Instruction manual AQ101, AQ101D, AQ110P, AQ01
32 (48
)
6
T
ROUBLE SHOOTING
6.1
AQ101,
AQ101D,
AQ110P
ARC FLASH PROTECTION RELAYS
Led:
State
Error led
state
IF relay
state
Possible issues
Binary input
or Sensor
Blink
ON
OFF
- Bad connection between sensors or other devices
connected to BI
- Damaged wire
- Unit amount or sensor amount changed
Others than
error
OFF
ON
OFF
- Dip switch settings changed or current pick-up
potentiometer value changed > 20% (AQ110P only)
Power
OFF
ON
OFF
- Internal voltage too low. Auxiliary supply voltage may
be less than specified
Blink
OFF
OFF
- Input channels (binary inputs and sensor channel)
connection verification. See set button function in
chapter 3.1.3.
All
OFF
OFF
OFF
- Auxiliary supply voltage not connected.
Table 6-1: troubleshoot function description.
Summary of Contents for Arcteq AQ01
Page 1: ...INSTRUCTION MANUAL AQ101 AQ101D AQ110P AQ01 ...
Page 44: ...Instruction manual AQ101 AQ101D AQ110P AQ01 44 48 ...
Page 45: ...Instruction manual AQ101 AQ101D AQ110P AQ01 45 48 ...
Page 46: ...Instruction manual AQ101 AQ101D AQ110P AQ01 46 48 9 2 AX001 CONNECTION FIBER ...
Page 47: ...Instruction manual AQ101 AQ101D AQ110P AQ01 47 48 9 3 AQ01 ARC FLASH SENSOR ...