74
Revision 04 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9
Operating lever for the withdrawable voltage transformers
mechanism
6.5. Opening and closing the high voltage compartment door
DANGER!
High voltage! Danger!
Isolate the busbars in the busbar compartment and the cable or bar connections in
the connection compartment
before
opening the high-voltage door. Observe the
Five Safety Rules.
Do not operate the panel with the high voltage door open.
NOTE!
The following instructions for opening and closing the high-voltage door apply to:
Circuit breaker panels
Disconnecting panels
Metering panels
Opening the high voltage compartment door
Closing the high voltage compartment door
Preconditions
•
Truck in test position
Either without truck or:
•
Truck inserted in TEST position
•
Low voltage connector plugged in
Procedure
Pull the door handle upwards and open the door
Pull the door handle upwards and close the door
Push the door handle downwards
Result
High-voltage door is open.
High-voltage door is closed.
1
st
step
Close
the
door
2
nd
step