7SG11 Argus 8 Performance Specification
Fast Transient – IEC 60255-22-4 Class IV
Variation
4kV 5/50ns 2.5kHz repetitive
≤
5%
Conducted RFI – IEC 60255-22-6
Variation
0.15 to 1000MHz - 10V
≤
5%
12.3 Emissions
Radiated Limits – IEC 60255-25
Frequency Range
Limits at 10m
Quasi-peak dB (µV/m)
30 to 230MHz
40
230 to 1000MHz
47
Conducted Limits – IEC 60255-25
Limits dB (µV)
Frequency Range
Quasi-peak Average
0.15 to 0.5MHz
79
66
0.5 to 30MHz
73
60
12.4 Mechanical
Vibration (Sinusoidal) – IEC 60255-21-1 Class 1
Variation
Vibration response
0.5gn
≤
5%
Vibration endurance
1.0gn
≤
5%
Shock and Bump – IEC 60255-21-2 Class 1
Variation
Shock response
5 gn 11ms
≤
5%
Shock withstand
15 gn 11ms
≤
5%
Bump test
10 gn 16ms
≤
5%
Seismic – IEC 60255-21-3 Class 1
Variation
Seismic Response
1gn
≤
5%
Mechanical Classification
Durability
In excess of 106 operations
Qualification
Product :- C compliant to all relevant EU directives.
Quality Systems :- accredited to ISO 9001
©2010 Siemens Protection Devices Limited
Chapter 2 Page 8 of 9