Argus 2-5xx software release history
April
2004
2434H80040 R4
Minor change: Min P/F, E/F settings now 0.05 x In
Jan 2004
2434H80040 R3
Additional Features: Added CT Failure functionality
Maximum Demand Added for Ia, Ib, Ic, W, Vars
General Alarms added to scrolling fault screen
Nov 2005
2434H80040 R8
Highset and Lowset setting steps revised between 2.5xIn and 3.0xIn
July 2005
2434H80040 R7
ACD bit in IEC 60870 library corrected
Mar 2005
2434H80040 R6
CBF logic modified, timer will run while trip is being issued and I >
ICBF Level
Aug 2004
2434H80040 R5
Modification to “checking settings” screen at switch on. Corrected “CT
Failure” setting display when configured to show
PRIMARY/SECONDARY Amps.
ASDU4 measurands return value 0 correctly.
April 2004 2434H80023 R6
Minor change: Min P/F, E/F settings now 0.05 x In
Jan 2004
2434H80023 R5
Additional features:
Modbus added
Additional features:
CT Failure function added
Minor change:
IEC60870 Class 2 measurands
Sep 2003
2434H80023 R4
Additional features:
CBF Level detectors added
Minor change:
DTL timers extended to 5 minutes
Mar 2003
2434H80023 R3
Minor change: Time synch via IEC870
Nov 2002
2434H80023 R2
Minor change:
communications with ReyDisp
Jun 2002
2434H80023 R1
Minor change:
power on alarm added
Feb 2002
2434H80022 R3
Additional features:
CB fail (all models).
Oct 2001
2434H80022 R2
Additional features:
external trip via status input.
Minor change:
SEF 2
nd
stage can be disabled.
Feb 2001
2434H80022 R1
Additional features:
general alarms, status input inversion,
resettable instruments, output relay pulse length setting, 10 second
delay on trip test.
Additional features:
CB fail, trip circuit supervision (single-pole
models).
Apr 2000
2434H80021 R6
Additional features:
New model variants
Jan 2000
2434H80021 R5
Minor change:
current meter averaging.
Jul 1999
2434H80021 R4
Minor change:
status group select
May 1999 2434H80021 R3
Additional features:
default instruments
Mar 1998
2434H80020 R1
Additional features:
new expansion board (8SI).
Additional features:
clock synchronisation using status input
Additional features:
new directional SEF model and -90
°
characteristic angle available for E/F and SEF
Sep 1997
2434H80019 R4
Minor change:
settings displayed in ReyDisp
Jul 1997
2434H80019 R3
Additional features:
status input pick-up and drop-off delays
added.
Additional features:
CB fail, trip circuit supervision (all
expanded I/O models).
Minor change:
separate settings for P/F, E/F and SEF current
ratings.
Minor change:
sum of I
2
setting range.
Apr 1997
2434H80018 R2