Operating instructions
Œ•Ž
45
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
continued
Switching on
'Test condition'
operating mode
Perform the following steps to set
all
the detector zones of a LINE to 'Test condition' operating
mode:
Step
Action
Result / Comment
1
Navigate
to the LINE you want us-
ing:
<Operate..>
t
<Browse..>
t
< HARDWARE level..>
t
<Lower level
¯
>
t
(
<Lower level
¯
>
)
t
<More functions..>
t
<More functions..>
(The number of 'Lower level' com-
mands to be executed depends on
the type of line board)
The line functions are displayed
2
Press
softkey
<Detector line -> TEST>
Implementation messages
'
Implementing ...
' - and -
'
Implemented
'
Ending 'Test
condition'
operating mode
Perform the following steps to end 'Test condition' operating mode for
all
detector zones of a
LINE:
Step
Action
Result / Comment
1
Navigate
to the LINE you want us-
ing:
<Operate..>
t
<Browse..>
t
< HARDWARE level..>
t
<Lower level
¯
>
t
(
<Lower level
¯
>
)
t
<More functions..>
t
<More functions..>
(The number of 'Lower level' com-
mands to be executed depends on
the type of line board)
The line functions are displayed
2
Press
softkey
<Detector line -> TEST OFF>
Implementation messages
'
Implementing ...
' - and -
'
Implemented
'