6.4
time programs
For the heating circuits and DHW heating, a number of switching programs are
available. They are activated in Automatic mode and control the change of the
temperature levels (and the associated setpoints) via the selected switching times.
The switching times can be set in a combined way, either commonly for several days,
or separately for individual days. The preselection of groups of days like for instance
Mo...Fr and Sa...Su that use the same switching times simplifies setting of the switching
programs.
Entering the switching
times
Switching points
Line no.
Operating line
HC1
HC2 3/HCP 4/DHW 5
500 520 540 560 600
Preselection
Mo - Su
Mo - Fr
Sa - Su
Mo - Su
501 521 541 561 601
1. Phase on
502 522 542 562 602
1. Phase off
503 523 543 563 603
2. Phase on
504 524 544 564 604
2. Phase off
505 525 545 565 605
3. Phase on
506 526 546 566 606
3. Phase off
Standard program
Line no.
Operating line
516, 536, 556, 576,
616
Default values
No
Yes
All time programs can be reset to their default settings. Each time program has its own
operating line to make the reset.
In that case, individual settings will be lost!
6.5
Holidays
Line no.
Operating line
HC1
HC2 HC3P
642 652 662
Start
643 653 663
End
648 658 668
Operating level
Frost protection
Reduced
The holiday program is used to switch the heating circuits to a selectable operating
level according to calendar dates.
Important
•
The holiday program can only be used in "Automatic" mode
84/258