!PPENDIX
3$
6
# ' #
2100 EXTERNAL TRIP FUNCTION
2101 EXT.TRIP
State of external trip function
OFF
[ ] off
ON
[ ] on
BLOCK TRIP REL
[ ] Block trip relay
2102 T-DELAY
Time delay of external trip function
min. 0.02
s
max. 60.00
¬¬¬¬
2103 T-RESET
Reset delay after trip has been initiated
min. 0.00
s
max. 60.00
¬¬¬¬
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
2200 TRANSFER TRIP
2201 TRIP SEND
State of transfer trip send function
OFF
[ ] off
ON
[ ] on
2202 T-SEND-DEL
Send signal delay for transfer trip
min. 0.00
s
max. 60.00
¬¬¬¬
2203 T-SEND-PRO
Send signal prolongation for transfer trip
min. 0.00
s
max. 60.00
¬¬¬¬
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
2300 TRIP RECEIVER
2301 TRIP RECV.
State of transfer trip receiver
OFF
[ ] off
ON
[ ] on
BLOCK TRIP REL
[ ] Block trip relay
2302 T-RECV-DEL
Receive signal delay for transfer trip
min. 0.00
s
max. 60.00
¬¬¬¬
2303 T-RECV-PRO
Receive signal prol. for transf. trip receiver
min. 0.00
s
max. 60.00
¬¬¬¬
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
2600 BACK-UP OVERCURRENT PROT
2601 BACKUP O/C
State of back-up overcurrent protection
OFF
[ ] off
ON
[ ] on
BLOCK TRIP REL
[ ] Block trip relay
2603 I>>
Pick-up value for high current stage I>>
min. 0.10
I/InLn
max. 30.00
¬¬¬¬
Summary of Contents for 7SD502