Synchronizing up to 6 Protection Devices Using 2 Channels
Certain applications, such as line differential protection, require a high-precision second pulse in addition to
the protocols for time synchronization. The Sync-Transceiver can forward both types of time information in
parallel to up to 6 SIPROTEC 4 or SIPROTEC 5 devices using the cascadable Y bus cable 7XV5105-0AAxx.
Table 3-7
DIP Switch Positions in the Sync-Transceiver
Switch
Position
S1/1
Application-specific (light idle state mode as per the system configuration at the optical-fiber
input R1)
S1/2
Application-specific (light idle state mode as per the system configuration at the optical-fiber
input R2)
S1/3
Open (2-channel mode)
S1/4
Open
[dw_synchron_7SD5x-devices_in_separat-systems, 1, en_US]
Figure 3-7
Synchronizing Line Differential Protection Devices in Separate Plants
3.8
Application Examples
3.8 Synchronizing up to 6 Protection Devices Using 2 Channels
34