Operating Instructions

Temperature Controller Relay 

7UG0 480-1IU20

7UG0

IEC 60947-5-1

Please read and understand these instructions before installing, 
operating, or maintaining the equipment.

DANGER

Hazardous voltage can cause death or serious injury.
Disconnect power before working on equipment.

CAUTION

Reliable functioning of the equipment is only ensured 
with certified components.
Overvoltage category III 
(Refer IEC 60947-1)

NOTICE

This product has been designed for environment A. Use of this product 
in environment B may cause unwanted electromagnetic disturbances in 
which case the user may require to take adequate mitigation measures.

Technical Data

Designation

7UG0 480-1IU20

Type

Temperature controller relay

Control voltage

85 - 270V AC/DC  (±15%) , 50/60Hz

Operating conditions

0 to 50°C ,  
upto 95%RH (non-condensing)

Input Sensors

Thermocouple (J,K,T,R,S) /  
RTD (PT100)

Filter time

0.2 to 10 sec

Digital output for external SSR

12VDC, 50mA

Accuracy

For J,K,T inputs: ±(2% of s 1°)
For R,S inputs: ±(2% of s 2°)
For RTD inputs: ±(2% of s 1°)
(20 min of warm up time for TC inputs)

Control action

1. PID control with auto or self tuning
2. ON - OFF control
3. Heat - Cool with auto tuning

Propostional band (P)

0°C to 400°C / 1.0°F to 750°F

Integral  time (I)

0 to 9999 sec

Derivative  time (D)

0 to 9999 sec

Cyclic time

0 to 99.9 sec

Hysteresis width

0.1 to 99.9°

Dwell timer

0 to 9999 min

Manual reset value

-19.9 to 19.9°

Heat Cool PID

Control Method: PID
Proportional band - Cool: 0 to 400°C
Cyclic time - Cool: 0.1 to 99.9sec
Dead band: Programmable from 
setpoint low limit to setpoint high limit

Power consumption @ 230V AC

6VA

Rated current of relay output 
(@250VAC)

5A (AC12), 2A (AC15)

SCPD for relay output (For 
Short circuit current of 1kA as 
per IEC 60947-5-1)

6A, gL, HRC fuse

Terminal connections

7UG048...

0.5 Nm

Solid

1 x (0.75 to 2.5) mm

2

2 x 0.5 to 2 x 1.5 mm

2

Stranded with end sleeve

1 x (0.5 to 2.5) mm

2

2 x (0.5 to 1.5) mm

2

N

L

C

NO

TC

LOAD

R

C

TC

Snubber

MOV

TC

TC

N

L

Snubber

C

NO

R

C

Contactor

LOAD

C

MOV

For bigger loads, use interposing relay / contactor

For load current less than 0.5A

Summary of Contents for 7UG0 480-1IU20

Page 1: ...VDC 50mA Accuracy For J K T inputs 2 of setting 1 For R S inputs 2 of setting 2 For RTD inputs 2 of setting 1 20 min of warm up time for TC inputs Control action 1 PID control with auto or self tuning 2 ON OFF control 3 Heat Cool with auto tuning Propostional band P 0 C to 400 C 1 0 F to 750 F Integral time I 0 to 9999 sec Derivative time D 0 to 9999 sec Cyclic time 0 to 99 9 sec Hysteresis width ...

Page 2: ...at a fixed temperature for a defined period Once the process reaches the setpoint dwell timer starts to count from zero until time out After the time is completed control output goes OFF and auxiliary output energies as an alarm 5 Auto tuning AT The Auto tuning function automatically computes and sets the proportional band P integral time I Derivative time D ARW and cycle time CYC T as per process...

Page 3: ... Online menu for timer Anti reset windup DEV ABS Relay 2 type When ACT2 RE FD For CNTL PID For CNTL PID For CNTL PID For CNTL PID For CNTL PID For CNTL PID For CNTL PID HC YES When DWEL YES CONFIGURATION INSTRUCTIONS Press once to view online parameters Press for 3 sec to enter Level 2 Press once to view next parameter in configuration menu Press for 3 sec to enter Level 1 Press once to view previ...

Page 4: ...ations when taking the product out of service The local customer care service is available at any time to answer disposal related questions Customer Care Toll free no 1800 209 0987 Email ics india siemens com Order No A5E40846268A Resolution 1 Resolution 0 1 RANGE INPUT TYPE UNIT FOR THERMOCOUPLE J 199 to 750 C When an error has occurred the upper display indicates error codes as given below Error...

Reviews: