864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
107/214
Installation
27
Removal of voltage transformers
27.1
Removal of voltage transformers type 4MT3 from the busbar
DANGER
High voltage! Danger! Before starting installation work at the busbar voltage transformers, the
busbar must have been isolated and earthed.
➭ Isolate and earth the busbar.
ATTENTION
If a power-frequency voltage test has to performed before putting the switchgear into
operation,
➭ already mounted
non-disconnectable
busbar voltage transformers which are not suitable
at least for tests at 80% values according to IEC 62271-200 must be removed.
ATTENTION
Sensitive parts of the switchgear may be damaged during installation work at the busbar and
the busbar housings.
➭ While working at the busbars or the busbar housings, prop up only on the aluminum
housings and the frame.
➭ Do not prop up on sensitive parts of the switchgear like gas pipes, bursting discs, shafts,
etc.
ATTENTION
While working on metal-coated voltage transformers, the coating may be scratched or
damaged. Then, the voltage transformers cannot be touched anymore.
➭ Work carefully while mounting metal-coated voltage transformers.
➭ Take care not to scratch or damage the metal coating.
Fig. 115: 4MT3 busbar voltage transformer
(shown without cover)
①
4MT3 voltage transformer
②
Low-voltage plug connector
③
Adapter plate
④
Voltage transformer
mounting plate
⑤
Busbar housing
⑥
Distance sleeves
⑦
Outside-cone bushing
⑧
Hole with setnut for
press-out bolts