Operating instructions
Œ•Ž
29
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Switching INDIVIDUAL ZONE OFF/ON,
continued
Switching ON an
individual zone
The method used to switch the zone OFF have no impact on the steps required to switch the
zone ON.
Perform the following steps to switch a zone ON:
Step
Action
Result / Comment
1
Press
button
<Isolation>
Isolation messages appear on the
display
2
Use the scroll keys to
select the
zone
to be switched ON
The zone selected is displayed in-
versely
3
Press
softkey
<Functions for
sel. message..>
4
Press
softkey
<ON/OFF functions>
The sub-menu is displayed
5
Press
softkey
<Zone -> ON>
Implementation messages
'
Implementing ...
'
- and -
'
Implemented
'