79 / 92
Siemens
Actuators SAX.., SAY.., SAV.., SAL.. for valves
CE1P4040en
Building Technologies
Technical data
2018-12-05
SAY..
SAX..
SAV..
SAL..
Environ-
mental
conditions
Operation
IEC 60721-3-3
Climatic conditions
Class 3K5
Mounting location
Indoors (weather-protected)
6)
Temperature General
-15…55 °C
Humidity (noncondensing)
5…95% r.h.
Transport
IEC 60721-3-2
Climatic conditions
Class 2K3
Temperature
-25…70 °C
Humidity
<95% r.h.
Storage
IEC 60721-3-1
Climatic conditions
Class 1K3
Temperature
-15…55 °C
Humidity
5…95% r.h.
Max. media temperatur when mounted
on valve
130 °C
130 °C
130 °C
5)
120 °C
SAY..
SAX..
SAV..
SAL..
Directives
and
Standards
Product standard
EN60730-x
Electromagnetic compatibility
(Application)
For residential, commercial and industrial environments
EU Conformity (CE)
A5W00000333
1)
CE1T4501x1
7)
CE1T4503xx
7)
CE1T4502X1
7)
RCM Conformity
AC 230 V A5W00000334
1)
CE1T4515X4
7)
CM1T4503_C1
7)
-
EAC Conformity
Eurasia conformity for all SA..-variants
UL, cUL
AC 230 V -
AC/DC 24 V UL 873 http://ul.com/database
Environ-
mental
compati-
bility
The product environmental declarations contain data on environmentally
compatible product designs and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal):
7173310559Ben
7)
7173310559Ben
7)
A6V101083254
7)
7173310522A
7)
CE1E4502en
7)
Dimensions
See "Dimensions" (page 84)
Weight
Excl. packaging
See "Dimensions" (page 84)
Accessories
8)
Potentiometer ASZ7.5
0…1000
Ω
± 5%
Voltage
DC 10 V (SELV)
Current rating
< 4 mA
Auxiliary switch ASC10.51
Switching capacity
External supply line protection
US installation, UL & cUL
AC 24…230 V, 6 (2) A, floating
See section power supply
AC 24 V class 2, 5 A general purpose
Stem heating element ASZ6.6
Power supply
AC / DC 24 V ± 20%
Power consumption
at 50 Hz
50 VA / 30 W
Inrush current (cold)
Max. 8.5 A (max. Temperatur 85 °C / 185 F)
Function module AZX61.1 for SA..61..
Switching capacity
AC 24…230 V, 6 (2) A, floating
External supply line protection
See section power supply
US installation, UL & cUL
AC 24 V class 2, 5 A general purpose
1)
Observe acting direction of DIL switches
2)
AWG = American wire gauge
3)
Also with weather shield ASK39.1
4)
SAL.T20 / T40 have a minimum holding torque of 14 Nm
5)
Up to 150 °C with horizontal mounting position
6)
SAX61../MO is not suitable for outdoor applications.
7)
The documents can be downloaded from
http://siemens.com/bt/download
8)
UL recognized component