slight increase of the room temperature causes an immediate drop of the flow
temperature.
To activate the function, following must be considered:
•
A room sensor must be connected
•
"Room influence" must be set to 100%
•
There should be no controlled valves in the reference room (mounting location of
the room sensor) (If such valves are installed, they must be set to their fully open
position)
Room temperature limitation
Line no.
Operating line
932
Room temperature limitation
The "Room temperature limitation" function makes it possible to deactivate the cooling
circuit pump if the room temperature falls by more than the preset difference below the
effective room temperature setpoint (with summer compensation, 920).
The heating circuit pump will be activated again as soon as the room temperature
returns to a level below the current room temperature setpoint.
During the time the "Room temperature limitation" function is active, no cooling request
is sent to the source.
The function is deactivated in the following situations:
•
No room temperature sensor
•
"Room temp limitation" = ---
•
"Room influence" (928) = --- (pure weather compensation)
ON
TRKw-SDR
23
55
Z
10
TRKw
TRx
P
OFF
°C
TRx
Actual room temperature
TRKw Room temperature setpoint cooling
(incl. summer
compensation)
SDR
Room’s switching differential
P
Pump
t
Time
Mixing valve control
Line no.
Operating line
938
Mixing valve decrease
939
Actuator:type
2-position ¦ 3-position
940
Switching differential
2-pos
941
Actuator running time
945
Mixing valve in heating mode
Control ¦ Open
The refrigeration request from the mixing valve circuit to the source is reduced by the
preset value. The purpose of this reduction is to enable the mixing valve controller to
compensate for the variation in temperature caused by the source (2-position control).
Mixing valve cooling offset
2-position
Actuator:type
The controller drives the actuator with only one relay output. When the output delivers a
signal, the valve opens. When there is no signal, the valve closes automatically.
3-position
102/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
6 The settings in detail
28. September 2009