7SG11 Argus User Manual
©2013 Siemens Protection Devices Limited
P20006 Page 28 of 37
4.4 Commissioning Record Tables
These tables should be completed during commissioning as a record of the commissioning tests.
Relay Type
Serial Number
Substation
Feeder
Identity
Tester
Date
4.4.1 Secondary Injection Tests
4.4.1.1 Overcurrent
IDMTL/DTL Characteristic
Table 4-4
Pick-up/Drop-off Results
Pole
Pick-up setting Measured pick-up
Pick-up error
( 4% of 105%)
Measured
drop-off
Drop-off error
( 95% of pick-up)
Phase A
Phase B
Phase C
E/F
Table 4-5
Timing Characteristic Results
2x Is
5x Is
Pole
Characteristic
(NI, VI, EI,
LTI, DTL)
Delay
Error
( 5% or
30 ms)
Delay
Error
( 5% or
30 ms)
Phase A
Phase B
Phase C
E/F
Lowset and Highsets
Table 4-6
Lowset setting results
Pole
Lowset setting
Measured pick-up
Error
( 5% of setting)
Phase A
Phase B
Phase C
E/F