INSTALLATION INSTRUCTIONS 

See Figure 1

 

1. 

Turn “OFF” and lock out the power to the equipment in which the GFCI is to be installed. 

2. 

Move th

e handle of the breaker (A) to the “OFF” position. 

3. 

Engage the back of the GFCI with the mounting tabs in the panelboard. For the plug in type, 
push down firmly on the front end to engage the line terminal stab. For the bolt in type, securely 
fasten the line terminal to the panelboard load bus. 

4. 

Connect the panelboard neutral (pig-tail) (B) wire to a load center or panel neutral bar (C) as 
shown in the Fig.1. Torque per specifications on wiring diagram or equipment label. 

5. 

Strip insulation off load wires to a length of 3/8 in. 

6. 

Connect load neutral wire (D) into terminal (H) and load power wires (E and F) to terminals (G 
and I) as shown in Fig.1.  Ensure that wire connectors are properly torque per breaker label 
specification. 

7. 

Check wiring to ensure that there are no shared neutral connections. 

8. 

Place GFCI 

“Breaker Trouble Shooting Card label” in the appropriate locations. 

9. 

Instruct the occupants on test procedures and importance of periodic testing. 

TESTING INSTRUCTIONS 

1. 

Turn on power to load center or panelboard. 

2. 

Turn “ON” the GFCI handle. 

3. 

Press white test button (F) as shown in Fig.1. 

 
The GFCI breaker is functioning properly when: 
1. 

The circuit is interrupted. 

2. 

The handle moves to the tripped center position (K) as shown in Fig.1.

 

 

If the LED (J) stays on and/or the device does not trip, this indicates the device is no longer 
functioning properly and should be replaced by a qualified electrician.

 

TROUBLESHOOTING 

 

Problem: 

GFCI does not trip after pressing the test button.

 

Possible Cause 

 

Solution 

Panelboard is not energized 

Check to ensure that the panelboard is energized. 

The circuit breaker handle is in the “OFF” position 

The circuit breaker handle must be in the “ON” position. 

The circuit breaker is in the tripped position 

Reset the circuit breaker by swi

tching the handle to the “OFF” position and then to the “ON” position. 

Panel neutral (pigtail) is not connected to the 
neutral bus bar 

Check that the load power wire, panel neutral (pig- tail) wire and load neutral wire are properly 
connected. 

Problem: 

GFCI trips immediately after the GFCI or a connected device has been turned on.

 

Possible Cause 

 

Solution 

The ground-fault circuit interrupter is not wired 
properly

 

Check that the load power wire, panel neutral (pig- tail) wire and load neutral wire are properly 
connected. A qualified electrician should make the repairs. 

Short-circuit 

If the GFCI trips when a device is turned on, remove the device from the circuit and turn the GFCI on. If the 
GFCI does not trip this would indicate a short in the device. A qualified electrician should make the repairs. 

GFCI does not have a dedicated neutral 

Check wiring to ensure that there are no shared neutral connections. 

GFCI does not have the correct neutral 

Check wiring to ensure the load power wire and load neutral wire are from the same branch circuit 

A ground-fault condition exists 

 

If the GFCI trips, then you have a ground-fault condition.  A common ground fault is a grounded 
neutral, which may only cause a trip under load.  This occurs when the neutral conductor contacts 
a ground conductor.  

Reset the circuit breaker by switching the handle to the “OFF” position and 

then to the “ON” position. If the GFCI trips again, call a qualified electrician to make the repairs. 

Problem: 

GFCI trips after it has been turned on, but not immediately 

 

Possible Cause 

 

Solution 

The ground-fault circuit interrupter is not wired 
properly.  

Check that the load power wire, panel neutral (pig- tail) wire and load neutral wire are properly 
connected.  A qualified electrician should make the repairs. 

Overloaded circuit 

There are probably too many devices plugged into the circuits and overloading the GFCI. 

A ground-fault condition exists 

 

Reset the circuit breaker by switching the handle to the “OFF” position and then to the “ON” 
position. If the GFCI trips again, call a qualified electrician to make the repairs. 

If solutions do not work, the 

GFCI circuit breaker must be replaced.

 

GFCI will need to be replaced if the following conditions are displayed by the LED 

 

LED (J):   On or Blinking 

 

Summary of Contents for 814913A

Page 1: ...rga eléctrica de línea a línea 2 Para máxima protección contra descargas eléctricas no se deben conectar al circuito de carga de esta unidad las cocinas eléctricas ni las secadoras de ropa cuyas estructuras tengan la conexión a tierra mediante el conductor del circuito conectado a tierra 3 Los cortacircuitos GFCI deben ser instalados y reparados únicamente por electricistas calificados 4 Debe inst...

Page 2: ...F position and then to the ON position Panel neutral pigtail is not connected to the neutral bus bar Check that the load power wire panel neutral pig tail wire and load neutral wire are properly connected Problem GFCI trips immediately after the GFCI or a connected device has been turned on Possible Cause Solution The ground fault circuit interrupter is not wired properly Check that the load power...

Page 3: ...doit être sur Marche La manette du disjoncteur est en position déclenchée Réarmer le disjoncteur en mettant la manette sur Arrêt puis sur Marche Le fil neutre en queue de cochon destine au tableau n est pas branché sur une barre de neutre Vérifier que le fil de phase le fil de neutre en queue de cochon raccordé au tableau et le fil de neutre du circuit sont bien branchés Problème Le GFCI se déclen...

Page 4: ... cortacircuito moviendo la manija hasta la posición OFF apagado y luego hasta la posición ON encendido El cable neutro del panel cable flexible de conexión no está conectado a la barra del bus neutro Verifique que el cable de carga de corriente el cable neutro del panel cable flexible de conexión y el cable de carga neutro estén conectados correctamente Problema El GFCI se dispara inmediatamente d...

Reviews: