20
Revision 04 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9
2.4.4. Current & Voltage transformer
Current transformer
Voltage transformer
Voltage transformer with fuse
Features
• According to IEC 60044-1
• 4MA7 block-type current
transformer, cast-resin insulated
• According to IEC 60044-2
• Cast-resin insulated
• According to IEC 60044-2
• Cast-resin insulated
• Replaceable primary fuses
Mounting
location
The block-type current transformers
can be installed in the cable
compartment of switching device
panels, bus sectionalizing panels or
at the busbar in the metering panel.
VB36M voltage transformers can be
mounted on the metering truck, in
the cable compartment or at the
busbar. The transformers on the
metering truck can be equipped with
fuses.
VBF36-KDS voltage transformers
with fuses can be mounted in
cable compartment as
withdrawable, only in free standing
version.
Pictures
2.5. Interlocks
2.5.1. Panel interlocks with circuit breaker
Mechanical interlocks
Action
Interlocking condition
Closing the circuit-breaker
Low-voltage plug connector on circuit-breaker is plugged in; switching device
truck has reached defined end position
Removing the low-voltage plug connector from the circuit-breaker
Switching device truck is in TEST position
Opening the high-voltage door
If the switching device truck is in the panel: Switching device truck is in TEST
position
Closing the high-voltage door
If the switching device truck is in the panel: Low-voltage plug connector on
circuit-breaker is plugged in, and locking gates of guide rails are closed
Racking the switching device truck to SERVICE position
High-voltage door is closed and feeder earthing switch is open
Racking the switching device truck to TEST position
High-voltage door is closed and circuit-breaker is open
Replacing the switching device truck
Switching device truck can only be replaced if the coding is identical
Additional interlocks (optional)
Action
Interlocking condition
Racking the switching device truck
Electromechanical interlock
Mechanical locking device with padlock for switching device truck
2.5.2. Panel interlocks with earthing switch
Mechanical interlocks
Action
Interlocking condition
Operating the feeder earthing switch
Switching device truck is in TEST position
Racking the switching device truck to SERVICE position
Feeder earthing switch is in OPEN position
Additional interlocks (optional)
Action
Interlocking condition
Operating the feeder earthing switch
Electromechanical interlock
Padlock
2.6. Accessories
Standard accessories
The below accessories are supplied with the switchgear:
Operating rod for closing / opening the circuit breaker
mechanically
Double bit key with a diameter of 3 mm for opening and
closing the door of the low voltage compartment