7SG11 Argus Technical Reference
©2013 Siemens Protection Devices Limited
P20007 Page 24 of 71
Setting name
Range (
bold
= default)
Units Notes
Export power / lag VAr Sign
+ve/+ve
, +ve/-ve, -ve/+ve, -ve/-ve,
2.2.4 Identifier
User defined identifying text can be programmed into the relay using the
System Config.:
Set Identifier
setting. This
text is displayed on the title screen of the Argus and is used in communications with ReyDisp to identify the Argus
relay.
Table 2-5
Identifier Setting
Sub-menu:
System Config.
Setting name
Range (
bold
= default)
Units Notes
Set Identifier
ABCDEFGHIJKLMNOPQRSTUV
WXYZ1234567890 -+/
(default =
Argus n
e.g.
Argus 1
)
Up to 16 characters
2.2.5 General Alarms
General Alarms are user-defined text messages displayed on the LCD when mapped status inputs are raised. Up
to five general alarms can be programmed, however this is limited by the number of status inputs on the device.
Each general alarm can be triggered from one or more status inputs, as programmed by the appropriate setting.
The
System Config.:
SET Alarm n
setting (where
n
is the alarm number) allows the user to programme a text message
which is displayed on the LCD when the associated status inputs are raised, as set by
Status Config.:
Alarm n
. The
general alarm will also generate an event. If it is wished to operate an output contact for the alarm this can be
programmed using the status input to output relay mapping (section 2.11).
If multiple alarms are active simultaneously the messages are linked in series in a rolling display on the LCD,
separated by a ‘+’ character. If it is necessary to display alarm messages longer than 13 characters then a status
input may be mapped to multiple alarms, in which case a longer message will result.
All general alarms raised when a Fault Trigger is generated will be logged into the Fault Data record, transient
general alarms will thus be latched and displayed at the end of the scrolling ‘Fault Data’ screen, see section
2.13.2
Table 2-6
General Alarm Settings
Sub-menu:
System Config.
Setting name
Range (
bold
= default)
Units Notes
SET Alarm 1
SET Alarm 2
…
SET Alarm 5
ABCDEFGHIJKLMNOPQRSTU
VWXYZ 1234567890 -+/
(
ALARM n
)
Up to 13 characters per name
Sub-menu:
Status Config.
Setting name
Range (
bold
= default)
Units Notes
Gn Alarm 1
Gn Alarm 2
…
Gn Alarm 5
mappable to any status input
(default=
_ _ _ _ _ _ _ _ _
)
Default - not mapped to any status
2.2.6 Direction Tags
Argus 2 and Argus 6 only
User defined text names for the Forward and Reverse directions can be applied to assist in identification of fault
direction. For example, ‘FWD’ could be renamed ‘FEEDER X’, and ‘REV’ renamed ‘BUSBAR Y’.
Note: Directional Relay convention is such that current flowing away from a busbar flows in the Forward direction.
These identifiers are used in the fault records to identify the direction of the fault.