Oper
a
tin
g
line
Oper
a
tin
g
level
Func
tio
n
Defaul
t
val
ue
Min
Max
Unit
6046 I
Function input H2
None ¦ Optg mode change HCs+DHW ¦ Optg mode
changeover HCs ¦ Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Heat
request 10V ¦ Dewpoint monitor ¦ Flow temp setp incr
hygro ¦ Refrigeration request ¦ Refrigeration request 10V ¦
Pressure measurement 10V ¦ Rel room humidity 10V ¦
Room temp 10V ¦ Release swimming pool ¦ Swi-on
command HP stage 1 ¦ Swi-on command HP stage 2
Optg mode changeover HCs+DHW
-
6047 I
Contact type H2
NC ¦ NO
NO
-
6048 I
Function value contact H2
30
0
130
°C
6049 I
Voltage value 1 H2
0
0
10
V
6050 I
Function value 1 H2
0
-100
500
-
6051 I
Voltage value 2 H2
10
0
10
V
6052 I
Function value 2 H2
100
-100
500
-
6070 I
Function output UX
None ¦ Source pump Q8/fan K19 ¦ Collector pump Q5 ¦
Solar pump buffer K8 ¦ Solar pump ext exch K9
¦ Solar
pump swi pool K18
¦ HP setpoint ¦ Output request ¦ Heat
request ¦ Refrigeration request
None
-
6070 I
Function output UX
None ¦ Source pump Q8/fan K19 ¦ DHW pump Q3 ¦ DHW
intern circ pump Q33 ¦ Instant DHW heater Q34 ¦ Collector
pump Q5 ¦ Collector pump 2 Q16 ¦ Solar pump buffer K8 ¦
Solar pump ext exch K9 ¦ Solar pump swi pool K18 ¦ Heat
circ pump HC1 Q2 ¦ Heat circ pump HC2 Q6 ¦ Heat circ
pump HCP Q20 ¦ HP setpoint ¦ Output request ¦ Heat
request ¦ Refrigeration request
None
-
6071 I
Signal logic output UX
Standard ¦ Inverted
Standard
-
6072 I
Signal output UX
0..10V ¦ PWM
0..0.10V
-
6075 I
Temp value 10V UX
100
5
130
°C
6097 F
Sensor type collector
NTC* ¦ Pt 1000
1
1
2
-
6098 F
Readjustm collector sensor
0
-20
20
°C
6099 F
Readjustm coll sensor 2
0
-20
20
°C
6100 F
Readjustm outside sensor
0.0
-3.0
3.0
°C
6110 F
Time constant building
20
0
50
h
6120 F
Frost protection for the plant
Off ¦ On
On.
-
6135 F
Air dehumidifier
Off ¦ On
Off.
-
6136 F
Release air dehumidifier
24h/day ¦ Time progr HC ¦ Time program 5
24h / day
-
6137 F
Air dehumidifier r.h. ON
55
0
100
%
6138 F
Air dehumidifier r.h. SD
5
2
50
%
6200 F
Save sensors
No ¦ Yes
No
-
6201 F
Reset sensors
No ¦ Yes
No
-
6204 F
Save parameters
No ¦ Yes
No
-
6205 F
Reset to default parameters
No ¦ Yes
No
-
6212 I
Check no. heat source 1
-
0
199999
-
6)
4)
6)
6)
68/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
5 Handling
28. September 2009