861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
171/214
Operation
7
➭ Push the left-hand control gate to the left.
8
➭ Switch the left-hand three-position disconnector to OPEN position
(insert the operating lever for the DISCONNECTING function and turn
180° counter-clockwise).
9
➭ Remove the operating lever for the DISCONNECTING function.
The interrogation lever and the left-hand control gate return to their initial
position.