction UMSITRPDS3 1 13 4 November 2010 ...