Oper
a
tin
g
line
Oper
a
tin
g
level
Func
tio
n
Defaul
t
val
ue
Min
Max
Unit
562
E
1. Phase off
05:00 00:00
24:00
hh:mm
563
E
2. Phase on
24:00 00:00
24:00
hh:mm
564
E
2. Phase off
24:00 00:00
24:00
hh:mm
565
E
3. Phase on
24:00 00:00
24:00
hh:mm
566
E
3. Phase off
24:00 00:00
24:00
hh:mm
576
E
Default values
No ¦ Yes
No
1
-
Time program 5 / DHW
600
E
Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo - Su
-
601
E
1. Phase on
06:00 00:00
24:00
hh:mm
602
E
1. Phase off
22:00 00:00
24:00
hh:mm
603
E
2. Phase on
24:00 00:00
24:00
hh:mm
604
E
2. Phase off
24:00 00:00
24:00
hh:mm
605
E
3. Phase on
24:00 00:00
24:00
hh:mm
606
E
3. Phase off
24:00 00:00
24:00
hh:mm
616
E
Default values
No ¦ Yes
No
-
Holidays heating circuit 1
642
E
Start
--.--
01.01
31.12
dd.MM
643
E
End
--.--
01.01
31.12
dd.MM
648
E
Operating level
Frost protection ¦ Reduced
Frost protection
-
Holidays heating circuit 2
652
E
Start
--.--
01.01
31.12
dd.MM
653
E
End
--.--
01.01
31.12
dd.MM
658
E
Operating level
Frost protection ¦ Reduced
Frost protection
-
Holidays heating circuit P
662
E
Start
--.--
01.01
31.12
dd.MM
663
E
End
--.--
01.01
31.12
dd.MM
668
E
Operating level
Frost protection ¦ Reduced
Frost protection
-
Heating circuit 1
710
E
Comfort cooling setpoint
20.0
Operating line 712 Operating line 716 °C
712
E
Reduced setpoint
19
Operating line 714 Operating line 710 °C
714
E
Frost protection setpoint
10.0
4
Operating line 712 °C
716
F
Comfort setpoint max
35.0
Operating line 710 35
°C
720
E
Heating curve slope
0.8
0.10
4.00
-
721
F
Heating curve displacement
0.0
-4.5
4.5
°C
726
F
Heating curve adaption
Off ¦ On
Off.
-
730
E
Summer/winter heating limit
18
−
−
−
/ 8
30
°C
732
F
24-hour heating limit
-3
−
−
−
/ -10
10
°C
740
I
Flow temp setpoint min
8
8
Operating line 741 °C
741
I
Flow temp setpoint max
50
Operating line 740 95
°C
750
F
Room influence
20
−
−
−
/ 1
100
%
760
F
Room temperature limitation
1
−
−
−
/ 0.5
4
°C
770
F
Boost heating
−
−
−
−
−
−
/ 0
20
°C
780
F
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
48/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
5 Handling
28. September 2009