– Irradiation with HF Field,
single frequencies
IEC 60255-22-3, IEC 61000-4-3, Class
III
10 V/m
amplitude-modulated
80; 160; 450; 900 MHz; 80 % AM 1 kHz;
duty cycle > 10 s
pulse-modulated
900 MHz; 50 % PM,
repetition frequency 200 Hz
– Fast Transient Disturbance Variables/Burst
4 kV; 5/50 ns; 5 kHz; 100 kHz;
Burst length = 15 ms;
IEC 60255-22-4, IEC 61000-4-4,
repetition rate 300 ms; both polarities;
Class
IV
R
i
= 50
Ω
; test duration 1 min
– High Energy Surge Voltages (SURGE)
IEC 61000-4-5, Installation Class 3
Impuls: 1.2/50 µs
Power supply
common mode: 2 kV; 12
Ω
; 9 µF
diff. mode: 1 kV; 2
Ω
; 18 µF
Relay output (
GOK
)
common mode: 2 kV; 42
Ω
; 0.5 µF
Communication interfaces
common mode: 2 kV; 2
Ω
; 18 µF
– High Energy Surge Voltages (SURGE)
TBR14 (3), ETS 300046–3 Sect. 5.7.1
Communication interfaces
common mode: 2 kV; 15
Ω
; 18 µF
– Line Conducted HF, amplitude modulated
10 V: 150 kHz to 80 MHz; 80 % AM; 1 kHz
IEC 61000-4-6, Class
III
– Power System Frequency Magnetic Field
IEC 61000-4-8, Class
IV
30 A/m continuous; 300 A/m for 3 s; 50 Hz
IEC 60255-6
0.5 mT; 50 Hz
– Oscillatory Surge Withstand Capability
2.5 kV (Peak Value); 1 MHz;
τ
= 15 ms;
IEEE C37.90.1
400 surges per s; test duration 2 s;
R
i
= 150
Ω
– Fast Transient Surge Withstand Capability
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
IEEE C37.90.1
repetition rate 300 ms; both polarities;
R
i
= 50
Ω;
test duration 1 min
– Radiated Electromagnetic Interference
35 V/m; 80 MHz to 1000 MHz
IEEE C37.90.2
– Damped Oscillations
2.5 kV (Peak Value), polarity alternating
IEC 60694, IEC 61000-4-12
100 kHz, 1 MHz, R
i
= 200
Ω