864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
163/214
Operation
➭ Push the control gate to the left.
➭ Push the control gate to the left.
✔ The opening for the DISCONNECTING function is free.
To switch the DISCONNECTING function of three-position disconnector to the desired end
position (CLOSED or OPEN), perform the following actions:
➭ Turn the emergency operating lever until the position indicator changes to CLOSED or OPEN
position.
➭ Remove the emergency operating lever again.
✔ The control gate returns to its initial position.
✔ The opening for the DISCONNECTING function is closed.
Fig. 189: Emergency operation of the DISCONNECTING function of the three-position disconnector
Position of emergency
operating lever
Marking of slot
Position of three-position
disconnector
horizontal
at the bottom
CLOSED
at the top
OPEN