Optimum start / stop control is possible with or without room temperature sensor.
0
24
23
58
Z
02
Xein
Xaus
TRx
TRw
ZSP
1/4 °C
Xein
Switch-on time shifted forward in time
Xaus
Switch-off time shifted forward in time
ZSP
Time program
TRx
Actual room temperature
TRw
Room temperature setpoint
Raising the Reduced setpoint
Line no.
Operating line
HC1
HC2
HCP
800
1100
1400
Reduced setpoint increase start
801
1101
1401
Reduced setpoint increase end
The function is used primarily in connection with heating systems with
only
little spare
capacity (e.g. low-energy houses). In such cases, the heating up time at low outside
temperatures would be too long. When the Reduced setpoint is raised, the rooms are
prevented from cooling down excessively, thus shortening the heating up time when
changing to the nominal setpoint.
23
58
Z
06
-15
-5
TR
TRK
TAgem
TRwA2
TRwA1
TRR
TRwA1 Reduced setpoint increase start
TRwA2 Reduced setpoint increase end
TRK
Comfort cooling setpoint
TRR
Reduced room temperature setpoint
TAgem Composite outside temperature
Overtemp prot pump heating circuit
Line no.
Operating line
HC1
HC2
HCP
820
1120
1420
Overtemp prot pump heating circuit
In the case of heating plants with pump heating circuits, the flow temperature of the
heating circuit can be higher than the flow temperature called for by the heating curve,
the reason being higher requests from other heat consumers (mixing heating circuit,
DHW charging, external heat demand), or a parameterized minimum heat source
temperature. As a result of this too high flow temperature, the pump heating circuit
would assume excessive temperatures.
Function "Overtemperature protection for pump circuits" ensures that the energy supply
for pump heating circuits corresponds to the demand from the heating curve by
activating / deactivating the pump.
92/258
Siemens Switzerland Ltd
User manual RVS61.843, RVS41.813
CE1U2355en_02
HVAC Products
6 The settings in detail